Loading...
11-715-015TYPE: CUTLER -+1AM M ER PANELBOARD PANEL 7) �� MAIN BUS: 225 A SERVICE: SHOWr4 MAIN: M.L.O. VOLTAGE: 120/208V, 30, 4W EXISTING @ MASSAGE ROOM 6 RATING: 22 KAIC MOUNTING: SURFACE #) ENCLOSURE: NEMA1 M o o o '=1 REMARKS � MODEL REFRIGERATOR � REMARKS uj N� o o o = 10,860 VA 60 2 12,960 1" #6 AHU -1 (10 KW) (EXISTING) 8 TIMER CU -1 (EXISTING) (7) #6 1" 8,160 2 60 = 21,120 VA SINGLE POLE TOGGLE SWITCH 3 4 30 2 6,000 3/4" #8 W/H #1 (7) UNV ABOVE BATH VAN MOUNT AT 8' VAN A.F.F. ITY DRYER #10 1/2" 5,000 2 30 1 -- 7 8 E O 20 1 1,500 1/2" #12 MICROWAVE 9 10 WASHER #12 1/2" 1,500 1 20 1 - 20 1 1,200 1/2" #12 REFRIGERATOR 11 12 GENERAL LIGHTS #12 1/2" 900 1 20 H 20 1 1,260 1/2" #12 13REAKROOM RECEPT (3) 13 14 GENERAL LIGHTS #12 1/2" 900 1 20 INCANDESCENT 2 X 9W T12 2 20 1 1,800 1/2" #12 GENERAL RECEPT (3) 15 16 GENERAL LIGHTS #12 1/2" 1,000 1 20 20 1 1 1,620 1/2" #12 GENERAL RECEPT (3) 17 18 GENERAL LIGHTS #12 1/2" 1,200 1 20 20 1 1,620 1/2" #12 GENERAL RECEPT (3) 19 20 GENERAL LIGHTS #12 1/2" 900 1 20 20 1 1,620 1/2" #12 GENERAL RECEPT (3) 21 22 SIGN (5) #12 1/2" 800 1 20 20 1 900 1/2" #12 GENERAL RECEPT 23 24 TIME CLOCK #121/2" 300 1 20 20 1 1,620 1/2" #12 GENERAL RECEPT 25 26 SPACE 20 1 600 1/2" #12 GENERAL RECEPT 27 28 SPACE 20 1 360 1/2" #12 BATHROOM RECEPT 29 30 SPACE 20 1 720 1/2" #12 TEL. /SERVER RECEPT. 31 32 SPACE SPACE 33 34 SPACE SPACE 35 36 SPACE SPACE 37 38 SPACE SPACE 39 40 SPACE SPACE 41 42 SPACE SUBTOTAL I I SUBTOTAL WATER HEATER = 6,000 VA 0 DRYER = 5,000 VA A/C LOAD: WASHER = 1,500 VA MODEL REFRIGERATOR - 1,200 VA AHU'S + CU'S 0 1007. MICROWAVE = 1,500 VA = AHU #1 + CU #1 RECEPTACLE LOAD = 10,860 VA = 12,960 VA + 8,160 VA LIGHTING LOAD = 4,900 VA = 21,120 VA SIGN = 800 VA 8 TIMER = 300 VA A/C LOAD (LARGEST) = 21,120 VA CONNECTED LOADS = 32,060 VA -- A/C LOAD (LARGEST) = 21,120 VA SINGLE POLE TOGGLE SWITCH TOTAL LOADS = 53,180 VA BATHROOM VANITY LIGHT ADD 10% FUT. LOADS = 5,300 VA - -- TOTAL EST. LOADS = 58,480 VA UNV TOTAL DEMAND CURRENT: 58,480 VA / 208V 3PH= 162.5 AMPS FEEDER: 4 #4/0 THWN CU, 1#4 THWN CU (G) IN 2" C (FULL NEUTRAL) (EXISTING) (1) EXISTING TO REMAIN. (2) PROVIDE SHUNT -TRIP. (3) PROVIDE GFI PROTECTION. (4) NON CONCURRENT LOADS. (5) THROUGH TIMER - PHOTOCELL (6) LOCKED OUT DEVICE. (7) SIZE OCPD AS PER MANUFACTURER NAMEPLATE. CEILING FLOOR STUB OUT 6" ABOVE CEILING, EXTEND CONDUIT TO NEAREST HALLWAY CEILING SPACE. PROVIDE PLASTIC INSULATING BUSHING. PROVIDE PULL WIRE. WIRES AND CABLES TO BE RATED FOR USE IN PLENUM SPACES. (--:1 r-D T 1 -D i -71 T r-_1 TV 60" Ill G. S SECURITY DEVICES SPEAKER (BY OTHERS) 1 (BY OTHERS) J314" CONDUIT CONCEALED IN WALL AND CEILING SPACES. PROVIDE PULL STRING (TYP.) TYPICAL PHONE /DATA OUTLET BOX, 4"x4", 1 GANG, 2112" DEEP EACH. [ 18" PROVIDE PULL WIRE, NOTE: FOR RETURN AIR PLENUMS USE PLENUM RATED CABLE OR NON -RATED CABLE IN EMT CONDUIT. (REFER TO MECHANICAL PLANS) 314" PLYWOOD BACKBOARD WITH 1 HOUR RETARDANT PAINT. TELEPHONE/ 1#6 CU GROUND CAN/ SECURITY BOARD CABINET OFFICE EXISTING JUNCTION BOXES FOR TELEPHONE POINT OF ENTRANCE TO TENANT SPACE FROM MAIN TELEPHONE ROOM. REFER TO PLAN FOR ACTUAL LOCATION. (FIELD VERIFY) EXTEND CONDUIT AND WIRES ABOVE CEILING TO PROPOSED TELEPHONE BOARD CABINET REFER TO PLAN FOR ACTUAL LOCATION. TELEPHONE /DATA /POWER /SECURITY OUTLET BOX DETAIL NTS EMERGENCY LIGHT WITH BATTERY BACK -UP F LIGHT WITH TERY BACK ---UP HT -LITE /EMERGENCY JIMINATION J ERAL 1MINATION SWITCH NOTE: CONNECT EXIT, EMERGENCY AND NIGHT LIGHTS AHEAD OF SWITCH. EMERGENCYZEXIT LIGHT DETAIL SCALE: N.T.S. LIGHT FIXTURE SCHEDULE ' LAMPS 0 TYPE SYMBOL DESCRIPTION MANUFACTURER CATALOG NUMBER MODEL NO LOAD VOLT REMARKS A Q WALL SCONCE WESTMORE LIGHTING PROVIDED BY OWNER - -- -- -- UNV DATA OUTLET 8 TELEPHONE /DATA OUTLET WALL SCONCE WESTMORE LIGHTING PROVIDED BY OWNER - -- -- -- UNV SINGLE POLE TOGGLE SWITCH C 2 BATHROOM VANITY LIGHT WESTMORE LIGHTING PROVIDED BY OWNER - -- - -- UNV ABOVE BATH VAN MOUNT AT 8' VAN A.F.F. ITY D O RECESSED DOWNLIGHT LIGHTOLIER 1102P1 (FRAME -IN KIT) - -- 1 -- UNV ANODIZED ALUMINUM REFLECTOR, WHITE TRIM E O MINI PENDANT LIGHT FIXTURE PROGRESS LIGHTING PROVIDED BY OWNER - -- 1 -- UNV EXISTING TO REMAIN F 0 RECESSED WALL WASHER LIGHTOLIER 1102P1 (FRAME -IN KIT) - -- 1 - UNV ANODIZED ALUMINUM REFLECTOR, WHITE TRIM G ELECTRICAL MOTOR ❑ CCTV CAMERA 2X2 ACRILIC LENS FLOURESCENT LIGHT FIXTURE - - -- PROVIDED BY GC - -- -- -- UNV H SIGN (BY OTHERS) - - -- PROVIDED BY VENDOR I > WALL MOUNTED TWIN -HEAD EMERGENCY LIGHTING UNIT LIGHTOLIER E2 SERIES / E2236LT9W INCANDESCENT 2 X 9W T12 2 9W UNV EMERG BATT PACK X e THERMOPLASTIC EXIT SIGN COOPER LIGHTING ELX7- X- 70- 00- WH -R -SD LED INCLUDED -- -- UNV WHITE TRIM RED LETTERS EXISTING ELECTRICAL ROOM (GROUND FL.) F_ L_ - �- -- - - - -- --- - - - --I o - -S� --1-------------I- I- i 1� 1 F/- F"_ MAINZ STING F 4 / ( I ` J o L Lo� 1200 AMP I `- 120/208V i O I IJ 1 O J I O L 0 T I I T ----- I--- - - - - -� - - - - -� L L - - -- -I 2 ELECTRICAL ROOM SCALE: N.T.S. - FOR REFERENCE ONLY BACK TO BACK TO MAIN 1 OF 4 INSIDE ELECTRICAL ROOM (LOCATED AT PARKING GARAGE ENCLOSED AREA BELOW THE ACCESS RAMP). I- O NOTES: EXISTING GUTTER. �2 EXISTING METER FOR OTHER TENANT SPACE. �3 EXISTING DISCONNECT SWITCH FOR OTHER TENANT SPACE. ® EXISTING METER. SPACE #170 0 EXISTING DISCONNECT SWITCH 3P/225A FOR SPACE #170 IN NEMA 3R ENCLOSURE. FEEDER SCHEDULE: n EXISTING GROUNDING SYSTEM EXISTING FEEDERS IN 2" C UNDERGROUND TO EXISTING TENANT SPACES. 3❑ 4 #4/0 THWN CU, 1 #4 THWN CU (G) IN 2" C. (EXISTING) "TENANT -170" EXISTING PANEL "TENANT -170" 30 225A 120/240V NEMA 1 I I DEMOLITION NOTES 1. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE WORK SITE PRIOR TO BID AND BECOME FAMILIAR WITH THE SCOPE OF THE WORK INVOLVED UNDER THIS CONTRACT. 2. SALVAGEABLE MATERIALS AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE OWNER AFTER REMOVAL FROM THEIR PRESENT LOCATION. MATERIALS AND EQUIPMENT TO BE REUSED SHALL BE TREATED WITH CARE AND REINSTALLED AS SHOWN. 3. DISCONNECT AND REMOVE EXISTING WIRING FROM ELECTRICAL ROOM PROVIDING TEMPORARY POWER TO THE SPACE AND ASSOCIATED CONDUITS (INSIDE TENANT SPACE), INCLUDING JUNCTION BOXES AND REMOVE OFFSITE PROPERLY. 4. UNLESS OTTHERWISE NOTED, DISCONNECT AND REMOVE ALL EXISTING LIGHTING, RECEPTACLES, JUNCTION BOXES, DISCONNECT MEANS, DATA, SECURITY, CONDUITS AND ALL ASSOCIATED WIRING AND REMOVE OFFSITE PROPERLY. 5. NOT USED. 6. ALL WORK COMPLETED OR OTHERWISE, SHALL BE PROPERLY PROTECTED AT ALL TIMES. CONTRACTORS SHALL FOLLOW ALL ACCEPTED METHODS OF SAFETY PRACTICE AND PROVIDE ALL FENCE, BARRICADES, ETC. AS MAY BE NEEDED TO PROTECT LIFE AND PROPERTY AND AS MAY BE REQUIRED BY AUTHORITIES HAVING JURISDICTION OVER THIS WORK. 7. CONTRACTOR SHALL REPAIR, AT HIS OWN COST, ANY DAMAGES TO THE PREMISES OR ADJACENT WORK CAUSED BY HIS OPERATION. 8. NO DEMOLITION INVOLVING EXTERIOR AND /OR OPENINGS SHALL BE PERFORMED UNLESS UNDER DIRECTION OF OWNER /ARCHITECT. 9. BEFORE COMMENCING DEMOLITION WORK, GENERAL CONTRACTOR SHALL SET UP A MEETING WITH ARCHITECT AND /OR STRUCTURAL ENGINEER FOR AUTHORIZATION. BEFORE ANY STRUCTURAL DEMOLITION CAN START, CONTRACTOR SHALL NOTIFY ARCHITECT AND /OR STRUCTURAL ENGINEER FOR AUTHORIZATION. 10. EXISTING CONDITIONS IDENTIFIED ARE AS BUILT. CONTRACTOR TO CONFIRM ALL EXISTING IN FIELD. CONTRACTOR TO REMOVE ALL EXISTING SYSTEMS, DEVICES, ETC. CONFIRM DETAILS IN FIELD WITH THE ARCHITECT. ELECTRICAL LEGEND: (� 120V DUPLEX RECEPTACLE 0 120V SINGLE RECEPTACLE F___ T­_ T T T 120V QUAD RECEPTACLE a 120V GFI DUPLEX RECEPTACLE 19L I 10 I IOJ LIL LIL LIL SPECIAL OUTLET V TELEPHONE OUTLET 3 DATA OUTLET TELEPHONE /DATA OUTLET L L� ® L -- - - - -- 1 SINGLE POLE TOGGLE SWITCH 3 2 $2 I- O NOTES: EXISTING GUTTER. �2 EXISTING METER FOR OTHER TENANT SPACE. �3 EXISTING DISCONNECT SWITCH FOR OTHER TENANT SPACE. ® EXISTING METER. SPACE #170 0 EXISTING DISCONNECT SWITCH 3P/225A FOR SPACE #170 IN NEMA 3R ENCLOSURE. FEEDER SCHEDULE: n EXISTING GROUNDING SYSTEM EXISTING FEEDERS IN 2" C UNDERGROUND TO EXISTING TENANT SPACES. 3❑ 4 #4/0 THWN CU, 1 #4 THWN CU (G) IN 2" C. (EXISTING) "TENANT -170" EXISTING PANEL "TENANT -170" 30 225A 120/240V NEMA 1 I I DEMOLITION NOTES 1. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE WORK SITE PRIOR TO BID AND BECOME FAMILIAR WITH THE SCOPE OF THE WORK INVOLVED UNDER THIS CONTRACT. 2. SALVAGEABLE MATERIALS AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE OWNER AFTER REMOVAL FROM THEIR PRESENT LOCATION. MATERIALS AND EQUIPMENT TO BE REUSED SHALL BE TREATED WITH CARE AND REINSTALLED AS SHOWN. 3. DISCONNECT AND REMOVE EXISTING WIRING FROM ELECTRICAL ROOM PROVIDING TEMPORARY POWER TO THE SPACE AND ASSOCIATED CONDUITS (INSIDE TENANT SPACE), INCLUDING JUNCTION BOXES AND REMOVE OFFSITE PROPERLY. 4. UNLESS OTTHERWISE NOTED, DISCONNECT AND REMOVE ALL EXISTING LIGHTING, RECEPTACLES, JUNCTION BOXES, DISCONNECT MEANS, DATA, SECURITY, CONDUITS AND ALL ASSOCIATED WIRING AND REMOVE OFFSITE PROPERLY. 5. NOT USED. 6. ALL WORK COMPLETED OR OTHERWISE, SHALL BE PROPERLY PROTECTED AT ALL TIMES. CONTRACTORS SHALL FOLLOW ALL ACCEPTED METHODS OF SAFETY PRACTICE AND PROVIDE ALL FENCE, BARRICADES, ETC. AS MAY BE NEEDED TO PROTECT LIFE AND PROPERTY AND AS MAY BE REQUIRED BY AUTHORITIES HAVING JURISDICTION OVER THIS WORK. 7. CONTRACTOR SHALL REPAIR, AT HIS OWN COST, ANY DAMAGES TO THE PREMISES OR ADJACENT WORK CAUSED BY HIS OPERATION. 8. NO DEMOLITION INVOLVING EXTERIOR AND /OR OPENINGS SHALL BE PERFORMED UNLESS UNDER DIRECTION OF OWNER /ARCHITECT. 9. BEFORE COMMENCING DEMOLITION WORK, GENERAL CONTRACTOR SHALL SET UP A MEETING WITH ARCHITECT AND /OR STRUCTURAL ENGINEER FOR AUTHORIZATION. BEFORE ANY STRUCTURAL DEMOLITION CAN START, CONTRACTOR SHALL NOTIFY ARCHITECT AND /OR STRUCTURAL ENGINEER FOR AUTHORIZATION. 10. EXISTING CONDITIONS IDENTIFIED ARE AS BUILT. CONTRACTOR TO CONFIRM ALL EXISTING IN FIELD. CONTRACTOR TO REMOVE ALL EXISTING SYSTEMS, DEVICES, ETC. CONFIRM DETAILS IN FIELD WITH THE ARCHITECT. ELECTRICAL LEGEND: (� 120V DUPLEX RECEPTACLE C� 120V SINGLE RECEPTACLE 120V DUPLEX RECEPTACLE, UC 120V SINGLE RECEPTACLE, UC 120V QUAD RECEPTACLE a 120V GFI DUPLEX RECEPTACLE UP 120V GFI DUPLEX RECEPTACLE WITH COVER FOR WEATHER PROOF PROTECTION ® SPECIAL OUTLET V TELEPHONE OUTLET Q DATA OUTLET TELEPHONE /DATA OUTLET 120 -V DUPLEX FLOOR RECEPTACLE ® 120 -V QUAD, FLOOR RECEPTACLE DATA /TELEPHONE FLOOR OUTLET SINGLE POLE TOGGLE SWITCH 3 SINGLE POLE 3 -WAY TOGGLE SWITCH $2 TWO POLE 30A TOGGLE SWITCH EF EXHAUST FAN OT A/C THERMOSTAT S� SPEAKER 2' X 4' LAY -IN FLUORESCENT LIGHT FIXTURE El2' X 2' LAY -IN FLUORESCENT LIGHT FIXTURE EMERGENCY LIGHT FIXTURE, BATTERY BACKUP 8 EXIT LIGHT FIXTURE, BATTERY BACKUP F-Q VANITY /WALL MTD LIGHT FIXTURE Q HI -HAT, RECESSED LIGHT FIXTURE, U.O.N. ® RECESSED WALL WASHER E=P DISCONNECT SWITCH WP WEATHER PROOF DEVICE E EXISTING TO REMAIN ER EXISTING RELOCATED N NEW Q ELECTRICAL PANEL I� JUNCTION BOX FLEXIBLE CONDUIT /S ELECTRICAL MOTOR 04 CCTV CAMERA EXISTING EXISTING METER AND MAIN 1 OF 4 3P 225A DISC. SW. BELOW 1200 AMP FOR TENANT SPACE #170 30, 120/208 V , =, �-a EXISTING METER AND EXISTING DISC. SWITCH FOR SWITCHBOARD EXISTING TENANTS (TYP.) EXISTING SWITCHBOARD EXISTING ELECTRICAL ROOM EXISTING ELECTRICAL ROOM scnLe yr - V-0" - GENERAL NOTES 1. WIRING SHOWN ON PLANS IS SCHEMATIC AND INTENDED TO SHCW REQUIRED SWITCHING AND CIRCUITING. JUNCTION 9C,XFS AND FLEXiPLE CONNECTIONS ARE INDICATED. PROVIDE PROPER NUMBER OF WIRES IN EACH CONDUII AS REQUIRED BY INDICATED CIRCUITRY AND SWITCHING.'' ALL CIRCUIT FEEDERS AND DISCONNECTS SHALL BE SIZED BY N.E.C. 2. A (GREEN) INSULATED COPPER GROUND CONDUCTOR SHALL BE INSTAl_LED IN ALL RACEWAYS. 3. ALL BREAKERS SHALL BE "FULL SIZE ". NO TANDEM, PIGGY BACK, TWIN OR HALF SIZE BREAKERS WILL BE ACCEPTED. 4. ALL CIRCUIT FEEDERS AND, DISCONNECTS SHALL BE SIZED BY N.E.C. 5. CONTRACTOR IS TO VERIFYi CIRCUIT BREAKER, DISCONNECT SWITCH, STARTER AND FUSES SIZES WITH SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWING PRIOR TO PLACING ORDER AND PROVIDE EVERYTHING AS REQUIRED. 6. COORDINATE THE REQUIRED SIZE OF ALL CIRCUIT BREAKERS FEEDING EQUIPMENT (I.E. MOTORS, HVAC EQUIPMENT, ETC.) WITH APPROVED EQUIPMENT SHOP DRAWINGS AND OWNER'S REPRESENTATIVES PRIOR TO PLACING ORDER AND PROVIDE EVERYTHING AS REQUIRED. BRANCH CIRCUITS AND CIRCUIT BREAKERS SHALL BE SIZED PER THE EQUIPMENT NAME PLATE,THE MANUFACTURER'S RECOMMENDATIONS, AND PER THE N.E.C. 7. FOR EXACT LOCATION OF MECHANICAL EQUIPMENTS AND EQUIPMENT POINT OF CONNECTION, REFER TO MECHANICAL DRAWINGS AND MANUFACTURER'S SHOP DRAWINGS. 8. WHERE CONDUIT PENETRATES A FIRE RATED WALL, FLOOR,ETC., FIRESTOPPING SHALL BE PROVIDED. MEET ALL REQUIREMENTS FOR UL ASSEMBLY INVOLVED. PROVIDE FIRESTOPPING UL LISTED FOR ASSEMBLY AND /OR CONDUIT INVOLVED. SEAL SHALL BE FLUSH WITH FINISHED SURFACE, WATERTIGHT AND PAINTED TO MATCH SURROUNDING FINISH, COORDINATE WITH', OWNER. 9. PROVIDE NEW TYPED PANEL DIRECTORIES FOR ALL PANELBOARDS AFFECTED BY RENOVATION. TRACE -OUT ALL BRANCH CIRCUITS AS REQUIRED. 10. WHERE DRAWINGS INDICATE THE INSTALLATION OF A NEW CIRCUIT BREAKER IN EXISTING PANEL, THE AIC, ' RATING OF THE NEW CIRCUIT BREAKER SHALL MATCH THE EXISTING. 11. ALL OPENINGS IN WALLS AND FLOORS SHALL BE SEALED WATERTIGHT. SEAL SHALL BE FLUSH WITH FINISH SURFACE AND PAINTED TO MATCH SURROUNDING FINISH, COORDINATE EXACT REQUIREMENTS WITH OWNER. 12. INSTALL METAL CONDUITS AND FILL IN ANNULAR SPACE WITH 3M FIRE DAM CAULK. ON ALL EXISTING WIRES AND CONDUITS PENETRATING THE CORRIDOR WALLS. 13. ALL EMPTY CONDUITS RUNS IN EXCESS OF 10 FT. SHALL BE PROVIDED WITH A PULL WIRE OR FISH TAPE /CORD. 14. CONTRACTOR SHALL NOTE U.L. LABELS ON PACKAGE TYPE MECHANICAL EQUIPMENT. IF U.L. LABEL ON MECHANICAL EQUIPMENT CALLS FOR THE OVERCURRENT PROTECTIVE DEVICE TO BE FUSES, THE ELECTRICAL CONTRACTOR SHALL PROVIDE A FUSED DISCONNECT SWITCH WITH PROPER SIZE FUSES AT THE SWITCH LOCATION INDICATED ON DRAWINGS. 15. CONTRACTOR SHALL VERIFY WIRE SIZES, C/B AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION OF THE ARCHITECT AND /OR THE ENGINEER ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO PROCEEDING. 16. PROVIDE APPROVED "HACR" TYPE CIRCUIT BREAKERS FOR ALL HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT INDICATED FOR CONNECTION ON ELECTRICAL DRAWINGS. 17. THE CONTRACTOR SHALL GUARANTEE ALL HIS WORK AND MATERIALS FOR A PERIOD OF AT LEAST ONE YEAR AFTER ACCEPTANCE BY OWNER. 18. PANELBOARD DIRECTORIES (SHALL BE UPDATED TO REFLECT ALL WORK DONE AS PART OF THIS PROJECT. 19. SITE INVESTIGATION: IT SHALL BE THE RESPONSIBILITY OF BIDERS TO VISIT THE SITE OF THE WORK AND TO ACQUAINT THEMSELVES WITH ALL INFORMATION REGARDING THE BUILDING; I i ELECTRICAL SPECIFICATIONS 1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE N.E.C. AND LOCAL AUTHORITIES. 2. ALL WORK SHALL BE DONE BY WORKMEN SKILLED IN THE ELECTRICAL TRADE AND IN A NEAT AND WORKMANLIKE MANNER. A MASTER ELECTRICIAN OR JOURNEYMAN SHALL BE ON THE JOB AT ALL TIMES WHEN WORK IS BEING DONE. 3. ALL ELECTRICAL EQUIPMENT, DEVICES, RACEWAYS, OUTLETS, ETC. SHALL BE SUPPORTED IN A SUBSTANTIAL MANNER. 4. SCHEDULE AND COORDINATE ALL WORK WITH OWNER. ALL WORK SHALL BE SCHEDULED, AT OWNER'S CONVENIENCE, 5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC. ALTHOUGH LOCATION OF NEW AND EXISTING EQUIPMENT ARE SHOWN TO SCALE, THE CONTRACTOR SHALL VERIFY ALL INFORMATION ON THE SITE BEFORE BIDDING THE JOB. NOTIFY OWNER /ENGINEER OF ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK. 6. PROVIDE SHOP DRAWINGS FOR APPROVAL BY OWNER AND ENGINEER ON FOLLOWING PRODUCTS. A. LIGHT FIXTURES B. RACEWAYS AND FITTINGS. C. POWER WIRES, D. RECEPTACLES, SWITCHES, ETC. E. FIRE ALARM DEVICES. F. WIRING DIAGRAM OF NEW DEVICES TO NEW FIRE ALARM PANEL. 7. MATERIALS SHALL BE NEW AND BEAR THE UNDERWRITERS LABORATORIES LABEL. 8. SEAL ALL WALLS, FLOORS AND ROOF PENETRATIONS BACK TO ORIGINAL FIRE RATING USING UL APPROVED COMPOUND MATERIALS. 9. PRODUCTS: A. RACEWAYS INSIDE BUILDINGS SHALL BE EMT, CONCEALED IN WALLS OR CEILINGS. RUNS SHALL BE PARALLEL OR PERPENDICULAR TO STRUCTURAL BEAMS AND JOISTS. RUN AS HIGH AS I POSSIBLE. B. USE FLEXIBLE METALLIC GALVANIZED CONDUIT INDOORS FOR CONNECTIONS TO LIGHT FIXTURES AND TO VIBRATION OR ROTATING EQUIPMENT LIKE MOTORS, ETC. USE LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT FOR CONNECTIONS OUTDOORS OR WHERE SUBJECT TO WET CONDITIONS. C. WIRES SHALL BE COPPER, THWN /THHN, 600 VOLTS INSULATION. SIZED AS INDICATED. MINIMUM SIZE #12 AWG. D. NEW CIRCUIT BREAKERS IN EXISTING PANELBOARDS SHALL BE UL LISTED FOR RESPECTIVE MANUFACTURER AND SHALL MATCH EXISTING DEVICES AIC RATING. E. AUTOMATIC CIRCUIT BREAKERS SHALL BE THERMAL - MAGNETIC TYPE, QUICK -MAKE AND QUICK -BREAK ON MANUAL OPERATION, TRIP FREE, WITH INVERSE TIME CHARACTERISTICS. F. POWER AND LIGHTING CIRCUIT WIRING SHALL BE COLOR CODED AS FOLLOWS: 120/208 V. SYSTEMS PHASE "A "- RED PHASE "B "- BLACK PHASE "C "- BLUE NEUTRAL - WHITE GROUND - GREEN 10. CONTROL WIRING SHALL BE PERFORMED UNDER THIS SECTION. MOTORS, STARTERS, CONTROL DEVICES, ETC. SHALL BE FURNISHED AND INSTALLED UNDER MECHANICAL SPECIFICATIONS. COMPLETE POINT BY POINT CONTROL DIAGRAMS SHALL BE FURNISHED UNDER THE MECHANICAL SPECIFICATIONS. 11. CONTRACTOR SHALL PROVIDE A SET OF CLEARLY MARKED DRAWINGS TO SHOW AS- BUILT, CONDITIONS AT THE COMPLETION OF CONSTRUCTION. 12. LIFE SAFETY SYSTEMS PULL /JUNCTION BOXES MUST BE LABELED IN RED IDENTIFYING THE FEEDER OR SYSTEM. ALL OTHERS MUST BE LABELED IN BLACK. FG ENGINEERS, INC. Franl<Garcia, P. E. L'' # 60778 Ildh Jd ar K �3A� 3001 PONCE DE LEON BLVD. SUITE-1 01 CORAL GABLES, FLORIDA 33134 PH: (305) 441 -5892, FAX: (305) 441 -5893 Email: fgarciaf @bellsouth.net C.A. #. 26052 NTERIOR RENOVATION FOR: HAND & STONE Massage & Faciol Spa 7301 SW 57th CT,, SUITE 170, SOUTH MIAMI, FL 1,33143 TI TLE: FORM GROUP, INC. 4300 SW 73 AVE., SUITE 106, MIAMI, FL 33155 TEL. 305.443.4244 FX, 305.443.3338 CORPORATE LICENSE No. AA- 26000668 ARCHITECT OF RECORD: OMAR MORALES ARCHITECT LICENSE No AR 00014851 Ili' 1 0 'F I R 11I, 1 '11 1 1 Ill lily " l l 01 f''! 1­1, II O P] I{ 1 _v ]P­ I)I< .':I v 11i0U't' li.t t ,� 1N.. .11l ill .I.­Illlf PROJECT NO. 11 -606 DATE: JUNE 3. 2011 DRA IiWING NO.: E-2