14-998-014ECO �\''
>
�� <
�'' 1/2" TRAP
PRIMER
(TYP)
- I
FD -1
LAV LAV
FD -1 SINK
1 /2" TRAP
PRIMER
(TYP)
SANITARY ISOMETRIC
SCALE: N.T.S.
T•
PHILLIPS CONCRETE
FASTENER I.T.T. GRINNELL
(RED HEAD)
ALL THREAD
HANGER ROD
PIPE
SIZE
D
DIMENSION
1 IN.
1/8
IN.
1 1/4
IN. 1/8
IN.
1 1/2
IN. 1/8
IN.
2 IN.
1/4
IN.
2 1/2
1 IN. 1/4
IN.
D
DIMENSION
I
PIPE HANGER RING PIPE
LT. T. GRINNELL FIG.260
PIPE HANGER RING
LT. T. GRINNELL FIG. 69
PIPES 3" & SMALLER PIPES 4" & LARGER
-
U.L./F.M. APPROVED
CONCRETE INSERT
PIPING HANGER DETAIL
SCALE: N.T.S.
�J li
GENERAL NOTES:
1. ALL SANITARY PIPING TO BE SLOPED PER FLORIDA
BUILDING CODE 2010 SECTION 704.1
2. ALL SANITARY PIPING 2" & LESS TO BE SLOPED
@ 1 /4 " /FT. ALL SANITARY PIPING 3"& LARGER
TO BE SLOPED @ 1 18 " /FT UNLESS EXCEPT WHERE
THEY ARE CONNECTED TO A 2" BRANCH, THEN THE
BRANCH SHALL BE SLOPPED AT 114 " /FT TO MAINTAIN
UNIFORM SLOPE PER FBC 704.1.
3. PROVIDE CLEANOUTS AT BASE OFALL STACKS.
SHOCK
ARRESTOR SCHEDULE
P.D.I. DESIGNATION
MANUF. do MODEL
FIXTURE UNITS
CONNECTION
A
SIOUX CHIEF 652 -A
1 -11
1/2"
B
SIOUX CHIEF 653 -B
12 -32
3/4-
C
SIOUX CHIEF 654 -C
33 -60
1"
SIOUX CHIEF SHOCK ARRESTORS APPROVED FOR INSTALLATION WITH NO
ACCESS DOOR REQUIRED. CONFORMS TO ANSI /ASSE 1010 STANDARDS.
Ak '
" 1
T —1 LAV J
\ SINK F260S
1�
i
LAV TP -1 E22S
NEW CONSTRUCTION LEGEND
SYMBOL
DESCRIPTION
FITTING AMSCO
EXISTING TO REMAIN
REMARKS
NEW CONSTRUCTION
--®
CONNECT TO EXIST. AT THIS POINT
PLUMBING DRAIN SCHEDULE
SHEET
N0.
SYMBOL
FITTING AMSCO
WASTE
REMARKS
MANUFACTURER
MODEL
TYPE
FD -1
JAY R. SMITH
FLOOR DRAIN
#3101 -Y12
112. GRATE
AS SHOWN
IN PLAN
WITH TRAP
PRIMER
DOMESTIC ISOMETRIC RISER
SCALE: N.T.S.
PLUMBING - DEMOLITION NOTES:
1. CONTRACTOR SHALL REMOVE EXISTING SERVICES TO EXISTING
EQUIPMENT WHICH IS TO BE REMOVED, OR RELOCATED AS INDICATED
AND SHOWN ON THE DRAWINGS. PERMANENTLY SEAL AND CAP SERVICES
NEXT TO MAIN SERVICE LINES ABOVE CEILING, IN WALLS.
2. EXISTING FIXTURES, EQUIPMENT, SERVICES, AND CONNECTIONS TO
REMAIN AS IS, WHICH ARE DAMAGED DURING CONSTRUCTION, SHALL BE
REWORKED OR REPLACED AS REQUIRED TO PROVIDE ORIGINAL
OPERATION.
3. PENETRATIONS OR OPENINGS FROM REMOVED PIPES THROUGH EXISTING
WALLS AND FLOORS SHALL BE SLEEVED AND /OR PATCHED TO MATCH THE
EXISTING STRUCTURE. SEE ARCHITECTURAL DRAWINGS FOR FINAL
FINISHES.
4. CONTRACTOR SHALL COORDINATE INTERRUPTION OF EXISTING SERVICES;
WITH OWNER, BEFORE CONSTRUCTION.
5. REPAIR /REPLACE EXISTING VALVES WHICH DO NOT HOLD WHEREVER NEW
PIPING IS CONNECTED TO EXISTING PIPING, AND THE EXISTING
VALVES ARE TO BE REUSED.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION
AND CONSTRUCTION DEBRIS GENERATED FROM WORK ON ALL FLOORS.
7. CONTRACTOR IS ADVISED THAT LOCATIONS SHOWN FOR EXISTING
MEDICAL GAS SERVICES ARE APPROXIMATE. CONTRACTOR SHALL
FIELD VERIFY LOCATIONS, MATERIALS AND SIZES OF PLUMBING
SERVICES PRIOR TO CONSTRUCTION. CONTRACTOR SHALL BRING
DISCREPANCIES BETWEEN THE NEW CONSTRUCTION DRAWINGS AND
THE EXISTING CONDITIONS TO THE ARCHITECT'S ATTENTION FOR
COORDINATION PRIOR TO CONSTRUCTION.
8. CONTRACTOR SHALL SUBMIT A COMPLETE LIST OF EQUIPMENT THAT
ARE TO BE REMOVED TO THE LOCAL OWNER'S REPRESENTATIVE.
ALL ITEMS THAT THE LOCAL OWNER'S REPRESENTATIVE WISHES TO
RETAIN SHALL BE PLACED IN STORAGE AND THE REMAINDER SHALL
BE REMOVED FRO&I THE SITE AND LEGALLY DISPOSED.
PLUMBING FIXTURE SCHEDULE
SHEET
N0.
FIXTURE
FITTING AMSCO
FLOOR
P2.1
PARTIAL PLUMBING NEW WORK PLAN
Ld
SYMBOL
LLJ
LIJ
MOUNTED
C. W
H. W.
WASTE
REMARKS
/
V n)
LJ
- J
--j z
Q
D —
[):�
C) m
Li
MANUFACTURER
MODEL
TYPE
SIZE
MANUFACTURER
TYPE
SUPPLY
TRAP
FAUCET
CARRIER
LAV
KOHLER (HC)
KINGSTON
WALL HUNG
5" BACKSPLASH
21"X18"
#155WC GRID DRAIN
#88721114 "P-
CHICAGO FAUCET
Z
MOUNT
LAVATORY
K -2005
CONCEALED ARM
McGUIRE
WITH PRO WRAP
H -2165
TRAP OFFSET FOR
#895 -317CP
Z -1231
123
1 / 2"
1 / 2"
1 1/4 "
34" A.F.F.
VITREOUS CHINA
4" FAUCET CTR
#PW2125 -WC
WHEEL CHAIR USE
WRISTBLADE HANDLE
TO RIM
FX -20
JUST- (STAFF)
#SLX- 2019 -A -GR
SINGLE COMP.
(S.S.) GAUGE
14 "X16 "X101/2"
McGUIRE
GRID DRAIN
H -2165
#8912
„
CHICAGO FAUCET
NA
e.
1/2
112
1 112 fr
NA
S.S. SINK
SELF - RIMMING
#151
1 1/2 -
P TRAP
#786- GN2FCCP
E -22 -S
WHITEWALL
STATIONARY
E -22 -S OWNER
NA
NA
NA
NA
H -2165
NA
NA
NA
112”
1/2"
2"
NA
WHIRLPOOL
FURNISHED
F -260 -S
WHITEWALL
WHIRLPOOL
E -260 -S OWNER
NA
NA
NA
NA
H -2165
NA
NA
NA
3/4"
3/4"
3"
NA
TANK
FURNISHED
TP -1
P.P.P. PRIME -RITE
PR -500
NA
NA
NA
NA
NA
NA
NA
NA
1/2"
SIZE AS REQUIRED TO
SERVE NUMBER OF
TRAP PRIMER
DRAIN
REGULATORY REQUIREMENTS
A. NFPA 101: LIFE SAFETY CODE (2009).
B. FGI - 2010 FACILITIES GUIDELINES INSTITUTE
C. ANSI HANDICAPPED CODE A117.1.
D. FLORIDA BUILDING CODE 2010
E. FLORIDA FIRE PREVENTION CODE - 2010 EDITION
F. NFPA 99: STANDARD FOR HEALTH CARE
FACILITIES (2005).
PLUMBING - GENERAL NOTES:
1. ALL EXISTING WORK NOT SHOWN ON THESE DRAWINGS
(UNLESS NOTED OTHERWISE) SHALL REMAIN AS IS.
2. THE CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS
AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE
TO PLUMBING DESIGN /ENGINEERING UNLESS IT HAS BEEN
COORDINATED DRAWN, AND SUBMITTED FOR APPROVAL TO
THE ARCHITECT.
3. CONTRACTOR SHALL COORDINATE WITH ALL
DISCIPLINES INVOLVED SO AS TO AVOID ANY PIPE
ROUTING PROBLEMS.
WARRANTY /GUARANTEE
THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN
THE STABILITY OF WORK AND MATERIALS AND KEEP SAME IN
PERFECT REPAIR AND CONDITION OF THE PERIOD OF ONE YEAR.
DEFECTS OF ANY KIND DUE TO THE FAULTY WORK OR MATERIALS
APPEARING DURING THE ABOVE MENTIONED PERIOD MUST BE
IMMEDIATELY MADE GOOD BY THE CONTRACTOR AT HIS OWN
EXPENSE TO THE ENTIRE SATISFACTION OF THE OWNER AND
ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL
INCLUDE DAMAGE TO THE FINISH OR FURNISHING OF THE
BUILDING RESULTING FROM THE ORIGINAL DEFECTOR REPAIR
THERETO.
PLUMBING SPECIFICATIONS
PLUMBING MATERIALS
PLUMBING SYSTEMS SHALL BE INSTALLED IN
ACCORDANCE WITH SOUTH FLORIDA PLUMBING
BUILDING CODE AND ADA REQUIREMENTS.
WASTE AND VENT. NO HUB SERVICE WEIGHT CAST IRON ABOVE FLOOR, BELL
AND SPIGOT WITH NEOPRENE GASKET BELOW FLOOR.
WATER: DOMESTIC COLD, HOT WATER PIPING SHALL BE TYPE "L" HARD
DRAWN COPPER WITH WROUGHT FITTINGS, WITH 9515 LEAD FREE SOLDERED
JOINTS. TYPE "K" COPPER BELOW FLOOR SLAB. INSULATE HOT WATER
AND HOT WATER RECIRCULATION PIPING USING 1" THICK FIBERGLASS
INSULATION HAVING A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE
DEVELOPMENT OF 50 OR LESS IN ACCORDANCE WITH ASTM E -84, NPFA 225
AND UL 723. FOAMGLASS INSULATION SHALL BE USED WHERE PIPING
PENETRATES RATED WALLS.
TEST WATER AND WASTE PIPING AS PER LOCAL CODES.
PLUMBING FIXTURES: KOHLER, AMERICAN STANDARD, EVER.
PLUMBING TRIM: CHICAGO, SPEAKMAN
FLUSH VALVES: SLOAN ROYAL, ZURN
STAINLESS STEEL SINK. ELKAY OR JUST
PLUMBING FIXTURES
PROVIDE PLUMBING FIXTURES, TRIM AND RELATED ITEMS SUCH AS
SUPPLIES, TRAPS, DRAINS, CLEANOUTS, WATER CLOSET SEATS AND
COVERS, FIXTURE SUPPORTS AND OTHER ACCESSORY ITEMS. COORDINATE
FIXTURE REQUIREMENTS BY REVIEWING ARCHITECTURAL AND EQUIPMENT
DRAWINGS. INSTALL FIXTURES IN ACCORDANCE WITH CONTRACT DRAWINGS
AND MANUFACTURER'S ROUGH IN DRAWINGS. WALL HUNG LAVATORIES SHALL
BE PROVIDED WITH FLOOR MOUNTED CARRIERS.
MATERIALS VALVES
1. BALL VALVES - 2" AND LESS:
A. DOMESTIC WATER: FIGURE T585 -70 ORS-585-70,2-PIECE,
FULL PORT. 600 PSI, WOG, TFE SEATS.
B. PROVIDE BALL VALVES WITH LOCKING HANDLES.
C. PROVIDE EXTENDED LEVER FOR INSULATED SERVICE.
PLUMBING DRAWING INDEX
SHEET
N0.
DESCRIPTION
PD.1
GENERAL NOTES, DETAILS &RISERS - PLUMBING
P2.1
PARTIAL PLUMBING NEW WORK PLAN
INTERIOR MODIFICATIONS ONLY
(ANY EXTERIOR MODIFICATION MAY REQUIRE
A BOARD APPEARANCE)
MIAMI -DADE COUNTY
FIRE DEPARTMENT
1.•
KEY PLAN -
FIRST FLOOR
VIETB. NGUYEN, P.E.
MECHANICAL ENGINEER
P.E.l1 69753 MJM Job # 2014027 .
rMJM ENGINEERING INC.
MECHANICAL, ELECTRICAL & FIRE PROTECTION
TM ENGINEERING CONSULTING SERVICES
VVJ 12717 wsUNRLSE BLVD SuRe 21s
Sums& n 33313
CA No: 30046
Tel:(9 74)- 536 -8426
mjmonterora comcast.net
mjm <<-comcact.net
Revisions:
A
D
0
i— Q
0. 0.
w=
::D
V z
I_ D
z�
w
.72o Q U
wZ.
=<
V)
Z a
H
P4 a
U2
0
a x
.. V
0
y
V i
0
DRAWN:•
(f)
CHECKED:
Q_
DATE:
zz
-
Ld
0 _
LLJ
LIJ
I-
0
.,
2
/
V n)
LJ
- J
--j z
Q
D —
[):�
C) m
Li
W >
Z-
1E
W
0- J
CD(n0-
PERMIT
SET
08/01/14
DRAWN:•
JM _
CHECKED:
JM
DATE:
07 -29 -14
SCALE:
AS SHOWN
Illfl it,
Sheet. No.-.
PO.1
OF
2
JOB # 201426
SEAL LICEN
697
'0
�0
�
'// ;DIVA L EN x-\ �
W
Sheet. No.-.
PO.1
OF
2
JOB # 201426