14-998-012CONSTRUCTION WORK ZONE VENTILATION NOTES CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE PHASING PLAN. ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF THE OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA COMMITTEE OFFICER. ALL ICRA EQUIPMENT BY CONTRACTOR UNLESS OTHERWISE STATED IN BID DOCUMENTS. ALL HEPA SCRUBBERS, NEGATIVE AIR FILTER SYSTEMS SHALL BE A MINIMUM OF MERV 17 AFTER THE FAN OR DISCHARGE OF FILTER SYSTEM. ALL FILTER PROVIDE TESTING CERTIFICATION ON FILTRATION SYSTEM. CONSTRUCTION ZONE VENTILATION PROVIDE A MINIMUM ICRA AC PER HOUR WITHIN THE CONSTRUCTION SITE. HEPA NEGATIVE AIR MACHINE AND /OR HEPA SCRUBBER AIR CHANGES PER OWNER'S ICRA REQUIREMENTS = 10 ACHNEGATIVE AIR MACHINES SHALL PROVIDE A MIN. OF 0.02" WG OR MAX. 0.04" WG WITH ADJACENT AREAS. PROVIDE NEGATIVE AIR MACHINES (AS REQUIRED) TO PROVIDE THE OWNER ICRA OF 0.02" WG AND SCRUBBERS NEGATIVE AIR MACHINES (AS REQUIRED) TO PROVIDE THE OWNER ICRA OF 0.02" WG AND SCRUBBERS TO COMPLETE THE REQUIRED AC RATE PER HOUR. PLAN SHOWS ONE NEGATIVE AIR MACHINE AND ONE SCRUBBER, PROVIDE ADDITIONAL SCRUBBERS FOR A COMPLETE AIR CHANGE RATE PER OWNERS ICRA. CONSTRUCTION ALARM LOCATIONS PROVIDE A PRESSURE MONITOR AT EACH ENTERANCE OF THE CONSTRUCTION ZONE, THIS SHALL BE CONNECTED TO THE BMS SYSTEM OR MONTIORED BY HOSPITAL STANDARD AND RECORDED PER ICRA STANDARDS AND /OR HOSPITAL STANDARDS. NEGATIVE AIR PRESSURE FILTER ASSEMBLY DETAIL G.C. TO BLOCK ALL OF THE SUPPLY, RETURN AND EXHAUST GRILLS WITH PLASTIC DURING CONSTRUCTION AND REMOVE IT AFTER COMPLETION OF PROJECT. ILING :E PARTIAL MECHANICAL PLAN - ICRA SCALE: 1/4" = 1' -0" INTERIOR MODIFICATIONS ONLY (ANY EX'fERI MAY REQUIRE BOARD APPEARANCE) MIAMI -DADE COUNTY L FIRE DEPARTMENT i I PROJECT SITE L IF I I I I I I 1 1777 !1 1 1 KEY PLAN FIRST FLOOR VIETB. NGUYEN, P.E. MECHANICAL ENGINEER P.E.# 69753 MJM Job # 2014027 MJM ENGINEERING INC. MECHANICAL, ELECTRICAL & FIRE PROTECTION MTM ENGINEERING CONSULTING SERVICES mJ 12717 WSUNRISE BLVD Suite 215 SUNRISE, FL 33323 CA No: 30046 Tel:(954) -536 -8426 Injmontero a, comcastmet mjmCromcast.net Revisions: 0 0 0 0 JAw z 11 OJ9, oCL Q. o �p.. w= :D ,• Z � , W �0 W c? z Q Z a H P.4 Ul O- O v C-51 .ell V a�� O v Q U_ Z U Q L> J ry � U Q Z Q Q J n— n PERMIT SET J 06/01/14 DRAWN: JM CHECKED: 'BN DATE: 07 -29 -14 SCALE: AS SHOWN I SF LICENS�• 0, 690e lF r � Sheet No. M1.1 = OF 3 JOB # •201426 4