11-358-009
MECHANICAL NOTES: 1. ALL SUPPLY AIR REGISTERS SHALL BE 10 INCHES X 10 INCHES ADJUSTABLE w / 1.0 INCHES X 20 INCHES (INSIDE) OVERHEAD FIBERGLASS DUCT, UNLESS OTHERWISE SPECIFIED, nUCTS LOCATED IN VENILATED ATTIC SPACES SHALL HAVE AN R -6 INSULATION VALUE. DUCTS LOCATED IN UNCONDITIONED INTERIOR SPACE. INTERIOR SPACES SHALL HAVE AN R -4.2 INSULATION VALUE. 2. RESTROOM VENT FANS SHALL PROVIDE 50 CFM MINIMUM PER WATER CLOSET AND / OR URINAL. 3. VENT FANS SHALL BE DUCTED TO THE EXTERIOR AND TERMINATE AT ANI APPROVED VENT CAP. 4. HVAC EQUIPMENT SHALL BE EQUIPPED WIYH OUTSIDE FRESH INTAKES PROVIDING 20 CFM FOR EACH " OCCUPANT OR 50 CFM FOR EACH WATER HEATER CLOSET AND EACH URf :4AL, WHICH EVER IS GREATER. PLUMBING NOTES: 1. CUSTOME"MSUMES ALL RESPONSIBILITY FOR DRINKING WATER FACILITIES AND SERVICE SINK WHEN NOT SHOWN ON THE FLOOR PLAN. 2. TOILETS SHALL BE ELONGATED WITH NON - ABSORBENT OPEN FRONT SEAT. 3. RESTROOMS WALLS SHALL BE COVERED WITH NON - ABSORBENT MATERIAL TO A MINIMUM HEIGHT OF 48 INCHES A.F.F. 4. ALL PLUMBING FIXTURES SHALL HAVE SEPARATE SHUT -OFF VALVES. 5. WATER HEATER SHALL HAVE SAFTY PAN WITH 1 INCH DRAIN TO EXTERIOR, T & P RELIEF VALVE WITH DRAIN TO EXTERIOR, AND A SHUT OFF VALVE WITHIN 3 FEET ON A COLD WATER SUPPLY LINE, 6. DWV SYSTEM SHALL BE EITHER ABS OR PVC - DWV. 7. WATER SUPPLY LINES SHALL BE POLYBUTYLLENE, CPVC, OR COPPER; WHEN POLYBUTYLENE SUPPLY LINES ARE INSTALLED THE MAXIMUM WATER HEATER TEMPERATURE SFTtING IS 180° F. THE POLY - BUTYLENE PIPE SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURES LIMITATIONS AND INSTRUCTIONS. 8. WATER CLOSETS ARE TANK TYPE AND URINALS ARE FLUSH TANK TYPE UNLESS OTHERWISE SPECIFIED. 9. BUILDING DRAIN AND CLEANOUTS ARE DESIGNED AND SITE INSTALLED "3Y OTHERS. SUBJECT TO LOCAL JURISDICTION APPROVAL. 10. SHOWERS SHALL BE CONTROLLED BY AN APPROVED MIXING VALVE WITH A MAXIMUM WATER OUTLET TEMPERATURE OF 120° F (48.8° C). 11. THERMAL EXPANSION DEVICE, IF REQUIRED BY WATER HEATER INSTALLED, AND IF NOT SHOWN ON PLUMBING PLAN, IS DESIGNED AND SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 12. A WATER- HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK- CLOSING VALVES ARE UTILIZED, UNLESS OTHERWISE APPROVED. WATER HAMMER ARRESOTRS SHALL BE INSTALLED" IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. SITE INSTALLED NOTES: NOTE THAT THIS LIST DOES NOT NECESSARILY LIMITS THE ITEMS OF WORK AND MATERIALS THAT MAY BE REQUIRED FOR A COMPLETE INSULATION. ALL SITE RELATED ITEMS ARE SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 1. THE COMPLETE FOUNDATION SUPPORT AND TIE DOWN SYSTEM. 2. RAMPS, STAIRS AND GENERAL ACCESS TO THE BUILDING. 3. PORTABLE FIRE EXTINGUISHERS (S). 4. DRINKING FOUNTAIN, BUILDING DRAINS, CLEAN -OUTS, AND HOOK - UP TO PLUMBING SYSTEM. 5. ELECTRICAL SERVICE HOOK -UP ( INCLUDING FEEDERS) TO THE BUILDING. 6. THE MAIN ELECTRICAL PANEL AND SUB- FEEDERS ( MULTI -UNITS ONLY). , 7: CONNECTION OF ELECTRICAL CIRCUITS CROSSING OVER MODULE MATING LINES (S)-(MULTI-UNITS ONLY). 8. STRUCTURAL AND AESTHETIC INTERCONNECTIONS BETWEEN ' 9. WINDOW AND DOOR HIGH WIND STORM COVERINGS PER CODE. 10. GUTTERS AND DOWNSPOUTS ( IF APPLICABLE). 11. SINK AND CABINETS. 12. FIRE ALARM SYSTEM, WIRING, ETC. 13. THERMAL EXPANSION DEVICE IF REQUIRED. STATE CODES: FLORIDA 2009 FLORIDA BUILDING CODE* 2007 FPC w/ 2009 SUPPLEMENTS 2007 FMC w/ 2009 SUPPLEMENTS 2008 NEC * w/ 2009 SUPPLEMENTS OCCUPANCY B CONSTRUCTION TYPE V - B DRAWING INDEX: Cl COVER SHEET Al FLOOR PLAN A2 ELEVATIONS A3 BUILDING CROSS SECTION S1 FOUNDATION 9. ACCESSIBILE WATER CLOSETS SHALL BE 19 INCHS FROM THE FLOOR TO THE TOP OF THE SEAT. GRAB BARS SHALL BE 36 INCHES LONG MINIMUM WHEN LOCATEDBEHIND THE WATER CLOSET AND 42 INCHES MININUM WHEN LOCATED ALONG THE SIDE OF THE WATER CLOSET, AND SHALL BE MOUNTED 33 INCHES FROM THE ELEVATION NOTES TYP. FLOOR TO THE TOP OF THE RAIL WITH 0.5 INCH MAXIMUM VARIATION. 1.) SEE CROSS SECTION FOR METHOD OF ROOF VENTILATION i 10. ACCESSIBLE URINALS SHALL BE STALL -TYPE OR WALL HUNG WITH ELONGATED RIMS AT A MAXIMUM OF 17 2,) HANDICAP RAM(S), STAIRS (S), AND HANDRAILS ARE TO BE DESIGNED AND SITE ♦�'1 INCHES ABOVE THE FLOOR. INSTALLED BY OTHERS, SUBJECT TO,LOCAL JURISDICTION AND APPROVAL. �! 11. ACCESSIBLE LAVATORIES SHALL BE MOUNTED WITH THE RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR 3.( FOUNDATION ENCLOSURE ( WHEN PROVIDED) MUST HAVE 1 SQUARE FOOT NET AND A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE FLOOR TO THE BOTTOM OF THE APRON. VENT AREA PER 1/1 1/150th OF THE FLOOR AREA AND AN 18" X 24" MINIMUM` 12. ACCESSIBLE SINKS SHALL BE MOUNTED WITH RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR AND A CRAIAYL SPACE ACCESS, SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL CLEARANCE OF AT LEAST 27 INCHES HIGH, 30 INCHES WIDE, AND 19 INCHES DEEP UNDERNEAT SINK. JURISDICTION AND APPROVAL. n/ THE SINK DEPTH SHALL BE 6.5 INCHES MAXIMUM, 13. HOT WATER AND DRAIN PIPES UNDER ACCESSIBLE LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT CONTACT. INSULATION OR PROTECTION MATERAL MAY BE SITE V INSTALLED. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER ACCESSIBLE LAVATORIES AND SINKS. THESE PRINTS COMPLY WITH THE FLORIDA BUILDING CODE AND 14. ACCESSIBLE LAVATORIES AND SINKS SHALL HAVE ACCESSIBLE FAUCETS (ie. LEVER- OPERATED, PUSH -TYPE, ADHERE TO THE FOLLOWING CRITERIA. ELECTRONICALLY CONTROLLED). 15 WHERE MIRRORS ARE PROVIDED IN RESTROOM, AT LEAST ONE, SHALL BE PROVIDED WITH ITS BOTTOM ;I•i Y OF SOUTH MIAMI EDGE NO HIGHER THAN 40 INCHES ABOVE THE FIOOR. CONST. TYPE � -� )) ) )I G DEPT ° cl 16 WHERE MEDICINE CABINETS ARE PROVIDED, AT LEAST ONE SHALL BE LOCATED WITH A USABLE SHELF NO OCCUPANCY O HIGHER THAN 44 INCHES ABOVE THE FLOOR. ALLOWABLE NO, - 17. GRAB BARS REQUIRED FOR ACCESSIBILITY SHALL BE 1,25 INCHES TO 1.5 INCHES IN DIAMETER WIRH 1.5 INCHES OF FLOORS 1 ,�• TR1JC TUBA' • 3 C ) CLEAR SPACE BETWEEN THE BAR AND THE WALL. WIND VELOCITY 146(EXP.C) 18. TOILET STALL DOORS SHALL BE THE SELF - CLOSING TYPE. FIRE RATING of 19. A TOWEL DISPENCER SHALL BE LOCATED ADJACENT TO ALL ACCESSIBLE LAVATORIES. EXT. WALLS O 20. WATER CLOSET FLUSH CONTROL SHALL BE MOUNTED ON THE WIDE SIDE OF THE CLOSET. PLAN No. . ALLOW. FLOOR 50100;/ ?, LOAD - APPROVAL DATE 12/ 12/2005 :. ... MANUFACTURER WDSPACE HIGH VELOCITY YES HURRICANE ZONE REVISION DATE: t ,, _ j >� '� DATE: 04 -05 -2011 NOTICE ., y ��w°. :,�<�\', DRAWN: R.C.S. PLEASE REVIEW PLANS COMPLETELY ANY L%I[ 9''' �•'�� ). ��+"y �� �.�► 'Z' �. JOB #: 14056AB COMPONENTS CROSSING MATE. LINES WILL °F ar.�< n r.. {' BE SITE INSTALLED BY SETUP CREW. r� T l,)r����aF9 ,_. .,�.�. ► .'s s� >��"_,; sr ono SHEET NO. JAIN ;• .I 1�. -� s f 3 F 4l Y w r} f ,�figy �.A r [ate i.Y o-B ' i © COPYRIGHT 2007- MODULAR PLANS DESIGN. CO. ,, - Os N O c ■ O Lin or) OM C14 r- 00 N` 4. o 'y Q Z00 Co a MECHANICAL NOTES: 1. ALL SUPPLY AIR REGISTERS SHALL BE 10 INCHES X 10 INCHES ADJUSTABLE w / 1.0 INCHES X 20 INCHES (INSIDE) OVERHEAD FIBERGLASS DUCT, UNLESS OTHERWISE SPECIFIED, nUCTS LOCATED IN VENILATED ATTIC SPACES SHALL HAVE AN R -6 INSULATION VALUE. DUCTS LOCATED IN UNCONDITIONED INTERIOR SPACE. INTERIOR SPACES SHALL HAVE AN R -4.2 INSULATION VALUE. 2. RESTROOM VENT FANS SHALL PROVIDE 50 CFM MINIMUM PER WATER CLOSET AND / OR URINAL. 3. VENT FANS SHALL BE DUCTED TO THE EXTERIOR AND TERMINATE AT ANI APPROVED VENT CAP. 4. HVAC EQUIPMENT SHALL BE EQUIPPED WIYH OUTSIDE FRESH INTAKES PROVIDING 20 CFM FOR EACH " OCCUPANT OR 50 CFM FOR EACH WATER HEATER CLOSET AND EACH URf :4AL, WHICH EVER IS GREATER. PLUMBING NOTES: 1. CUSTOME"MSUMES ALL RESPONSIBILITY FOR DRINKING WATER FACILITIES AND SERVICE SINK WHEN NOT SHOWN ON THE FLOOR PLAN. 2. TOILETS SHALL BE ELONGATED WITH NON - ABSORBENT OPEN FRONT SEAT. 3. RESTROOMS WALLS SHALL BE COVERED WITH NON - ABSORBENT MATERIAL TO A MINIMUM HEIGHT OF 48 INCHES A.F.F. 4. ALL PLUMBING FIXTURES SHALL HAVE SEPARATE SHUT -OFF VALVES. 5. WATER HEATER SHALL HAVE SAFTY PAN WITH 1 INCH DRAIN TO EXTERIOR, T & P RELIEF VALVE WITH DRAIN TO EXTERIOR, AND A SHUT OFF VALVE WITHIN 3 FEET ON A COLD WATER SUPPLY LINE, 6. DWV SYSTEM SHALL BE EITHER ABS OR PVC - DWV. 7. WATER SUPPLY LINES SHALL BE POLYBUTYLLENE, CPVC, OR COPPER; WHEN POLYBUTYLENE SUPPLY LINES ARE INSTALLED THE MAXIMUM WATER HEATER TEMPERATURE SFTtING IS 180° F. THE POLY - BUTYLENE PIPE SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURES LIMITATIONS AND INSTRUCTIONS. 8. WATER CLOSETS ARE TANK TYPE AND URINALS ARE FLUSH TANK TYPE UNLESS OTHERWISE SPECIFIED. 9. BUILDING DRAIN AND CLEANOUTS ARE DESIGNED AND SITE INSTALLED "3Y OTHERS. SUBJECT TO LOCAL JURISDICTION APPROVAL. 10. SHOWERS SHALL BE CONTROLLED BY AN APPROVED MIXING VALVE WITH A MAXIMUM WATER OUTLET TEMPERATURE OF 120° F (48.8° C). 11. THERMAL EXPANSION DEVICE, IF REQUIRED BY WATER HEATER INSTALLED, AND IF NOT SHOWN ON PLUMBING PLAN, IS DESIGNED AND SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 12. A WATER- HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK- CLOSING VALVES ARE UTILIZED, UNLESS OTHERWISE APPROVED. WATER HAMMER ARRESOTRS SHALL BE INSTALLED" IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. SITE INSTALLED NOTES: NOTE THAT THIS LIST DOES NOT NECESSARILY LIMITS THE ITEMS OF WORK AND MATERIALS THAT MAY BE REQUIRED FOR A COMPLETE INSULATION. ALL SITE RELATED ITEMS ARE SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 1. THE COMPLETE FOUNDATION SUPPORT AND TIE DOWN SYSTEM. 2. RAMPS, STAIRS AND GENERAL ACCESS TO THE BUILDING. 3. PORTABLE FIRE EXTINGUISHERS (S). 4. DRINKING FOUNTAIN, BUILDING DRAINS, CLEAN -OUTS, AND HOOK - UP TO PLUMBING SYSTEM. 5. ELECTRICAL SERVICE HOOK -UP ( INCLUDING FEEDERS) TO THE BUILDING. 6. THE MAIN ELECTRICAL PANEL AND SUB- FEEDERS ( MULTI -UNITS ONLY). , 7: CONNECTION OF ELECTRICAL CIRCUITS CROSSING OVER MODULE MATING LINES (S)-(MULTI-UNITS ONLY). 8. STRUCTURAL AND AESTHETIC INTERCONNECTIONS BETWEEN ' 9. WINDOW AND DOOR HIGH WIND STORM COVERINGS PER CODE. 10. GUTTERS AND DOWNSPOUTS ( IF APPLICABLE). 11. SINK AND CABINETS. 12. FIRE ALARM SYSTEM, WIRING, ETC. 13. THERMAL EXPANSION DEVICE IF REQUIRED. STATE CODES: FLORIDA 2009 FLORIDA BUILDING CODE* 2007 FPC w/ 2009 SUPPLEMENTS 2007 FMC w/ 2009 SUPPLEMENTS 2008 NEC * w/ 2009 SUPPLEMENTS OCCUPANCY B CONSTRUCTION TYPE V - B DRAWING INDEX: Cl COVER SHEET Al FLOOR PLAN A2 ELEVATIONS A3 BUILDING CROSS SECTION S1 FOUNDATION 9. ACCESSIBILE WATER CLOSETS SHALL BE 19 INCHS FROM THE FLOOR TO THE TOP OF THE SEAT. GRAB BARS SHALL BE 36 INCHES LONG MINIMUM WHEN LOCATEDBEHIND THE WATER CLOSET AND 42 INCHES MININUM WHEN LOCATED ALONG THE SIDE OF THE WATER CLOSET, AND SHALL BE MOUNTED 33 INCHES FROM THE ELEVATION NOTES TYP. FLOOR TO THE TOP OF THE RAIL WITH 0.5 INCH MAXIMUM VARIATION. 1.) SEE CROSS SECTION FOR METHOD OF ROOF VENTILATION i 10. ACCESSIBLE URINALS SHALL BE STALL -TYPE OR WALL HUNG WITH ELONGATED RIMS AT A MAXIMUM OF 17 2,) HANDICAP RAM(S), STAIRS (S), AND HANDRAILS ARE TO BE DESIGNED AND SITE ♦�'1 INCHES ABOVE THE FLOOR. INSTALLED BY OTHERS, SUBJECT TO,LOCAL JURISDICTION AND APPROVAL. �! 11. ACCESSIBLE LAVATORIES SHALL BE MOUNTED WITH THE RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR 3.( FOUNDATION ENCLOSURE ( WHEN PROVIDED) MUST HAVE 1 SQUARE FOOT NET AND A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE FLOOR TO THE BOTTOM OF THE APRON. VENT AREA PER 1/1 1/150th OF THE FLOOR AREA AND AN 18" X 24" MINIMUM` 12. ACCESSIBLE SINKS SHALL BE MOUNTED WITH RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR AND A CRAIAYL SPACE ACCESS, SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL CLEARANCE OF AT LEAST 27 INCHES HIGH, 30 INCHES WIDE, AND 19 INCHES DEEP UNDERNEAT SINK. JURISDICTION AND APPROVAL. n/ THE SINK DEPTH SHALL BE 6.5 INCHES MAXIMUM, 13. HOT WATER AND DRAIN PIPES UNDER ACCESSIBLE LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT CONTACT. INSULATION OR PROTECTION MATERAL MAY BE SITE V INSTALLED. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER ACCESSIBLE LAVATORIES AND SINKS. THESE PRINTS COMPLY WITH THE FLORIDA BUILDING CODE AND 14. ACCESSIBLE LAVATORIES AND SINKS SHALL HAVE ACCESSIBLE FAUCETS (ie. LEVER- OPERATED, PUSH -TYPE, ADHERE TO THE FOLLOWING CRITERIA. ELECTRONICALLY CONTROLLED). 15 WHERE MIRRORS ARE PROVIDED IN RESTROOM, AT LEAST ONE, SHALL BE PROVIDED WITH ITS BOTTOM ;I•i Y OF SOUTH MIAMI EDGE NO HIGHER THAN 40 INCHES ABOVE THE FIOOR. CONST. TYPE � -� )) ) )I G DEPT ° cl 16 WHERE MEDICINE CABINETS ARE PROVIDED, AT LEAST ONE SHALL BE LOCATED WITH A USABLE SHELF NO OCCUPANCY O HIGHER THAN 44 INCHES ABOVE THE FLOOR. ALLOWABLE NO, - 17. GRAB BARS REQUIRED FOR ACCESSIBILITY SHALL BE 1,25 INCHES TO 1.5 INCHES IN DIAMETER WIRH 1.5 INCHES OF FLOORS 1 ,�• TR1JC TUBA' • 3 C ) CLEAR SPACE BETWEEN THE BAR AND THE WALL. WIND VELOCITY 146(EXP.C) 18. TOILET STALL DOORS SHALL BE THE SELF - CLOSING TYPE. FIRE RATING of 19. A TOWEL DISPENCER SHALL BE LOCATED ADJACENT TO ALL ACCESSIBLE LAVATORIES. EXT. WALLS O 20. WATER CLOSET FLUSH CONTROL SHALL BE MOUNTED ON THE WIDE SIDE OF THE CLOSET. PLAN No. . ALLOW. FLOOR 50100;/ ?, LOAD - APPROVAL DATE 12/ 12/2005 :. ... MANUFACTURER WDSPACE HIGH VELOCITY YES HURRICANE ZONE REVISION DATE: t ,, _ j >� '� DATE: 04 -05 -2011 NOTICE ., y ��w°. :,�<�\', DRAWN: R.C.S. PLEASE REVIEW PLANS COMPLETELY ANY L%I[ 9''' �•'�� ). ��+"y �� �.�► 'Z' �. JOB #: 14056AB COMPONENTS CROSSING MATE. LINES WILL °F ar.�< n r.. {' BE SITE INSTALLED BY SETUP CREW. r� T l,)r����aF9 ,_. .,�.�. ► .'s s� >��"_,; sr ono SHEET NO. JAIN ;• .I 1�. -� s f 3 F 4l Y w r} f ,�figy �.A r [ate i.Y o-B ' i © COPYRIGHT 2007- MODULAR PLANS DESIGN. CO. ,, - Os N O c ■ O Lin or) OM C14 r- 00 N` V o 'y Q Z00 Co a CL LL` � WLL 0 A a MECHANICAL NOTES: 1. ALL SUPPLY AIR REGISTERS SHALL BE 10 INCHES X 10 INCHES ADJUSTABLE w / 1.0 INCHES X 20 INCHES (INSIDE) OVERHEAD FIBERGLASS DUCT, UNLESS OTHERWISE SPECIFIED, nUCTS LOCATED IN VENILATED ATTIC SPACES SHALL HAVE AN R -6 INSULATION VALUE. DUCTS LOCATED IN UNCONDITIONED INTERIOR SPACE. INTERIOR SPACES SHALL HAVE AN R -4.2 INSULATION VALUE. 2. RESTROOM VENT FANS SHALL PROVIDE 50 CFM MINIMUM PER WATER CLOSET AND / OR URINAL. 3. VENT FANS SHALL BE DUCTED TO THE EXTERIOR AND TERMINATE AT ANI APPROVED VENT CAP. 4. HVAC EQUIPMENT SHALL BE EQUIPPED WIYH OUTSIDE FRESH INTAKES PROVIDING 20 CFM FOR EACH " OCCUPANT OR 50 CFM FOR EACH WATER HEATER CLOSET AND EACH URf :4AL, WHICH EVER IS GREATER. PLUMBING NOTES: 1. CUSTOME"MSUMES ALL RESPONSIBILITY FOR DRINKING WATER FACILITIES AND SERVICE SINK WHEN NOT SHOWN ON THE FLOOR PLAN. 2. TOILETS SHALL BE ELONGATED WITH NON - ABSORBENT OPEN FRONT SEAT. 3. RESTROOMS WALLS SHALL BE COVERED WITH NON - ABSORBENT MATERIAL TO A MINIMUM HEIGHT OF 48 INCHES A.F.F. 4. ALL PLUMBING FIXTURES SHALL HAVE SEPARATE SHUT -OFF VALVES. 5. WATER HEATER SHALL HAVE SAFTY PAN WITH 1 INCH DRAIN TO EXTERIOR, T & P RELIEF VALVE WITH DRAIN TO EXTERIOR, AND A SHUT OFF VALVE WITHIN 3 FEET ON A COLD WATER SUPPLY LINE, 6. DWV SYSTEM SHALL BE EITHER ABS OR PVC - DWV. 7. WATER SUPPLY LINES SHALL BE POLYBUTYLLENE, CPVC, OR COPPER; WHEN POLYBUTYLENE SUPPLY LINES ARE INSTALLED THE MAXIMUM WATER HEATER TEMPERATURE SFTtING IS 180° F. THE POLY - BUTYLENE PIPE SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURES LIMITATIONS AND INSTRUCTIONS. 8. WATER CLOSETS ARE TANK TYPE AND URINALS ARE FLUSH TANK TYPE UNLESS OTHERWISE SPECIFIED. 9. BUILDING DRAIN AND CLEANOUTS ARE DESIGNED AND SITE INSTALLED "3Y OTHERS. SUBJECT TO LOCAL JURISDICTION APPROVAL. 10. SHOWERS SHALL BE CONTROLLED BY AN APPROVED MIXING VALVE WITH A MAXIMUM WATER OUTLET TEMPERATURE OF 120° F (48.8° C). 11. THERMAL EXPANSION DEVICE, IF REQUIRED BY WATER HEATER INSTALLED, AND IF NOT SHOWN ON PLUMBING PLAN, IS DESIGNED AND SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 12. A WATER- HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK- CLOSING VALVES ARE UTILIZED, UNLESS OTHERWISE APPROVED. WATER HAMMER ARRESOTRS SHALL BE INSTALLED" IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. SITE INSTALLED NOTES: NOTE THAT THIS LIST DOES NOT NECESSARILY LIMITS THE ITEMS OF WORK AND MATERIALS THAT MAY BE REQUIRED FOR A COMPLETE INSULATION. ALL SITE RELATED ITEMS ARE SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 1. THE COMPLETE FOUNDATION SUPPORT AND TIE DOWN SYSTEM. 2. RAMPS, STAIRS AND GENERAL ACCESS TO THE BUILDING. 3. PORTABLE FIRE EXTINGUISHERS (S). 4. DRINKING FOUNTAIN, BUILDING DRAINS, CLEAN -OUTS, AND HOOK - UP TO PLUMBING SYSTEM. 5. ELECTRICAL SERVICE HOOK -UP ( INCLUDING FEEDERS) TO THE BUILDING. 6. THE MAIN ELECTRICAL PANEL AND SUB- FEEDERS ( MULTI -UNITS ONLY). , 7: CONNECTION OF ELECTRICAL CIRCUITS CROSSING OVER MODULE MATING LINES (S)-(MULTI-UNITS ONLY). 8. STRUCTURAL AND AESTHETIC INTERCONNECTIONS BETWEEN ' 9. WINDOW AND DOOR HIGH WIND STORM COVERINGS PER CODE. 10. GUTTERS AND DOWNSPOUTS ( IF APPLICABLE). 11. SINK AND CABINETS. 12. FIRE ALARM SYSTEM, WIRING, ETC. 13. THERMAL EXPANSION DEVICE IF REQUIRED. STATE CODES: FLORIDA 2009 FLORIDA BUILDING CODE* 2007 FPC w/ 2009 SUPPLEMENTS 2007 FMC w/ 2009 SUPPLEMENTS 2008 NEC * w/ 2009 SUPPLEMENTS OCCUPANCY B CONSTRUCTION TYPE V - B DRAWING INDEX: Cl COVER SHEET Al FLOOR PLAN A2 ELEVATIONS A3 BUILDING CROSS SECTION S1 FOUNDATION 9. ACCESSIBILE WATER CLOSETS SHALL BE 19 INCHS FROM THE FLOOR TO THE TOP OF THE SEAT. GRAB BARS SHALL BE 36 INCHES LONG MINIMUM WHEN LOCATEDBEHIND THE WATER CLOSET AND 42 INCHES MININUM WHEN LOCATED ALONG THE SIDE OF THE WATER CLOSET, AND SHALL BE MOUNTED 33 INCHES FROM THE ELEVATION NOTES TYP. FLOOR TO THE TOP OF THE RAIL WITH 0.5 INCH MAXIMUM VARIATION. 1.) SEE CROSS SECTION FOR METHOD OF ROOF VENTILATION i 10. ACCESSIBLE URINALS SHALL BE STALL -TYPE OR WALL HUNG WITH ELONGATED RIMS AT A MAXIMUM OF 17 2,) HANDICAP RAM(S), STAIRS (S), AND HANDRAILS ARE TO BE DESIGNED AND SITE ♦�'1 INCHES ABOVE THE FLOOR. INSTALLED BY OTHERS, SUBJECT TO,LOCAL JURISDICTION AND APPROVAL. �! 11. ACCESSIBLE LAVATORIES SHALL BE MOUNTED WITH THE RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR 3.( FOUNDATION ENCLOSURE ( WHEN PROVIDED) MUST HAVE 1 SQUARE FOOT NET AND A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE FLOOR TO THE BOTTOM OF THE APRON. VENT AREA PER 1/1 1/150th OF THE FLOOR AREA AND AN 18" X 24" MINIMUM` 12. ACCESSIBLE SINKS SHALL BE MOUNTED WITH RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR AND A CRAIAYL SPACE ACCESS, SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL CLEARANCE OF AT LEAST 27 INCHES HIGH, 30 INCHES WIDE, AND 19 INCHES DEEP UNDERNEAT SINK. JURISDICTION AND APPROVAL. n/ THE SINK DEPTH SHALL BE 6.5 INCHES MAXIMUM, 13. HOT WATER AND DRAIN PIPES UNDER ACCESSIBLE LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT CONTACT. INSULATION OR PROTECTION MATERAL MAY BE SITE V INSTALLED. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER ACCESSIBLE LAVATORIES AND SINKS. THESE PRINTS COMPLY WITH THE FLORIDA BUILDING CODE AND 14. ACCESSIBLE LAVATORIES AND SINKS SHALL HAVE ACCESSIBLE FAUCETS (ie. LEVER- OPERATED, PUSH -TYPE, ADHERE TO THE FOLLOWING CRITERIA. ELECTRONICALLY CONTROLLED). 15 WHERE MIRRORS ARE PROVIDED IN RESTROOM, AT LEAST ONE, SHALL BE PROVIDED WITH ITS BOTTOM ;I•i Y OF SOUTH MIAMI EDGE NO HIGHER THAN 40 INCHES ABOVE THE FIOOR. CONST. TYPE � -� )) ) )I G DEPT ° cl 16 WHERE MEDICINE CABINETS ARE PROVIDED, AT LEAST ONE SHALL BE LOCATED WITH A USABLE SHELF NO OCCUPANCY O HIGHER THAN 44 INCHES ABOVE THE FLOOR. ALLOWABLE NO, - 17. GRAB BARS REQUIRED FOR ACCESSIBILITY SHALL BE 1,25 INCHES TO 1.5 INCHES IN DIAMETER WIRH 1.5 INCHES OF FLOORS 1 ,�• TR1JC TUBA' • 3 C ) CLEAR SPACE BETWEEN THE BAR AND THE WALL. WIND VELOCITY 146(EXP.C) 18. TOILET STALL DOORS SHALL BE THE SELF - CLOSING TYPE. FIRE RATING of 19. A TOWEL DISPENCER SHALL BE LOCATED ADJACENT TO ALL ACCESSIBLE LAVATORIES. EXT. WALLS O 20. WATER CLOSET FLUSH CONTROL SHALL BE MOUNTED ON THE WIDE SIDE OF THE CLOSET. PLAN No. . ALLOW. FLOOR 50100;/ ?, LOAD - APPROVAL DATE 12/ 12/2005 :. ... MANUFACTURER WDSPACE HIGH VELOCITY YES HURRICANE ZONE REVISION DATE: t ,, _ j >� '� DATE: 04 -05 -2011 NOTICE ., y ��w°. :,�<�\', DRAWN: R.C.S. PLEASE REVIEW PLANS COMPLETELY ANY L%I[ 9''' �•'�� ). ��+"y �� �.�► 'Z' �. JOB #: 14056AB COMPONENTS CROSSING MATE. LINES WILL °F ar.�< n r.. {' BE SITE INSTALLED BY SETUP CREW. r� T l,)r����aF9 ,_. .,�.�. ► .'s s� >��"_,; sr ono SHEET NO. JAIN ;• .I 1�. -� s f 3 F 4l Y w r} f ,�figy �.A r [ate i.Y o-B ' i © COPYRIGHT 2007- MODULAR PLANS DESIGN. CO. ,, -