Loading...
12-1332-0053-5/8" CONTINUOUS HEADER TRACK W/ 1" POWER DRIVEN FASTENER @ 24"O.C. (MIN 7/32 0 PLATE WASHER) 3-5/8" METAL STUDS @ 16"O.C. (25 GUAGE) — 5/8" GYPSUM BOARD TYPE 'X' (BOTH SIDES) -­,, 3-5/8" CONTINUOUS SILL W1 1" POWER DRIVEN FASTENER @ 24"O.C. (MIN 7/32 0 PLATE WASHER) FLOORING - SEE FINISH SCHEDULE FOR SPEC EXTG. CONCRETE SLAB EXTG. CONCRETE BEAM 1/2" GAP @ STUD TO RUNNER JOINT EXTEND METAL STUDS OF INTERIOR PARTITION WALL PAST DROPPED CEILING TO BOTTOM OF EXTG. CONC. SLAB ACOUSTICAL CEILING TILE - SEE A4.0 FOR SPEC NOTE: 2 HOUR FIRE SEAL ALL GAPS & PENETRATIONS BETWEEN FLOOR SLABS SEE CORE DRILL DETAIL 3/A7.0 NOTE: FIRE SEAL ALL EXISTING PIPE, DUCTS, ETC. PENETRATING NEW PARTITON LOCATION NOTE: UL DESIGN NO. U419 ONE HOUR FIRE RATED TENANT SEPARATION WALL. No.25 GAUGE CHANNEL-SHAPED STUDS 16" O/C WITH ONE FULL-LENGTH LAYER OF 5/8" TYPE "X" GYPSUM WALLBOARD APPLIED VERTICALLY EACH SIDE. FIRST LAYER ATTACHED WITH 1" LONG No. 6 DRYWALL SCREWS TO EACH SIDE. SCREWS ARE 8" O.C. AROUND THE PERIMETER AND 12" O.C. ON THE INTERMEDIATE STUD. SECOND LAYER APPLIED WITH VERTICAL JOINTS OFFSET 1 STUD-SPACE FROM FIRST LAYER USING AN APPROVED ADHESIVE. SOUND ATTENUATION BATT INSULATION FIRE S AL ALL GAPS (BOTH SIDES) 4 4 DISPLAY -SEE RATED DOOR APPROVED SHOP TO REMAIN DRAWINGS — 0 0 UD11 - I Center for Surgery 0 0 4 4 . U C _c4 A UPSTAIRS STUDIO SOUTH H MIAMI, FL 33143 WAITING ROOM <6> A Ad L - ----- - - - - -- - 4 A Marlicarmen Martinez, AIA 0 4 Miami, Florida 33133 Tel 305 447-1907 Fax 305 447-1906 (D AL 0 0 (D A e-mail: infoCup;Girsstudioarchitectu A3 a r-r 0 3-5/8" CONTINUOUS HEADER TRACK W/ 1" POWER DRIVEN FASTENER @ 24"O.C. (MIN 7/32 0 PLATE WASHER) 3-5/8" METAL STUDS @ 16"O.C. (25 GUAGE) — 5/8" GYPSUM BOARD TYPE 'X' (BOTH SIDES) -­,, 3-5/8" CONTINUOUS SILL W1 1" POWER DRIVEN FASTENER @ 24"O.C. (MIN 7/32 0 PLATE WASHER) FLOORING - SEE FINISH SCHEDULE FOR SPEC EXTG. CONCRETE SLAB EXTG. CONCRETE BEAM 1/2" GAP @ STUD TO RUNNER JOINT EXTEND METAL STUDS OF INTERIOR PARTITION WALL PAST DROPPED CEILING TO BOTTOM OF EXTG. CONC. SLAB ACOUSTICAL CEILING TILE - SEE A4.0 FOR SPEC NOTE: 2 HOUR FIRE SEAL ALL GAPS & PENETRATIONS BETWEEN FLOOR SLABS SEE CORE DRILL DETAIL 3/A7.0 NOTE: FIRE SEAL ALL EXISTING PIPE, DUCTS, ETC. PENETRATING NEW PARTITON LOCATION NOTE: UL DESIGN NO. U419 ONE HOUR FIRE RATED TENANT SEPARATION WALL. No.25 GAUGE CHANNEL-SHAPED STUDS 16" O/C WITH ONE FULL-LENGTH LAYER OF 5/8" TYPE "X" GYPSUM WALLBOARD APPLIED VERTICALLY EACH SIDE. FIRST LAYER ATTACHED WITH 1" LONG No. 6 DRYWALL SCREWS TO EACH SIDE. SCREWS ARE 8" O.C. AROUND THE PERIMETER AND 12" O.C. ON THE INTERMEDIATE STUD. SECOND LAYER APPLIED WITH VERTICAL JOINTS OFFSET 1 STUD-SPACE FROM FIRST LAYER USING AN APPROVED ADHESIVE. SOUND ATTENUATION BATT INSULATION FIRE S AL ALL GAPS (BOTH SIDES) EXTG. CONCRETE SLAB EXTG. CONCRETE BEAM DETAIL SCALE: 1-1/2" = V-0" 11 L\ REMOVE EXTG, DOOR WAITING ROOM <9> REMOVE EXTG. RESTROOM EXTG. 45 MINUTE FIRE RATED DOOR REMOVE EXTG. TO REMAIN CEILING AND FLOOR FINISHES. PREP FOR NEW FINISHES EXTG. WINDOW TO REMAIN ---, DEMOLITION P1 4,N EXTG. DOOR TO REMAIN - MILLWORK NEW 45 DISPLAY - SEE MINUTE FIRE APPROVED SHOP RATED DOOR DRAWINGS WAITING ROOM <6> REFER TO CLARINS INTERIOR DESIGN DOCUMENTS FOR DETAILS, SPECS OF FINISHES & FURNISHINGS EXTG. 45 MILLWORK MINUTE FIRE DISPLAY -SEE RATED DOOR APPROVED SHOP TO REMAIN DRAWINGS — 0 0 UD11 - I Center for Surgery 0 0 'A DAT/�� U C _c4 A UPSTAIRS STUDIO SOUTH H MIAMI, FL 33143 WAITING ROOM <6> .2.2 architecture L - ----- - - - - -- - 4 A Marlicarmen Martinez, AIA 0 0 Miami, Florida 33133 Tel 305 447-1907 Fax 305 447-1906 (D AL 0 0 (D A e-mail: infoCup;Girsstudioarchitectu A3 a r-r 0 . °n 0 7 EXTG. CONCRETE SLAB EXTG. CONCRETE BEAM DETAIL SCALE: 1-1/2" = V-0" 11 L\ REMOVE EXTG, DOOR WAITING ROOM <9> REMOVE EXTG. RESTROOM EXTG. 45 MINUTE FIRE RATED DOOR REMOVE EXTG. TO REMAIN CEILING AND FLOOR FINISHES. PREP FOR NEW FINISHES EXTG. WINDOW TO REMAIN ---, DEMOLITION P1 4,N EXTG. DOOR TO REMAIN - MILLWORK NEW 45 DISPLAY - SEE MINUTE FIRE APPROVED SHOP RATED DOOR DRAWINGS WAITING ROOM <6> REFER TO CLARINS INTERIOR DESIGN DOCUMENTS FOR DETAILS, SPECS OF FINISHES & FURNISHINGS EXTG. 45 MILLWORK MINUTE FIRE DISPLAY -SEE RATED DOOR APPROVED SHOP TO REMAIN DRAWINGS — EXTG. WINDOW EXTG. DOOR TO REMAIN ---, TO REMAIN - FLOOR PLAN REFLECTED CEILING PLAN 2 PLANS & DETAILS SCALE: 1/4" = 11 -011 CONSTRUCTION -NOTES: 1. THE PARTITION LAYOUT IS TO BE DEMARCATED ON THE FLOOR, REVIEWED, AND APPROVED ZY THE ARCHITECT -r—r-LIOR TZ - - CONSTRUCTION. ANY DIME45TONAL DYSCREPANCIES AAE TD BE REPORTED TO THE ARCHITE� -PRIOR-1-0-CONSTRtJMO',V,,.-- - 2. ALL INTERIOR PARTITIONS ARE SLAB TO SUSPENDED CEILING, EXTENDING PAST SUSPENDED CEILING W/ 5/8" TYPE "X" WALL BOARD EACH SIDE. USE R-19 BATT INSULATION BETWEEN ALL WAY TO BOTT. OF SLAB & STAGGER ALL ELECTRICAL DEVICES FOR MAX. SOUND ATTENUATION. 3. 2 HR. FIRE SEAL @ ALL EXTG. & NEW PIPES, DUCTS, CHASES, ETC. PENETRATING FLOOR & CEILING SLABS. 4. CLEAN, REPAIR & PAINT, WINDOW FRAMES AS NEEDED-MEET W/ ARCHITECT TO DETERMINE. 5. ALL WALLS SUPPORTING SHELVING, CABINETRY, MILLWORK, AND GRAB BARS ARE TO BE REINFORCED WITH PROPER BACKING TO SAFELY SUPPORT AND ANCHOR THE ADDITIONAL LOADS. 6. PLUMBING WORK IN THIS SUITE WILL NEED TO BE DONE FROM CEILING BELOW, THEREFORE CEILING IN GARAGE AND DRIVEWAY WILL NEED TO BE OPENED TO ACCESS PLUMBING PIPES AND MUST BE REPAIRED ACCORDINGLY AFTER THE WORK IS COMPLETE. 7. AS PER NFPA 38.3.3 INTERIOR FINISH: INTERIOR WALL AND CEILING FINISH: EXITS AND EXIT ACCESS CORRIDORS = CLASS A OR CLASS B ALL OTHER AREAS CLASS A, CLASS B, OR CLASS C WALL LEG E N D EXISTING WALL TO REMAIN NEW CAST-IN-PLACE CONC. WALL, SEE STRUCTURAL DRAWINGS NEW 8" CMU WALL. 3/4" STUCCO FINISH ON EXTERIOR FACE AND 5/8" GYP. BOARD OVER 7/8" MTL. FURRING @ 16" O.C. W/ RIGID INSULATION BETWEEN FURRING ON INTERIOR., SEE STRUCTURAL NEW INTERIOR PARTITION W/3-5/8" METAL STUDS AT 16" O.C. AND 5/8" GYP. BOARD BOTH SIDES PROVIDE INSULATION BETWEEN STUDS - USE MOISTURE RESISTANT TYPE AT ALL DAMP LOCATIONS (BATHROOM, LAUNDRY, KITCHEN, BACKSPLASH, ETC.). USE 6" METAL STUDS AT 16" O.C. AS REQUIRED FOR PLUMBING WALLS. NEW INTERIOR FIRE RATED PARTITION W/ 3 5/8" METAL STUDS AT 16" O.C. AND 5/8" TYPE'X'GYP. BOARDS BOTH SIDES. UL DESIGN NO. U419 7=1 NEW INTERIOR PARTIAL HEIGHT PARTITION W/ 3-5/8" METAL STUDS AT 16" O.C. AND 5/8" GYP. BOARD BOTH SIDES. 0, JONI , 47, pq 'fie G E A, "7 67D'W\ I MCM 7 0 z 0 0 0 revi si ons: DRA)Nr5_Y"--\ 0 0 UD11 - I Center for Surgery 0 0 AL DAT/�� U C I DR. ALAN SERURE 7330 SW 20 62 PLACE SUrrE 0 A UPSTAIRS STUDIO SOUTH H MIAMI, FL 33143 WAITING ROOM <6> .2.2 architecture L - ----- - - - - -- - Marlicarmen Martinez, AIA 0 0 Miami, Florida 33133 Tel 305 447-1907 Fax 305 447-1906 (D AL 0 0 (D A e-mail: infoCup;Girsstudioarchitectu A3 a r-r 0 . 0 0 7 REFER TO CLARINS 0 INTERIOR DESIGN 0 DOCUMENTS FOR 0 DIMENSIONS, 0 LIGHTING SPECS, DETAILS & FINISHES 0 0 0 0 L z 0 0 0 0 0 REFLECTED CEILING PLAN 2 PLANS & DETAILS SCALE: 1/4" = 11 -011 CONSTRUCTION -NOTES: 1. THE PARTITION LAYOUT IS TO BE DEMARCATED ON THE FLOOR, REVIEWED, AND APPROVED ZY THE ARCHITECT -r—r-LIOR TZ - - CONSTRUCTION. ANY DIME45TONAL DYSCREPANCIES AAE TD BE REPORTED TO THE ARCHITE� -PRIOR-1-0-CONSTRtJMO',V,,.-- - 2. ALL INTERIOR PARTITIONS ARE SLAB TO SUSPENDED CEILING, EXTENDING PAST SUSPENDED CEILING W/ 5/8" TYPE "X" WALL BOARD EACH SIDE. USE R-19 BATT INSULATION BETWEEN ALL WAY TO BOTT. OF SLAB & STAGGER ALL ELECTRICAL DEVICES FOR MAX. SOUND ATTENUATION. 3. 2 HR. FIRE SEAL @ ALL EXTG. & NEW PIPES, DUCTS, CHASES, ETC. PENETRATING FLOOR & CEILING SLABS. 4. CLEAN, REPAIR & PAINT, WINDOW FRAMES AS NEEDED-MEET W/ ARCHITECT TO DETERMINE. 5. ALL WALLS SUPPORTING SHELVING, CABINETRY, MILLWORK, AND GRAB BARS ARE TO BE REINFORCED WITH PROPER BACKING TO SAFELY SUPPORT AND ANCHOR THE ADDITIONAL LOADS. 6. PLUMBING WORK IN THIS SUITE WILL NEED TO BE DONE FROM CEILING BELOW, THEREFORE CEILING IN GARAGE AND DRIVEWAY WILL NEED TO BE OPENED TO ACCESS PLUMBING PIPES AND MUST BE REPAIRED ACCORDINGLY AFTER THE WORK IS COMPLETE. 7. AS PER NFPA 38.3.3 INTERIOR FINISH: INTERIOR WALL AND CEILING FINISH: EXITS AND EXIT ACCESS CORRIDORS = CLASS A OR CLASS B ALL OTHER AREAS CLASS A, CLASS B, OR CLASS C WALL LEG E N D EXISTING WALL TO REMAIN NEW CAST-IN-PLACE CONC. WALL, SEE STRUCTURAL DRAWINGS NEW 8" CMU WALL. 3/4" STUCCO FINISH ON EXTERIOR FACE AND 5/8" GYP. BOARD OVER 7/8" MTL. FURRING @ 16" O.C. W/ RIGID INSULATION BETWEEN FURRING ON INTERIOR., SEE STRUCTURAL NEW INTERIOR PARTITION W/3-5/8" METAL STUDS AT 16" O.C. AND 5/8" GYP. BOARD BOTH SIDES PROVIDE INSULATION BETWEEN STUDS - USE MOISTURE RESISTANT TYPE AT ALL DAMP LOCATIONS (BATHROOM, LAUNDRY, KITCHEN, BACKSPLASH, ETC.). USE 6" METAL STUDS AT 16" O.C. AS REQUIRED FOR PLUMBING WALLS. NEW INTERIOR FIRE RATED PARTITION W/ 3 5/8" METAL STUDS AT 16" O.C. AND 5/8" TYPE'X'GYP. BOARDS BOTH SIDES. UL DESIGN NO. U419 7=1 NEW INTERIOR PARTIAL HEIGHT PARTITION W/ 3-5/8" METAL STUDS AT 16" O.C. AND 5/8" GYP. BOARD BOTH SIDES. 0, JONI , 47, pq 'fie G E A, f4 "7 67D'W\ I MCM project: revi si ons: DRA)Nr5_Y"--\ South Miami Advanced el UD11 - I Center for Surgery AL DAT/�� U C I DR. ALAN SERURE 7330 SW 20 62 PLACE SUrrE 0 A UPSTAIRS STUDIO SOUTH H MIAMI, FL 33143 A .2.2 architecture L - ----- - - - - -- - Marlicarmen Martinez, AIA 3941 Midway Street Miami, Florida 33133 Tel 305 447-1907 Fax 305 447-1906 (D AL (D A e-mail: infoCup;Girsstudioarchitectu A3 a r-r tu- . 0 FLORIDA LICENSE: AA 0003148 f4