11-715-016A
NAC
75CD 75CD 75CD 75CD
(E) (R) (R) (R)
EXISTING FIRE ALARM
CONTROL PANEL ® BUILDING LOBBY
NOTE:
CONTACT FIRE ALARM CONTRACTOR
ENGINEERING SYSTEM TECNOLOGY (EST)
FOR ANY IMPROVEMENT /ADDITION OR
MODIFICATION OF EXISTING SYSTEM.
DUAL TELCO LINES
CONNECTED VIA
DACT TO A REMOTE
SUPERVISING STATION
F AC P (EXISTING)
AC POWER (120V 20A MAX.)
2 #12 THWN IN 1/2" C
CIRCUIT R1 -53
(EXISTING)
EXISTING ENCLOSURE GROUNDED
Reproduced by HILTI, Inc. Courtesy of
FIRESTOP SYSTEMS Underwriters Laboratories, Inc.
System No, C -AJ -1388
F Rating - 2 Hr
T Rating - 0 Hr
75CD 75CD 15/75CD 15/75CD
(R) (N) (N) (N)
REA OF WORK IS SHOWN IN FIRE
1.
DEVICES IN BUILDING NOT SHOWN.
EOL
WIRE LEGEND: CLASS B WIRING
A — (INITIATING) 2 CONDUCTOR #16 SOL CU SHIELDED FPLR
B — (NOTIFICATION — HORN /STROBE) 2 CONDUCTOR #14 SOL CU FPLR
OTHERWISE USE APROVED FPLP WIRE IN PLENUM SPACES.
NOTE:
FOR EXACT LOCATION AND
QUANTITY OF FIRE ALARM
SYSTEM DEVICES, REFER TO
FLOOR PLAN DRAWING.
NOTE:
(E) — EXISTING FA DEVICES
(N) — NEW FA DEVICES
(R) — RELOCATED FA DEVICES
GROUND FLOOR
FIRE ALARM SYSTEM RISER DIAGRAM
SCALE: N.T.S.
"I ,SS I fl'
C US
5
A ?`'
1. Floor or Wall Assembly Min 4 -1/2 in. thick reinforced lightweight or normal weight
(100 -150 pcf) concrete. Wall may also be constructed of any UL Classified
Blocks *. Max area of opening 224 sq in. with max dimension of 32 in.
See Concrete Blocks (CAZT) in the Fire Resistance Directory for names of C1P16FfAturers.
2. Conduit One or more nom 4 in diam (or smaller) steel electrical metallic tubing or steel
conduit to be installed either concentrically or eccentrically within the firestop system. The
space between conduits or tubes shall be min 0 in. (point contact) to max 1/2 in. The
annular space between the conduit or tube and periphery of opening shall be min 0 in. (point
contact) to max 2 -3/4 in. Conduit or tube to be rigidly supported on both sides of floor or
wall assembly.
Conduit — Nom 4 in. diem (or smaller) steel electrical metallic conduit or steel conduit.
3. Fill, Void or Cavity Material * — Foam Min 5 in. thickness of fill material applied within the
annulus, extending 1/2 in. above the top surface of the floor or both surfaces of wall and
overlapping the concrete 1/2 in. on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- CP 620 Fire Foam
*Bearing the UL Classification Mark
System No, W -L -1095
F Ratings - 1 & 2 Hr (See Item 1)
T Ratings - 1 & 2 Hr (See Item 3)
L Rating At Ambient - Less Than 1 CFM /Sq Ft
L Rating At 400 F - 4 CFM /Sq Ft
FIRESTOP SYSTEMS
1�SSIFj�D
C US
FONT VIEW SECTION A -A
1. Wall Assembly — The 1 or 2 hr fire —rated gypsum wallboard /stud wall
assembly shall be constructed of the materials and in the manner
described in the individual U300 or U400 Series Wall and Partition
Designs in the UL Fire Resistance Directory and shall include the
following construction features:
A. Studs — Wall framing may consist of either wood studs or steel
channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced
16 in. OC. Steel studs to be min 2 -1/2 in. wide and spaced max 24 in.
OC.
B. Wallboard, Gypsum* — 5/8 in. thick, 4 ft wide with square or tapered
edges. The gypsum wallboard type, thickness, number of layers,
fastener type and sheet orientation shall be as specified in the
individual U300 or U400 Series Design in the UL Fire Resistance
Directory. Max size of opening 2 -5/8 in. by 18 in. The hourly F Rating
of the firestop system is equal to the hourly fire rating of the wall
assembly in which it is installed.
2. Electric Metallic Tubing (EMT) — One or more nom 1 in. diam steel
electric tubing. The annular space shall be min 1/2 in. to a max 1 in.
Conduit to be rigidly supported on both sides of wall assembly.
3. Fill, Void or Cavity Material* — Sealant — For 2 hr F Rating, min 1 -1/4 in.
thickness of fill material applied within the annulus, flush with both
surfaces of wall. For 1 hr F Rating, min 5/8 in. thickness of fill material
applied within the annulus, flush with both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI, Inc. — FS —ONE Sealant
*Bearing the UL Classification Marking
PENETRATION DETAILS EIRE ANDZOR SMOKE RATED WALE OR FLOOR.
SCALE: N.T.S.
FIRE
ALARM LEGEND
FACP
EXISTING ADDRESSABLE FIRE ALARM CONTROL PANEL
(LOCATED AT BUILDING LOBBY)
®
MANUAL PULL STATION
O
SMOKE DETECTOR
CO
CARBON MONOXIDE DETECTOR
p
HEATE DETECTOR
G
SMOKE DUCT DETECTOR W/ RELAY
M<
HORN /STROBE MULTICANDELA, SYSTEM SENSOR P2R
®
STROBE LIGHT MULTICANDELA, SYSTEM SENSOR SR
Q
SWITCH (BY OTHERS)
TAMPER SWITCH (BY OTHERS)
V)
ca
H~¢
(n
Ir
v
L I
°
°
W
W
(�
(f) ° Ld
Ld
_°
J
Q
a_
w
Ld
V)
0a_
Qx
0
U)
O
�
Z w
w
�
~
I
o
o
¢°
��
g
SEQUENCE
0
Z
a
da
Q
0
nf °
J°
\
Q
OF
�Q
�4
Cn
z
OPERATIONS
Q
Cn
1-
oQ
oQ
Q
�a
Imo-
Z
Z
Z
E
�
F-
ov
° �
0-
(wig
Cn
Cn
cr)
PULL STATION
DETECTORS (AREA)
t
F SPKLR FLOW SW
M
Mir
VALVE TAMP SW
AC POWER FAILURE
LOW BATTERY
OPEN FAULT
GROUND FAULT
NAC SHORT FAULT
MISSING PHONE LINE
DUCT SMOKE DET
FIRE
ALARM LEGEND
FACP
EXISTING ADDRESSABLE FIRE ALARM CONTROL PANEL
(LOCATED AT BUILDING LOBBY)
®
MANUAL PULL STATION
O
SMOKE DETECTOR
CO
CARBON MONOXIDE DETECTOR
p
HEATE DETECTOR
G
SMOKE DUCT DETECTOR W/ RELAY
M<
HORN /STROBE MULTICANDELA, SYSTEM SENSOR P2R
®
STROBE LIGHT MULTICANDELA, SYSTEM SENSOR SR
gFLOW
SWITCH (BY OTHERS)
TAMPER SWITCH (BY OTHERS)
SYSTEM OVERVIEW:
1) SYSTEM IS SINGLE STANDARD SCL LOOP, NFPA 4 STYLE.
2) SYSTEM IS A REMOTE SUPERVISING STATION.
3) SYSTEM IS AN ADDRESSABLE POWER LIMITED SYSTEM.
4) NOTIFICATION APPLIANCE CIRCUITS ARE STYLE Y, CLASS B.
5) USE 2 CONDUCTORS #14 (MIN.), JACKETED FIRE POWER LIMITED (FPL) WPW OR
EQUIVALENT FOR THE NOTIFICATION CIRCUITS.
6) NOTIFICATION APPLIANCES MAXIMUM CURRENT PER CIRCUIT IS 2.5 AMPS.
7) FOR SLC LOOP, USE 2/18 TWISTED WIRE MIN.
8) ACOUSTICAL CEILING AND GWB CEILING THROUGHOUT THE SPACE.
9) NOTIFICATION CIRCUIT TO BE 15 DB ABOVE AMBIENT NOISE IN ALL AREAS.
10) DETECTORS MUST BE PLACED 3 FEET AWAY MINIMUM FROM ANY AIR DIFFUSER.
11) ELECTRICAL /FIRE ALARM CONTRACTOR SHALL SUBMIT A COMPLETE SET OF
FIRE ALARM SHOP DRAWINGS TO ARCHITECT /ENGINEER FOR APPROVAL
BEFORE THE BEGINNING OF WORK. THIS SET SHALL INCLUDE A COMPLETE
RISER DIAGRAM, POINT TO POINT CONNECTION DIAGRAM, DEVICES ADDRESS
LIST, BACK —UP BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS AND
SPEC SHEETS.
SPECIFICATIONS:
1) ALL EQUIPMENT SHALL BE UL APPROVED.
2) ALL FIRE ALARM EQUIPMENT FOR THIS PROJECT SHALL BE RATED FOR POWER
LIMITED.
3) CABLE SIZE SHALL COMPLY WITH ARTICLE 760 -71 AND THE CABLE INSTALLATION
SHALL COMPLY WITH THE SEPARATION AND USE OF CONDUCTORS AND CABLES AS
SPECIFIED IN ARTICLES 760 -54 AND 760 -61 OF THE NEC.
4) BUILDING WIRING SHALL SPECIFICALLY CONFORM WITH THE NEC ARTICLE 760 PART
C FOR POWER LIMITED FIRE PROTECTION SIGNAL CIRCUITS WITH EMPHASIS ON
ARTICLE 760 -52(b) ON POWER LIMITED WIRING METHODS AND MATERIALS.
5) MINIMUM WIRE SIZE:
a) #18 AWG COPPER (2/18 FPLR TWISTED & SHIELDED) FOR INITIATING DEVICES
LOOP.
b) #14 AWG COPPER (2/14 FPL) FOR NOTIFICATION DEVICES CIRCUIT.
6) ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR
ENVIRONMEMNTAL AIR SHALL BE PLENUM RATED, FPLP, AS PER NEC ARTICLE 760 -61.
7) ALL ALARM NOTIFICATION DEVICES SHALL BE AUDIBLE AND VISUAL (UNLESS
SPECIFIED) AND SHALL BE VIA HORN STROBE COMBINATION DEVICES. STROBES
SHALL BE CLEAR XENON TYPE, WITH INTENSITY OF 75 CANDELAS, U.O.N., AS PER
ARTICLE 4.28(1) THROUGH (5) OF THE ADA GUIDELINES AND AS PER ARTICLE 4.28.2
& 4.28.3 OF THE FLORIDA ACCESIBILITY CODE.
8) HORN STROBES AND STROBE DEVIECS SHALL BE PLACED 80" (6' -8 ") ABOVE THE
HIGHEST FLOOR LEVEL WITHIN THE SPACE OR 6" BELOW THE CEILING, WHICHEVER
IS LOWER AS PER ADA GUIDELINES AND ARTICLE 4.28(6) OF THE NFPA -72.
9) MANUAL INITIATING DEVICES SHALL BE PLACED 48" (4') ABOVE FINISH FLOOR.
10) MAXIMUM OVER— CURRENT PROTECTION FOR OFIRE ALARM PANEL SHALL BE 20 AMPS.
fa a
1, n' a dt?a.1)
r' 1
c sR't�t'KDXI,��.7
� k o
I, 6,�.
"" FG ENGINEERS, INC.
} Frank Garcia, P.E.
t�
.'+ r c # 60778
` 3001 PONCE DE LEON BLVD. SUITE -101.
CORAL GABLES, FLORIDA 33134
PH: (305) 441 -5892, FAX: (305) 441 -5893
fE-mail: fgarciaf @bellsouth.net C -A. #:26052
I
INTERIOR RENOVATION FOR:
I
HAND & STONE Massage & Facial Spa
7301 SW 57th CT., SUITE 170, SOUTH MIAMI, FL 33143
FORM GROUP, INC.
4300 SW 73 AVE., SUITE 106, MIAMI, FL 33155
TEL. 305.443.4244 EX. 305.443.3338
CORPORATE LICENSE No. AA- 26000668
ARCHITECT OF RECORD: OMAR MORALES
rvo NU TiiHE AR ' D AT,HI CTGTENAIrD !S F No. AR, `3F F-1 51
TITLE:
SCALE:
PROJECT N0.
11 -606
DATE:
JUNE 3. 12011
REVISIONS:
DRAWING NO.:
E! 3