12-1332-009AIR DUCT (SEE PLAN VIEW)
LOW FRICTION LOSS
BRANCH TAKE -OFF FITTING
METAL ROUND FITTING
QUADRANT OPERATOR TO BE
OUTSIDE INSULATION
PROVIDE INSULATION GUARD
WHERE NECESSARY
AIR FLOW
SEAL JOINT W/
DUCT SEALER AND 6''
TAPE
AIR FLOW
n INSULATE TOP
V OF DIFFUSER. INSULATED FLEX. DUCT
SEAL JOINT WITH DUCT
SEALER AND TAPE
DIFFUSER W/ OPPOSED
BLADE DAMPER
ADAPTOR ROUND TO SQUARE
IF REQUIRED
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
HVAC NOTES
1. GENERAL
A. DRAWINGS: Refer to all drawings for coordination of the HVAC work.
B. ARRANGE AND PAY for all permits licenses, inspections and tests.
Obtain the required certificates and present to owner.
C. GUARANTEE: The completed installation shall be fully guaranteed
against defective materials and /or improper workmanship for a
minimum of one year for material and labor. Compressors shall be
guranteed for a period of five years.
D. As built drawings shall be submitted to owner at the completion
of project.
2. SHOP DRAWINGS: Contractors shall submit for approval, within 30 days
after signing contract, a minimum of five copies of fully descriptive
literature, including but not limited to: fans, air conditioning units, air outlets.
No work shall proceed without approval of these submittals.
3. DESIGN PARAMETERS:
A. Outdoor design temperature (Summer): 917 DB and 797 WB
B. Outdoor design temperature (Winter): 457
C. Indoor design temperature (Summer): 787 DB
D. Indoor design temperature (Winter): 727 DB
4. ALL THERMOSTATS SHALL have heating mode maximum setting of 75 F, and
cooling mode minimum setting of 70 F. The thermostat shall be arranged
to prevent the simultaneous operation of heating and cooling.
5. ELECTRICAL CONTROLS AND POWER WIRING: Under electrical contract.
6. EQUIPMENT SPECIFIED BY manufacturer's number shall include all
accessories, controls, etc., listed in the catalog as standard with the
equipment. Optional or additional accessories shall be furnished as
specified.
7. MATERIALS:
A. DUCTWORK:
a. All rigid supply and return air ductowrk shall be galvanized sheet metal not lighter than 24 GA.
as per latest edition of SMACNA "Low Pressure Duct Manual." Round supply ducts
shall be spiral factory fabricated. All supply ductwork in concealed spaced shall be
installed with 1 -1/2" thick fiberglass insulation with foil kraft cover (R -6 Min).
b. All duct dimensions are clear inside dimensions.
8. Provide metal round fittings at all flexible duct connection
to supply duct.
9. TEST AND BALANCE: Contractor shall test and balance all ventilation and
air conditioning systems. Submit four copies of Test and Balance Report
to owner for approval.
10. SECUENCE OF OPERATION
A. Air conditioning units shall be started and stopped thru
individual thermostat. Individual thermostats shall start /stop supply
fans and activate cooling /heating systems as selected.
11. Mechanical plans in general, are diagrammatic in nature, and ore to be read
in con juction with arch. Plumbing, electrical and structural plans and shall
be considered as one set of documents. Duct and piping offsets, bends
and transitions will be required to provide and install a complete functional
system and shall be provided by the contractor at no additional cost to
the owner.
12. Contractor shall verify job conditions prior to ordering, fabrication or
installation of materials or equipment. Notify architect /engineer of any
conflicts before fabrication.
AIR DISTRIBUTION SCHEDULE
SIMBOL
USE
TYPE
ACCESORIES
DESIGN MANUFACTURER & MODEL Mo.
LS
SUPPLY AIR
LINEAR DIFFUSER
O.B.D.
TITUS ML -38 (TWO 3/4" SLOTS) W/ MP -38 PLENUM
LR
RETURN AIR
LINEAR DIFFUSER
O.B.D.
TITUS MLR -38 (TWO 3/4" SLOTS) W/ MP -38 PLENUM
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
-
X
FIRE DAMPER(S)
X
X
SMOKE DAMPER(S)
-
X
FIRE RATED ENCLOSURE
-
X
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
-
X
FIRE STOPPING
X
-
SMOKE CONTROL
-
X
EXISTING EXHAUST FAN &
ASSOCIATED DUCTWORK
TO BE REMOVED
EXISTING RESTROOM TO
BE DEMOUSHED. CAP OFF
ALL PLUMB. PIPES AS
NEEDED
to l"1111111. JOB N0, 10 -091 LOBBY
® %` YAEL
.`
••L1 CFN•.9
0 Q 0 �
•:�
revi si ons:
NO
� •
s
• *=
0 �
71
ND C OFF
I
AEtJ5�AAY* (I
�
IfiIll VIII
(E) 36X16
APP D
QJ
-
0 Q 0 �
revi si ons:
LR 10' -O" LONG
I South Miami Advanced I
OVE E T. DU ORK
=M
71
ND C OFF
I
EE
I
�
aI
/3\
C�
G
DR. ALAN SERURE I
I SUITE 00 2 PLACE I
ANG RO M 102
ITI
L
a
O Q
I SOUTH MIAMI, FL 33143
EXISTING SA D t W USER & UJ
aik n,G resxv�
architecture
ASSOCIATED DUCTWORK
TO BE REMOVED °
Maricarmen Martinez, AIA
3941 Midway Street
REFER TO CLARINS
INTERIOR DESIGN 0
Miami, Florida 33133
DOCUMENTS FOR 0
QTel
DIMENSIONS,
305 447 -1907 Fax 305 447 -1906
M=l so
/ LIGHTING SPECS,
a
a
g
DETAILS &
rt
FINISHES
10 (E
EXISTING RA GRILLE
TO BE REMOVED --
CEILING PLAN - MECHANICAL
SCALE: 1/4" = V -011
RPJ, Inc.
M0CI1rI
STATE OF F1 CO. N0. (00006513) P.E. N0. (16395) '
. 4977 S.W. 74th COURT
ia
MIAMI, FL. 33155
PHONE: (305) 666 -2131 FAX: (305) 666 -0131
E —Mail: rpJ0rpjmep.com
,sp
r'' 8
,f4
�a
APP D
QJ
-
_ _ _
prO,eCt.-- -_ - -_�
�
revi si ons:
D a :
I South Miami Advanced I
=M
J Center for Surgery
aI
/3\
DAr11lz3tiz
G
DR. ALAN SERURE I
I SUITE 00 2 PLACE I
L
a
UPSTAIRS STUDIO
I SOUTH MIAMI, FL 33143
aik n,G resxv�
architecture
L___ __ ________J
Maricarmen Martinez, AIA
3941 Midway Street
Miami, Florida 33133
QTel
305 447 -1907 Fax 305 447 -1906
M=l so
fD
a
a
g
e -mail: infoCupstairsstudioarchitecture.com
rt
F
O
o
FLORIDA LICENSE: AA 0003146
,sp
r'' 8
,f4
�a