14-998-018FANS L S LOCATION N.T.S. SCALE NOTES: 1- ALL RECEPTACLES SHALL BE UL LISTED HOSPITAL GRADE 2- ALL LIGHTING FIXTURES SHALL BE UL LISTED HOSPITAL GRADE 3- ELECTRICAL CONTRACTOR SHALL FIELD VERIFY THE CONDITIONS OF WIRING, J- BOXES, CONDUITS, SWITCHES AND RECEPTACLES AND RE -USE IF IS POSSIBLE. 4- ALL BRANCH CIRCUITS IN PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13 (A) AND (B). REDUNDANT GROUNDING SCHEME AND INSULATED EQUIPMENT GROUNDING CONDUCTOR FOR RECEPTACLES. 5- ELECTRICAL CONTRACTOR SHALL VERIFY THAT ALL BREAKERS IN PANELS SHALL COMPLY WITH SAME LCA 6- DESIGN HAVE BEEN BASED ON PANEL INFORMATION, AS -BUILD DRAWINGS AND PARTIAL ROOM VISITS. ELECTRICAL CONTRACTOR SHALL VERIFY ALL ASSOCIATES PANELS INFORMATION DURING CONSTRUCTION AND COMMUNICATED ANY MAJOR DISCREPANCY TO THE ENGINEER. 7- CRITICAL OUTLET PLATE SHALL BE RED AND PERMANENT ENGRAVED CIRCUIT NUMBER IN WHITE COLOR. 8- NORMAL OUTLET PLATE SHALL BE WHITE AND PERMANENT ENGRAVED CIRCUIT NUMBER IN BLACK COLOR. 9- NOT STICK CIRCUIT NUMBER IS ALLOW. 10- EXISTING CIRCUITS NUMBER INFORMATION SHALL BE ENGRAVE IN A NEW PLATE. 11- ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED TYPED WRITTEN PANEL DIRECTORIES INDICATING TYPE OF LOAD AND LOCATION FOR ALL ELECTRICAL PANELS USED IN THIS PROJECT. 12- ANY FIRE WALL PENETRATION SHALL BE SEAL TO KEEP THE FIRE RATE. 13- ALL PANELS SHALL BE BOUNDED WITH ONE # 10 THWN AS PER NEC 517.14. 14- FIRE ALARM CONTRACTOR SHALL PROVIDE TEST REPORT OF ALL NEW EXISTING AND RELOCATED IN THE PROJECT AND RECORD OF COMPLETION AT 100% AHCA INSPECTION. 15- ELECTRICAL CONTRACTOR SHALL KEEP ONE EXIT LIGHT AND EMERGENCY ILLUMINATION IN THE MAIN OF EGRESS DURING CONSTRUCTION CONNECTED TO LIFE SAFETY PANEL EXISTING MAIN ELECTRICAL ROOM EXISTING PANEL 'DP5' 120/208V 600A, 30 500A MB EXISTING EXISTING PANEL 'L' 120/208V 200A, 30 EXISTING 4 #3 /OTHWN + 1 # 6 (GND) in 2" C. PARTIAL NORMAL POWER RISER N.T.S. PARTIAL LIFE SAFETY POWER RISER N.T.S. PARTIAL CRITICAL BRANCH POWER RISER N.T.S. FAULT CHIT CALCULATION SERVICE FEEDER: • #300 NUMBER OF CONDUCTORS PER PHASE.- •3 CONDUCTOR LENGTH 1 ":• •18' IIIIIIII■ �i •16,700 E 0.15 M - -I- - 1 = 0.8696 1 +f 1 +0.15 ISCA - AVAILABLE FROM TPL' X M - 50,221 X 0.8696 - 43,672 AMPS ISCA - 43,672 AMP AT PANEL. 'DP5' ISCA - AVAILABLE FROM TPL' X M = 50,221 SERVICE FEEDER: • #3/0 NUMBER OF CONDUCTORS PER PHASE.-. •1 CONDUCTOR LENGTH "C.- •112' CONDUCTOR "C" VALUE- • \I \Z IPA \� 3.665 C X EL -L 11,100 X 208 1.73XLX1 = 1.73 X55X24.186 �_ = 1 = M 0.2144 C X EL -L 1,950 X 208 1 + f 1 + 3.665 � a ISCA - 9,363A AT PANEL 'L' X 0.0969 = 3,118 AMPS ISCA = AVAILABLE FROM 'DP3' X M = 24,186 X 0.1498 = 3,623 AMPS ISCA = 3,623A AT PANEL 'LSA' 1 ' _ ' iii ......; ,.......�. " � �I • will _ ...... .--- ...... .. II ; LEM a •• a FANS L S LOCATION N.T.S. SCALE NOTES: 1- ALL RECEPTACLES SHALL BE UL LISTED HOSPITAL GRADE 2- ALL LIGHTING FIXTURES SHALL BE UL LISTED HOSPITAL GRADE 3- ELECTRICAL CONTRACTOR SHALL FIELD VERIFY THE CONDITIONS OF WIRING, J- BOXES, CONDUITS, SWITCHES AND RECEPTACLES AND RE -USE IF IS POSSIBLE. 4- ALL BRANCH CIRCUITS IN PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13 (A) AND (B). REDUNDANT GROUNDING SCHEME AND INSULATED EQUIPMENT GROUNDING CONDUCTOR FOR RECEPTACLES. 5- ELECTRICAL CONTRACTOR SHALL VERIFY THAT ALL BREAKERS IN PANELS SHALL COMPLY WITH SAME LCA 6- DESIGN HAVE BEEN BASED ON PANEL INFORMATION, AS -BUILD DRAWINGS AND PARTIAL ROOM VISITS. ELECTRICAL CONTRACTOR SHALL VERIFY ALL ASSOCIATES PANELS INFORMATION DURING CONSTRUCTION AND COMMUNICATED ANY MAJOR DISCREPANCY TO THE ENGINEER. 7- CRITICAL OUTLET PLATE SHALL BE RED AND PERMANENT ENGRAVED CIRCUIT NUMBER IN WHITE COLOR. 8- NORMAL OUTLET PLATE SHALL BE WHITE AND PERMANENT ENGRAVED CIRCUIT NUMBER IN BLACK COLOR. 9- NOT STICK CIRCUIT NUMBER IS ALLOW. 10- EXISTING CIRCUITS NUMBER INFORMATION SHALL BE ENGRAVE IN A NEW PLATE. 11- ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED TYPED WRITTEN PANEL DIRECTORIES INDICATING TYPE OF LOAD AND LOCATION FOR ALL ELECTRICAL PANELS USED IN THIS PROJECT. 12- ANY FIRE WALL PENETRATION SHALL BE SEAL TO KEEP THE FIRE RATE. 13- ALL PANELS SHALL BE BOUNDED WITH ONE # 10 THWN AS PER NEC 517.14. 14- FIRE ALARM CONTRACTOR SHALL PROVIDE TEST REPORT OF ALL NEW EXISTING AND RELOCATED IN THE PROJECT AND RECORD OF COMPLETION AT 100% AHCA INSPECTION. 15- ELECTRICAL CONTRACTOR SHALL KEEP ONE EXIT LIGHT AND EMERGENCY ILLUMINATION IN THE MAIN OF EGRESS DURING CONSTRUCTION CONNECTED TO LIFE SAFETY PANEL EXISTING MAIN ELECTRICAL ROOM EXISTING PANEL 'DP5' 120/208V 600A, 30 500A MB EXISTING EXISTING PANEL 'L' 120/208V 200A, 30 EXISTING 4 #3 /OTHWN + 1 # 6 (GND) in 2" C. PARTIAL NORMAL POWER RISER N.T.S. PARTIAL LIFE SAFETY POWER RISER N.T.S. PARTIAL CRITICAL BRANCH POWER RISER N.T.S. FAULT CHIT CALCULATION SERVICE FEEDER: • #300 NUMBER OF CONDUCTORS PER PHASE.- •3 CONDUCTOR LENGTH 1 ":• •18' CONDUCTOR "C" VALUE •16,700 18X = C X EL -L 3(16,700) X 50.221 208 0.15 M - -I- - 1 = 0.8696 1 +f 1 +0.15 ISCA - AVAILABLE FROM TPL' X M - 50,221 X 0.8696 - 43,672 AMPS ISCA - 43,672 AMP AT PANEL. 'DP5' ISCA - AVAILABLE FROM TPL' X M = 50,221 SERVICE FEEDER: • #3/0 NUMBER OF CONDUCTORS PER PHASE.-. •1 CONDUCTOR LENGTH "C.- •112' CONDUCTOR "C" VALUE- • •11,100 1.73 X L X I = 1.73 X 112 X 43.672 = 3.665 C X EL -L 11,100 X 208 1.73XLX1 = 1.73 X55X24.186 �_ = 1 = M 0.2144 C X EL -L 1,950 X 208 1 + f 1 + 3.665 _ -- __ 1 1 M = 0.1498 ISCA = AVAILABLE FROM 'DP5' X M = 43,672 X 0.2144 = 9,363 AMPS ISCA - 9,363A AT PANEL 'L' X 0.0969 = 3,118 AMPS FAULT CHIT CALCULATION SERVICE FEEDER: - /3 NUMBER OF CONDUCTORS PER PHASE:. •1 CONDUCTOR LENGTH "C.. •10' CONDUCTOR "C" VALUE. • •3,880 1.73XLX1 1.73X 10X50.221 - 1,0765 C X EL -L (3,880) X 208 M - -1- - 1 - 0.4816 1 + f 1 + 1.0765 X 0.6407 = 32,177 AMPS ISCA - AVAILABLE FROM TPL' X M = 50,221 X 0.4816 - 24,186 AMPS ISCA - 24,186 AMP AT PANEL 'DP3' #3 SERVICE FEEDER: • #6 NUMBER OF CONDUCTORS PER PHASE­ •1 CONDUCTOR LENGTH Z" :• •55' CONDUCTOR "C" VALUE: • •1,950 1.73XLX1 = 1.73 X55X24.186 = 5.6738 C X EL -L 1,950 X 208 _ -- __ 1 1 M = 0.1498 1 + f 1 + 5.6738 X 0.0969 = 3,118 AMPS ISCA = AVAILABLE FROM 'DP3' X M = 24,186 X 0.1498 = 3,623 AMPS ISCA = 3,623A AT PANEL 'LSA' FAULT CURRENT CALCULATION SERVICE FEEDER: • #250 NUMBER OF CONDUCTORS PER PHASE.- •1 CONDUCTOR LENGTH "L ":• -20' CONDUCTOR "C" VALUE: - • 14,900 1.73 X L X I = 1.73 X 20 X 50.221 C X EL -L (14,900) X 208 = 0.5606 M - - 1 = 1 = 0.6407 1 + f 1 + 0.5606 ISCA = AVAILABLE FROM 'FPL' X M = 50,221 X 0.6407 = 32,177 AMPS ISCA = 32,177 AMP AT PANEL 'DP4' SERVICE FEEDER:. #3 NUMBER OF CONDUCTORS PER PHASE.- - 1 CONDUCTOR LENGTH "L":• •135' CONDUCTOR 'C" VALUE - .3,880 1.73XLX1 = 1.73X 135'X32.177= 83117 C X EL -L 3.880 X 208 M =-1 - 1 - 0.0969 1 + f 1 + 9.3117 ISCA - AVAILABLE FROM 'DP4' X M - 32,177 X 0.0969 = 3,118 AMPS ISCA - 3,118A AT PANEL 'EC1' ELECTRICAL &ORMCATIM PART 1- C&SUAL -- ----- - - -_ _ :_ A.- Overall Installation: The installation shall comply with 2008 edition of Electrical Code (NEC). the Florida Building Code (FBC) 2010 with 2009 revision, Life safety code 101 -2009, NFPA -99 2005, FGI -2010 and any other applicable Federal, State and Local codes. B.- Conductor Calculations: Conductor calculations are based on 75 •C. 1. General: The General and Special Conditions and Requirements of the Contract and Specifications as well as plans and specifications of other disciplines and trades shall be a part of the work hereby specified. These specifications and accompanying plans are intended to provide for the complete furnishing and installation of the elec- trical systems. To provide means to furnish and install. 2. Compliance: Workmanship, materials and installation shall be in strict accordance with the applicable edition of the NEC,NFPA,NEMA,ASTM. OSHA. HRS health agencies, and other applicable national, state, and local codes and pertaining regulations established by the ruling authority having jurisdiction. Contractors shall also meet the requirements of other standards where such requirements are more strict than those standards cited above. 3. Workmanship: All work shall be performed by contractors licensed in their respective discipline. Work shall be done in a first class manner, fully operative, and to the acceptance of the Architect and the Engineers. Contractor shall provide for all necessary labor and material required for the completion of the work including but not limited to related work such as connection of existing systems, exca- vations and back filling. 4. Materials: Contractor shall provide all new materials of American ma- nufacture, bearing the Underwriter's Laboratory (UL) label as appli- cable. Materials shall be new, suitable for the application and above standard quality normally used for the purpose as called for on plans. Supplemental materials, products and components necessary to comply with the intent of the Contract drawings and /or specifications, but not noted or specified on these sections, shall be provided by the Contractor as required for the completion of the work at no additio- nal cost to the Owner. Contractor shall be responsible for provisions and coordination of delivery of materials. Equipment marred during shipment or installation shall be touched up and refinished to factory finish, replaced where not acceptable. 5.- Permits and Insurance: Contractor shall secure and pay for all permits. fees, taxes, inspections, tests, fines and other items as required for the installation of the complete electrical systems as outlined herein and shown on plans. Contractor shall provide all required insurance for protection against public liability and property damage for the duration of the work. 6.- Existing conditions: Before bidding. the contractor shall visit the job site and ascertain all existing conditions which will affect his work. Failure to do so will not be accepted as a reason for requesting extra pay where the existing conditions result in extra materials or Any existing conditions found by the Contractor which will adversely affect the work shall be immediately be brought to the attention of the Architect /Engineer. Correction of any defects shall be completely without additional charge and shall include replacements or repair of any other phase of the installation which may have been damaged thereby. 7.- Plans: Drawings are basically diagrams intended to depict approximately equipment locations and arrangements, not to show every minor detail. Plans shall not be scaled to determine exact location and dimensions. 8.- Interference: The Contractor shall coordinate his work with other trades so that interference with existing conditions, conduits, piping, equipment, architectural and structural members be avoided. 9.- Substitutions: Products and materials called out by trade name and /or catalog numbers establish a standard of quality, appearance, perfor- mance and dimension. Contractors shall base his proposal on those items as they shall be considered as a standard basis of bidding. Requests for substitution shall be submitted in writing to the Archi- tect /Engineer, demonstrating that product is of comparable and basic design, construction, standards and warranties, dimensions to fit wi- thout change, and does not cause extra work to other trades. Contractor shall be responsible for providing equality of substitution: Architect /Engineer will, under no circumstances, be required to prove such item is or is not of equal quality to the specified item. Archi- tect /Engineer expenses incurred due to Contractor's requested revi- sions or substitutions shall be paid by the Contractor. 10.- Record Drawings: Maintain a complete set of prints for indicating all changes. Use colored pens to mark changes at the time of exe- cution and deliver the set to the Architect /Engineer upon completion. Contractor shall stamp "As Built" on prints and plans, date and sign in ink. 11.-In comprionce with FBC 419.3.15.3 and NFPA 99 4.3.3 an Equipotentlal Grounding Test Report will be provided by the contractor at the completion of all equipment installation in Patient Care areas. 12.Conductor: All conductor wire abd cable shall consist of 98% conductivity copper, all cables shall be single conductors, 600 volt thermoplastic insulation. Suitable for continuous operation at 75 degrees c. Conductor temperature in both wet and dry locations. These cables shall be NEC insulation classification type thwn /thhn. Minimum size shall be # 12. All conductor installation shall be color coded maintaining. the integrity of the existing installation. Colored insulation shall . �a l used for AWG sizes 110 and smaller . and approved color tapes shall be used for AWG sizes 18. and larger all power and control circuits shall carry equipment grounding ' conductor sized per NEC article 250. INTERIOR MODIFICATIONS ONLY TER(ANY EXIOR NIODIFICA•r10N h1AY REQUIRE A SOA::D A °.PEARANCE) KEY PLAN FIRST FLOOR MWAI DAB GOLlWy F= DE14 Revisions: AREV11 08/01/14 D AHCA COMM. 0 zn� Z� 0 Z Colin On No-$ <C 0151 R LQ V) .z• Z W ::E0 <V W � z< H C7 w� PLO C) sw-vw �.x <aas;� O C • oil 4-0 r 1 0 Z,* Z z V k Z < a•r e 4 V 4 PERMIT SET 08/01/14 r2' DRAWN: IA CHECKED: Des DATE: 01 -29 -14 SCALE: AS SHOWN SEAL • . r • , NORTH � - • •4 I e(o w • , ~ V • Iff= O X Sheet No. E -2 OF 2 JOB # 201426 �Y GUIROLA & ASSOCIATES P.A. CONSULTING ENGINEERS P.E. No 57468 David Guirola Electrical Engineer 1150 NW 72nd AVE, S -451 - MIAMI, FLORIDA 33128 P.H: (305) 513 4)665 CA 00009112 EMAIL: GUIRO 5CAOLCOM .j.,. i � '