FIFTH LEVEL
5UILDING PLAN,
HVAC NOTES
1.1 PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY MATERIALS AND LABOR
FOR A COMPLETELY OPERATIONAL HEATING, VENTILATING AND AIR CONDITIONING
(HVAC) SYSTEM AS DEPICTED ON THESE CONTRACT DOCUMENTS.
1.2 INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
ASHRAE SMACNA, NFPA AND LOCAL ORDINANCES.
1.3 SCOPE OF WORK :
PROVIDE THE FOLLOWING COMPLETE SYSTEMS :
A. AIR CONDITIONING SUPPLY AND RETURN DUCT SYSTEM.
B. NOT USED
C. NOT USED
D. AIR CONDITIONING UNITS AND CONTROLS.
E. INDEPENDENT TEST AND BALANCE.
1.4 NOT USED
1.5 PAY FOR ALL FEES, INSPECTIONS AND
CONNECTION CHARGES REQUIRED
1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS AVAILABLE FOR THE INSTALLATION OF
MATERIALS AND EQUIPMENT PRIOR THE INSTALLATION OF EQUIPMENT AND
FABRICATION OF DUCTS AND PIPING SYSTEMS. COORDINATE SPACE REQUIREMENTS
FOR SERVICE AND MAINTENANCE AND COORDINATE INTERFERENCE WITH OTHER
TRADES.
1.7 NATURE OF DESIGN DRAWINGS; DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO
NOT INTEND TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WiLL BE
NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEMS REQUIRED BY THESE
SPECIFICATIONS.
1.8 COORDINATION DRAWINGS; PREPARE 1/4" SCALE (MIN.) COORDINATION DRAWINGS
SHOWING DUCTWORK, PIPING AND ALL MAJOR SYSTEM COMPONENTS FOR A/E
APPROVAL BEFORE PROCEEDING WITH THE INSTALLATION. IMPLEMENT ALL
INFORMATION FROM 1.6 ABOVE.
1.9 SUBMIT SHOP DRAWINGS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE
THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS. ALL SHOP
DRAWINGS MUST BE SUBMITTED IN A SINGLE BOUND AND INDEXED PACKAGE NO
LATER THAN 30 DAYS FROM THE ADJUDICATION OF THE PROJECT.
1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR
A A PERIOD OF ONE YEAR FROM THE DATE OF PROJECT ACCEPTANCE.
2.0 MATERIALS
2.1 DUCTWORK
2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE
DIMENSIONS.
2.1.2 DUCTWORK MATERIALS:
A: GENERAL AREA
A: EXPOSED AIR CONDITIONING DUCTWORK SPIRAL GALVANIZED
SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO
LATEST EDITION OF SMACNA'S. LOW PRESSURE CONSTRUCTION
STD. (0.5" W.G.)
2.1.3 NOT USED
.1 NOT USED
.2 NOT USED
2.1.4 PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY
OUTLET AND AT EACH DUCT BRANCH.
2.2 NOT USED.
2.3 NOT USED.
2.4 AIR DISTRIBUTION PRODUCTS :
2.4.1 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS.
2.4.2 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS
INDICATED ON THE DRAWINGS AND SCHEDULES.
2.4.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH
THE CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS,
2.4.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS
BEHIND ALL AIR SUPPLY OUTLETS.
2.5 PROVIDE A MINIMUM 5 YEAR WARRANTY FOR ALL AIR
CONDITIONING COMPRESSORS STARTING FROM THE DATE OF
PROJECT ACCEPTANCE.
2.6 CONTROLS:
2.6.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER
OPERATION OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC
STARTERS AND INTERLOCK WIRING INDICATED FOR EACH PIECE OF
EQUIPMENT.
2.6.2 OFFICE AREA DX EQUIPMENT: PROVIDE AIR CONDITIONING UNITS WITH
MATCHING LOW VOLTAGE HEAT /COOL THERMOSTATS WITH ON -OFF
AUTO SUB -BASE SWITCH AS FURNISHED BY THE EQUIPMENT
MANUFACTURER.
2.7 STARTERS:
PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS
SECTION AS DESCRIBED ON THE EQUIPMENT SCHEDULES. ALL STARTERS MUST
HAVE HAND -OFF -AUTO POSITION SWITCH ON THE COVER AND RED /GREEN
PILOT LIGHTS, PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED
CONTACTS FOR THE INTENDED OPERATION AND INTERLOCKS.
2.8 NOT USED.
2.9 IDENTIFICATION:
2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12 "x4"
HIGH WITH WITH 1.5" LETTERS. USE THE SAME NOMENCLATURE AS IN THESE
DOCUMENTS.
2.10 RETURN AIR CEILING PLENUMS:
2.10.1 WHEN CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS"
ALL MATERIALS INSIDE THE R/A CEILING PLENUM SHALL HAVE
A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAXIMUM
SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A.
"NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM."
2.10.2 PROVIDE FREE PATH FOR R/A INSIDE CEILING
SPACE. SEE ARCHITECTURAL PLAN FOR
COORDINATION
3.0 EXECUTION
3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION
TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION & SERVICE. FOR
INSTALLATION, OPERATION AND SERVICE.
3.2 NOT USED
3.3 THERMOSTAT LOCATION. THERMOSTAT LOCATION IS CRITICAL TO PROPER
EQUIPMENT OPERATION. INSTALL THERMOSTAT AT LOCATIONS SHOWN
ON PLANS. RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING.
3.4 NOT USED
3.5 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION
REPAIR AND /OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND
TO BE OBJECTIONABLE, TO THE SATISFACTION OF THE A /E.
3.6 BALANCE ALL SYSTEMS TO PROVIDE AIR AND WATER QUANTITIES AND CAPACITIES
TO MATCH SPECIFIED FLOWS & CAPACITIES. CALIBRATE FLOWS TO NEW
EQUIPMENT PER MANUFACTURER'S REQUIREMENTS, SUBMIT FINAL TEST AND
BALANCE REPORT TO A/E FOR ACCEPTANCE.
HYAL, OFF I
SCALE.- 1/4' =1' -0'
SHAFT IV txl5I wr�v�IVSIIVC
UNITS AT ROOF INDICATED
ON SHELL PERMIT
AN -SUITE 525
11 -12 -09
PERMIT SET
J ANTONIO
PE X1
640 MECH
F E
PE 49985 ME
:p
�'0 ,°
' Certificate of
y Authorization #
00002906
1061 7 Street, Mia L 33172
TEL: 5ik 1360 FAX: %5r 593V9279
WWW. en ineers.com
DES[ CsY F DATE
JOB NUMBER 013-xxx
i
•
:A R CH ITECT 4565 PON(- OE UON SUITE 201 'ORAL GABLES FL 33146
TEL 305 784 2871, FAX 305 739 2872
ARCHITECTURE LI(ENSE REGISTRATION NUMBERS
(ARLOS PRIO TOUZET FL AR0094099; JACQUELINE GONZALEZ FL AR0016319 •
• Drawings are subject to modification or change as required by actual measurements, standard industry
practices in light of existing structural and other conditions, applicable building codes, and the like. These
plans are and shall remain the property of Touzet Studio and shall not be sold or reproduced without Ito
prior written consen uze
t. Tot Studio shall be notified of any changes required by actual conditions as
. aforesald prior to submission of any phase for construction. 02009, TOUZET STUDIO.. .
OWNER
NG HOLDINGS, LL(
ME(HANKAL / ELECTRICAL / PLUMBING/ FIRE PROTE(TION ENGINEERS
FRANYIE ENGINEERS, INC
ANTONIO FRANYIE PE #11640 VIVIANNA FRANYIE PE #49985
10610 NW 27th AVENUE MIAMI, FLORIDA 33172
305.592.1360
PROFESSIONAL LICENSE
.................. ...............................
ISSUE
NO. DESCRIPTION ISSUE DATE
PERMIT SET 11.04.09
i
f
i
KEY PLAN
PROJECT PROJE(T NO.: 09_015
INTERIOR OFFICE
REMODELING
7301 SW 57th COURT
SPACE #525
SOUTH MIAMI, FLORIDA 33143
DRAWING TiTLE
H.V.AX. FLOOR PLAN & NOTES