13-185-047ELECTRICAL SPECIFICATIONS 16010 - BA4' -C. ELECTRICAL REQUIREMENTS A. ,,THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPUSH ,HE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, . STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT - LIMITED TO: 1. STATE OF FLORIDA 2. CITY OF MIAMI 3. LIFE SAFETY CODE - NFPA 101 (2006) 4. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) 5. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 7. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 9. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 10. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 11. NATIONAL ELECTRICAL SAFETY CODE (NBS Handbook 81) 12 REQUIREMENTS OF LOCAL UTILITY COMPANY 13. FLORIDA ADMINISTRATIVE CODE 59A -3, (March 2003) .14. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2005) 15. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005) 16. THE STATE FIRE PREVENTION CODE, 4A60 (2001) 17. BUILDING CODE: FLORIDA BUILDING CODE (2007) WITH 2008 AND 2009 REVISIONS 18. AIA GUIDELINES (2006) 19. NFPA 110 (2005) 20. FIRE MARSHALL'S RULE 4A3.012 F.A.C. adopted January 1, 2001 B. CODES AND STANDARDS REFERRED TO ARE MINIMUM. WHERE THE REQUIREMENTS OF THE DRAWINGS OR SPECIFICATIONS EXCEED THOSE OF THE CODES AND REGULATIONS, THE DRAWINGS AND SPECIFICATIONS GOVERN. C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS, PLAN CHECKS, INSPECTIONS, AND APPROVALS APPLICABLE TO THE WORK AS REQUIRED BY THE REGULATORY AUTHORITIES. FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS SHALL BE ASSUMED AND PAID BY THE CONTRACTOR. THE PRO -RATA COSTS, IF ANY, FOR UTILITIES SERVING THIS PROPERTY WILL BE PAID FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF THIS CONTRACT. D. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE. E ALL EXISTING SYSTEMS, EQUIPMENT OR MATERIAL CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS SUBMISSION OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. F. EQUIPMENT SHALL BE NEW AND SHALL BEAR THE U.L LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE. ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND ACCEPTANCE BY THE OWNER. G. CONTRACTOR SHALL INSTALL ELECTRICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS IN CASE OF DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF SUCH DIFFERENCE. SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE /SHE SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, UTILITY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. SHOULD THE CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. I. WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR 'OR EQUAL" ACCEPTANCE BY THE ENGINEER. SUBSTITUTION REQUESTS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL WHERE MORE THAN ONE MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS, ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR ACCEPTANCE SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE MATERIAL PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT SPECIFIED AT NO COST TO THE OWNER. J. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND EXISTING EQUIPMENT REQUIRING OPERATION AND /OR MAINTENANCE. RELOCATE EXISTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT OPERA11ON OR MAINTENANCE IS NOT RESTRICTED. K. INSTALL EQUIPMENT WITH WORKING CLEARANCES COMPLYING WITH NEC 110 -26 AND 110 -34. L SHOP DRAWING SUBMITTALS 1. CONTRACTOR SHALL PREPARE AND SUBMIT SEVEN COPIES OF ALL SUBMITTALS FOR ALL PERTINENT ELECTRICAL EQUIPMENT AND DEVICES INDICATED IN THE SCOPE OF WORK. 2. COMPLETE UST OF MATERIALS TO BE FURNISHED UNDER EACH SPECIFIC SECTION. 3. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED TO ASSURE SPECIFICATION COMPLIANCE. 4. CATALOG SHEETS, CLEARLY MARKED FOR IDENTIFICATION OF ITEMS TO BE PROVIDED, INCLUDING DISCONNECT SWITCHES, BREAKERS, FUSES, STARTERS, LIGHTING FIXTURES, TRANSFORMERS, OR OTHER MATERIAL NOT REQUIRING SPECIALLY PREPARED SHOP DRAWINGS 5. ALL SHOP DRAWING CUT SHEETS SHALL CLEARLY IDENTIFY THE SPECIFIC PRODUCT TO BE REVIEWED AND APPROVED, INCLUDING MANUFACTURER. GENERIC CUT SHEETS, INCOMPLETE CUT SHEETS AND CUT SHEETS SUBMITTED WITHOUT IDENTIFYING THE SPECIFIC PRODUCT PROVIDED, WILL BE AUTOMATICALLY REJECTED. 6. AS PART OF EQUIPMENT SHOP DRAWINGS, PROVIDE DETAILED DIMENSIONED LAYOUT DRAWINGS FOR ALL LARGE ELECTRICAL EQUIPMENT AND ELECTRICAL ROOMS WHERE NEW EQUIPMENT IS BEING INSTALLED. M. CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED FOR ALL FLOOR MOUNTED EQUIPMENT, UNLESS NOTED OR REQUIRED OTHERWISE ALL PADS SHALL BE NOT LESS THAN 3-1/2" HIGH AND EXTEND A MAXIMUM 3" BEYOND THE ACTUAL EQUIPMENT SIZE COORDINATE THE PROPER SIZE OF THE PAD WITH HE EQUIPMENT FURNISHED. PADS SHALL BE POURED IN FORMS BUILT OF NEW DRESSED LUMBER WITH CORNERS CHAMFERED USING SHEET METAL OR TRIANGULAR WOOD STRIPS NAILED TO THE FORM. USE 6X6 No. 3 MESH FOR REINFORCING. INSTALL HEAVY DUTY ADJUSTABLE ANCHOR BOLTS, SET IN THE FORM AND POSITIONED USING TEMPLATES, PRIOR TO POURING CONCRETE AFTER THE EQUIPMENT IS SET ON THE PAD, THE EQUIPMENT SHALL BE ALIGNED, LEVELED AND FULLY GROUTED TO THE PAD AND ALL VOID SPACES SHALL BE FILLED WITH A NON - SHRINKING GROUT. PERFORM ALL CONCRETE WORK SPECIFIED TO BE PROVIDED UNDER THIS DIVISION IN STRICT ACCORDANCE WITH THE APPLICABLE PROVISIONS OF DIVISION 3, CONCRETE N. EACH CONDUIT, REGARDLESS OF MATERIAL, WHICH PASSES THROUGH A CONCRETE SLAB, MASONRY WAD., OR ROOF OR PORTION OF THE BUILDING STRUCTURE SHALL BE FREE FROM THE STRUCTURE AND SHALL PASS THROUGH A SLEEVE ALL SLEEVES SHALL BE CONSTRUCTED FROM ELECTRIC-METALLIC TUBING OR EQUIVALENT WEIGHT GALVANIZED STEEL TUBING AND SHALL BE FLUSH ON BOTH SIDES OF THE SURFACE PENETRATED, U.N.O. ALL SLEEVES PENETRATING THE ROOF AREAS SHALL EXTEND A MINIMUM 10 INCHES ABOVE THE ROOF WITH APPROVED WEATHERPROOF COUNTERFLASHING ATTACHED TO THE CONDUIT ABOVE THE ROOF. ALL SLEEVES PENETRATING FLOORS SHALL EXTEND A MINIMUM OF 6 INCHES A.F.F. THE SLEEVES SHALL BE SIZED TO ALLOW FREE PASSAGE OF THE CONDUIT TO BE INSERTED. SLEEVES PASSING THROUGH WALLS OR FLOORS ON OR BELOW GRADE OR IN MOIST AREAS SHALL BE CONSTRUCTED OF GALVANIZED RIGID STEEL AND SHALL BE DESIGNED WITH A SUITABLE FLANGE INT HE CENTER TO FORM A WATERPROOF PASSAGE AFTER THE CONDUIT HAS BEEN INSTALLED IN SLEEVES, THE VOID SPACE AROUND THE CONDUIT SHALL BE CAULKED AND FILLED WITH AN ASPHALT -BASE COMPOUND TO INSURE A WATERPROOF PENETRATION. JUTE TWINE CAULKING SHALL NOT BE USED. 0. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS AT THE SITE, NOTING DAILY ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL NEW AND UNCOVERED EXISTING UTILITIES TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING "AS INSTALLED" WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH SHEET AND LABEL "AS- GUILTS" IN THE REVISION BLOCK ON THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF "AS- BUILT' BLUELINE PRINTS. P. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE, PREPARED IN A NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER. 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE. 2 APPROVED FIXTURE BROCHURES, WIRING DIAGRAMS AND CONTROL DIAGRAMS (ORIGINAL DATA, NO COPIES). 3. COPIES OF APPROVED SHOP DRAWINGS. 4. OPERATING INSTRUCTIONS FOR ALL ELECTRICAL SYSTEM EQUIPMENT. OPERATING INSTRUCTIONS SHALL ALSO INCLUDE RECOMMENDED MAINTENANCE PROCEDURES. 5. TEST REPORTS REQUIRED BY THESE SPECIFICATIONS 6. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED DURING CONSTRUCTION. 7. REPAIR PARTS LISTS OF ALL MAJOR ITEMS OF EQUIPMENT INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL SUPPLIER OR AGENT. Q. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS REVIEW AT SUCH TiME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS BEFORE FINAL INSPECTION. 16020 - ELECTRICAL WORK IN EXISTING FACILITIES A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMA71ON RELATED TO EXISTING FACILITIES FROM EXISTING DOCUMENTS, MEASUREMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS, AND OTHER OBSERVATIONS AT THE SITE. B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE CONSTRUCTION PERIOD, CARRY OUT THE WORK UNDER THIS DIVISION IN SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS. C. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING ADJACENT SURFACED UPON COMPLE11ON OF THE WORK. D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK. E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. F. WORKING JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT BEFORE COMMENCING WITH WORK. G. DEMOUTION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR. SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED OTHERWISE. H. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADD11IONAL COST TO THE OWNER. REPAIR AND RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLY OPERATIONS NEW MATERIALS AND ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SHOP DRAWINGS, PRODUCT DATA AND SAMPLES REMOVE CAREFULLY, IN REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE TO BE RELOCATED. PROTECT ITEMS UNTiL RELOCATION IS COMPLETE. CLEAN AND REPAIR ITEMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, . FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE WITH APPLICABLE PORTIONS OF THESE SPECIFICATIONS, UTILIZING SKILLED WORKERS 1. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS, WIRE, CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN EXISTING- TO-BE- REMOVED CONSTRUCTION. 16084 THROUGH PENETRATION FlRESTOPPING FOR ELECTRICAL SYSTEMS A. ONLY TESTED FIRESTOP SYSTEMS SHALL BE USED IN SPECIFIC LOCATIONS AS FOLLOWS. 1. PENETRATIONS FOR THE PASSAGE OF CONDUIT AND OTHER ELECTRICAL EQUIPMENT THROUGH FIRE -RATED VERTICAL BARRIERS (WADS AND PARTITIONS), HORIZONTAL BARRIERS (FLOOR /CEILING ASSEMBLIES), AND VERTICAL SERVICE SHAFT WALLS AND PARTITIONS 2. COMPLETION OF FIRESTOP INSTALLATIONS TO MAINTAIN THE RATING INTEGRITY OF THE BARRIER PENETRATED. B. INSTALLER SHALL CONSULT THE STRUCTURAL ENGINEER PRIOR TO PENETRATING ANY LOAD BEARING ASSEMBLY. C. ACCEPTABLE MANUFACTURERS: HILTi INC., TREMCO SEALANTS do COATINGS, 3M FIRE PROTECTION PRODUCT'S, JOHN- MANVILLE FIRETEMP, OR OTHER MANUFACTURERS LISTED IN THE U.L FIRE RESISTANCE DIRECTORY - VOLUME 2 D. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIRESTOPPING BARRIER AT ALL ELECTRICAL BOXES (EXISTING AND NEW) AND PENETRATIONS FOR ANY EXISTING FIRE WADS IN THE SCOPE OF WORK AREA AND /OR FOR ANY NEW FIRE WALLS. FOR NEW FIRE WALLS IN WHICH ONE SIDE OF THE WALL 1 FALLS OUTSIDE OF THE SCOPE OF WORK AREA AND OTHER DOES NOT, CONTRACTOR SHALL PROVIDE FIRSTOPPING BARRIER FOR ALL PENETRATIONS AND ELECTRICAL BOXES ON THE WALL SIDE NOT IN THE SCOPE OF WORK AREA. 16110 - SYSTEMS OF RACEWAYS A. CONDUIT 1. RIGID STEEL CONDUIT (GRC - GALVANIZED RIGID CONDUIT): CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, CONFORMING WITH FED. SPEC. WW- C -581E, ANSI C80.1 AND UL 6. 2 INTERMEDIATE METAL CONDUIT (IMC): CONSTRUCTED OF ZINC COATED STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. WW-C-5811-E, UL -1242 AND MEETING THE REQUIREMENTS OF THE NEC. 3. ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE STEEL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM WELDING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO FED. SPEC. WW-C- 563 -A, ANSI C80-3, AND UL 797. 4. LIQUIDTiGHT FLEXIBLE CONDUIT: FLEXIBLE METAL CONDUIT AS SPECIFIED HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY -APPLIED NEOPRENE JACKET. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE UL LISTED, EQUIVALENT TO ANACONDA "SFALTiTE", TYPE UA. 5. CONTRACTOR SHALL SUPPLY TRENCH DUCT AS REQUIRED IN RADIOLOGY ROOMS IN ACCORDANCE WITH THE RADIOLOGY VENDOR'S DRAWINGS DUCT SHALL BE AS REQUIRED BY VENDOR WITH A MINIMUM 1/4" THICK REMOVABLE COVER PLATES DUCT SHALL HAVE A SINGLE REVERSIBLE ALUMINUM TRIM WITH A SURFACE EXPOSURE THROUGH THE FLOOR TO RECEIVE FLOOR COVERING. TRENCH DUCT SHALL BE MANUFACTURED BY SQUARE D, WALKER, OR GENERAL ELECTRIC. 6. INSTALLATION OF BUILDING CONDUIT a. ALL INTERIOR RACEWAYS SHALL BE EMT. RACEWAYS IN DAMP OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE GRC OR IMC. b. CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY OR EXCESSIVE STRAIN, SHALL BE SECURED AT CABINETS AND BOXES WITH GALVANIZED LOCKNUTS, BOTH INSIDE AND OUTSIDE, AND SHALL HAVE APPROPRIATE BUSHINGS INSIDE. BUSHINGS SHALL BE INSULATING TYPE WITH BOND GROUND CLAMPS c. USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE 1 FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LIQUID TIGHT FLEXIBLE METAL CONDUIT, WITH APPROPRIATE CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS, AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS. d. GROUND METALLIC CONDUITS AS REQUIRED BY NEC. e. INSTALL RACEWAYS CONTINUOUS FROM OUTLET TO OUTLET BOX, OR CABINET, WITH A MAXIMUM OF 150 FEET BETWEEN PULLS. IN AREAS WHERE THERE ARE NO SUSPENDED CEILINGS, RUN ALL CONDUITS PARALLEL/PERPENDICULAR TO BUILDING SURFACE f. IN SYSTEMS OPERATING AT MORE THAN 300 VOLTS BETWEEN PHASE CONDUCTORS, AND WHERE DIFFERENT PHASE CONDUCTORS ARE TO BE RUN TO A COMMON GANG WALL SWITCH BOX, PROVIDE SUBSTANTIAL BARRIERS BETWEEN ADJACENT SWITCHES IN THE BOX SO THAT TWO DIFFERENT PHASE WIRES WILL NOT BE IN THE SAME COMPARTMENT. g. WHEREVER RACEWAYS PASS THROUGH FLOORS, WALLS, PENETRATIONS, OR OTHER PARTITIONS, CAREFULLY FILL ANY SPACE BETWEEN THE OUTSIDE OF THE RACEWAY AND THE BUILDING MATERIAL TO PREVENT PASSAGE OF AIR, WATER, SMOKE, AND FUMES. FILLING MATERIAL SHALL BE A UL LISTED, INTUMESCENT SEALING HAVING FIRE/SMOKE RESISTIVE RATING EQUAL TO THE BUILDING MATERIAL PENETRATED. h. CONDUITS UTILIZED THROUGHOUT THE PROJECT SHALL NOT BE SMALLER THAN 3/4 INCH FOR FEEDERS, MULTIPLE BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF CONDUCTORS LARGER THAN NO. 12 INDIVIDUAL BRANCH CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE ACCEPTABLE IN 3/4" CONDUIT, I.E. 2#12, 1/12G, 3/4 "C. 7. INSTALLATION OF UNDERGROUND CONDUIT a. INSTALL UNDERGROUND FEEDER CONDUCTORS IN RIGID NONMETALLIC CONDUIT (PVC), U.N.O. INSTALL AT LEAST 30 INCHES BELOW FINISHED GRADE U.N.O. ON A BED OF SAND BEFORE CONTINUING BACKFILL b. WHERE CONDUIT ENTERS INTO PULL OR JUNCTION BOXES AND AT ALL BENDS, CHANGE FROM PVC TO RIGID GALVANIZED STEEL CONDUIT BELOW GRADE. c. PROVIDE A PULL BOX OF APPROPRIATE SIZE EVERY 500 FEET OF STRAIGHT RUN AND AT EVERY 90 DEGREE BEND. B. COUPLINGS AND TERMINATORS 1. FOR RIGID STEEL OR INTERMEDIATE METAL CONDUIT. FACTORY -MADE THREADED COUPLINGS OF SAME MATERIAL AS THE CONDUIT. 2 FOR ELECTRICAL METALLIC TUBING, USE STEEL COMPRESSION COUPLINGS AND NYLON INSULATED GROUNDING BUSHINGS. 3. FOR FLEXIBLE METAL CONDUIT: COUPLINGS AT CONNECTIONS BETWEEN FLEXIBLE CONDUIT AND EMT, AND NYLON INSULATED THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS. 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS WITH NYLON INSULATED THROAT AND LOCKNUTS AT ALL BOXES AND CABINET TERMINATIONS OR NON - INSULATED BOX CONNECTOR, LOCKNUT AND NYLON - INSULATED GROUNDING BUSHING ON ALL TUBING WHERE GROUNDING BUSHINGS ARE REQUIRED. C. JUNCTION AND PULL BOXES 1. SIZE BOXES IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC. BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES SQUARE BY 1 -1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL TiMES. SET BOXES ON CONCEALED CONDUITS WITH COVERS FLUSH WITH THE FINISHED WALL OR CEILING LINE. PROVIDE JUNCTION AND PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND CONDUCTORS NOTED, WHERE SHOWN AND WHERE NECESSARY FOR THE INSTALLATION AND PULLING OF CABLES AND WARES. INSTALL COVERS ON JUNCTION BOXES AND CONDULETS AFTER WIRING AND CONNECTIONS ARE COMPLETED. 2 ALL JUNCTION AND PULL BOXES FOR EMERGENCY SYSTEMS AND LOW VOLTAGE SYSTEMS SHALL HAVE COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE YELLOW (LIFE SAFETY BRANCH), ORANGE (CRITICAL BRAMCH), GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM), AND BROWN (DATA/TELEPHONE). 3. INSTALLATION OF PULL AND JUNCTION BOXES a. FASTEN ALL BOXES SECURELY TO THE BUILDING CONSTRUCTION, INDEPENDENT OF CONDUIT SYSTEMS. b. ON CONCEALED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHERWISE ACCESSIBLE, SET BOXES FLUSH WITH FINISHED SURFACES FOR ACCESS, AND PROVIDE OVERLAPPING COVERS. C. ALL WIRING DEVICES FACEPLATES SHALL BE ENGRAVED WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER SERVING THE OUTLET. LABEL TAPE WALL NOT BE ACCEPTABLE. D. OUTLET BOXES 1. OUTLET BOXES SHALL BE UL LISTED, AND OF SIZES AND TYPES REQUIRED FOR THE APPLICATION. OUTLET BOXES SHALL BE SHEET STEEL, NO LIGHTER THAN 14 GAUGE, GALVANIZED AFTER FABRICATION. SET BOX SO FACE OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE a. FOR LIGHTING FIXTURE OUTLETS: 4 INCH SQUARE BY 1- 1/2 INCHES DEEP WITH RAISED FIXTURE RING. b. FOR WALL SWITCHES, RECEPTACLES, AND COMMUNICATION USE: 4 INCH AR BY 1 -1 SQUARE, 2 INCHES DEEP. USE BOXES XES / WITH PLASTER RINGS IN ALL PLASTERED WALLS WHERE WALL THICKNESS PERMITS USE BOXES LESS THAN 1 -1/2 INCH DEEP ONLY IN LOCA11ONS WHERE DEEP BOXES CANNOT BE ACCOMMODATED BY CONSTRUCTION. E. PULL CORDS 1. PROVIDE A NYLON POLYETHYLENE CORD, WITH A TENSILE STRENGTH OF NOT LESS THAN 200 POUNDS, IN EACH EMPTY CONDUIT TO FACILITATE THE FUTURE INSTALLATION OF CONDUCTORS INCORPORATE PLASTIC TAGS FOR IDENTIFICATION. F. SEGREGATION OF WIRING SYSTEMS 1. SEGREGATION OF WIRING SYSTEMS SHALL NOT BE COMPROMISED BY THE USE OF COMMON PULLBOXES, WIREWAYS, CABINETS OR ANY OTHER TYPE OF ENCLOSURE. 2 THE RACEWAY SYSTEM FOR EACH FEEDER SHALL BE A SEPARATE SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS. 3. THE RACEWAY SYSTEM FOR THE BRANCH CIRCUITS OF EACH PANELBOARD SHALL BE A SEPARATE SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS 6120 - SYSTEM OF CONDUCTORS A CONDUCTORS SHALL BE 98% CONDUCTIVITY SOFT DRAWN ANNEALED COPPER, 600 VOLT, THHN/THWN INSULATION, #10 AND SMALLER - SOLID, JB AND LARGER - STRANDED. B. NO CONDUCTORS SHALL BE SMALLER THAN NO. 12, EXCEPT FOR SIGNAL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS PERMITTED BY NEC. C. FOR HOME RUNS ON 120 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 LINEAR FEET, USE NO. 10 CONDUCTORS. WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS D. FOR HOME RUNS ON 277 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 LINEAR FEET, USE NO. 10 CONDUCTORS WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS E. NO MORE THAN FIVE CONDUCTORS (3 PHASE, 1 NEUTRAL, AND 1 GROUND) SHALL BE INSTALLED IN A COMMON BRANCH CIRCUIT CONDUIT. F. PROVIDE COLOR CODED CABLE SYSTEM APPROVED BY OWNER. IF NONE IS REQUIRED BY OWNER, PROVIDE THE FOLLOWING COLOR CODING: a. 48OV/277 b. 208V/120 A PHASE - BROWN A PHASE - BLACK B PHASE - ORANGE B PHASE - RED C PHASE - YELLOW C PHASE -BLUE NEUTRAL - GREY NEUTRAL - WHITE GROUND - GREEN GROUND - GREEN COLOR CODING SHALL BE CONTINUOUS ON INSULATION FOR #6 AWG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS FOR CONDUCTORS LARGER THAN 06 AWG. G. INSTALLA1ION OF CONDUCTORS 1. PULL NO CONDUCTORS INTO CONDUITS UNTiL ALL WORK OF A NATURE WHICH MAY CAUSE INJURY TO CONDUCTORS IS COMPLETED. 2 RUN FEEDERS IN CONTINUOUS LENGTHS, WITHOUT JOINTS OR SPLICES, INSOFAR AS PRACTICABLE. 3. RUN CONDUITS FOR EMERGENCY POWER CONDUCTORS SEPARATE FROM ALL OTHER WIRING. 4. CABLE TYPE AC OR MC IS NOT ALLOWED FOR HOMERUN AND FEEDER INSTALLATIONS 6140 - WIRING DEVICES A. ALL WIRING DEVICES SHALL BE UL LISTED. B. ACCEPTABLE MANUFACTURERS: PASS dt SEYMOUR, HUBBEL, LEVITON, AND COOPER. C. RECEPTACLES 1. RECEPTACLES SHALL BE HOSPITAL GRADE STANDARD STYLE THEY SHALL BE 20A, 125V. 2- POLE, 3-W i& N OMA 5-208 CONFKURATION. BACK AND SiDE WIRED WITH A GREEN EQUIPMENT GROUND SCREW OR AN AUTOMATIC MUM SYS181 ATTACHED 70 THE STRAP U.N.O. 2. GFCI RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES DOWNSTREAM ON THE SAME CIRCUIT THEY SHALL BE UL RATED CLASS 1 WITH 5MA GROUND FAULT TRIP LEVEL AND A 20A FEED- THROUGH RATING AND HAVE A NEMA 5-208 CONFIGURATION. 3. RECEPTACLE COLOR SHALL BE IVORY. THEY SHALL BE RED WHEN CONNECTED TO AN EMERGENCY CIRCUIT. 4. PEDIATRIC LOCATIONS ALL RECEPTACLES LOCATED IN PATIENT CARE AREAS SHALL BE LISTED TAMPER RESISITANT D. SWITCHES 1. SWITCHES SHALL BE SPECIFICATION GRADE, 20A, 120/277V, HORSEPOWER RATED, BACK AND SIDE WIRED. SWITCHES SHALL INCLUDE A GREEN GROUND SCREW ATTACHED TO THE MOUNTING STRAP. 2 WHERE LIGHTING CIRCUITS ARE SHOWN TO BE LINE VOLTAGE SWITCHED, PROVIDE WITH SPECIFICATION GRADE, HORSEPOWER RATED, UL LISTED, BACK - AND SIDE- WIRED, TOGGLE SWITCHES RATED 20A, 120V OR 277 VOLTS. SWITCHES SHALL BE SPST, DPST, 3 -WAY OR 4-WAY, WITH OR WITHOUT PILOT LIGHT AS INDICATED ON THE DRAWINGS. 3. SWITCH COLOR SHALL BE IVORY OR RED WHEN CONNECTED TO AN EMERGENCY CIRCUIT. E DIMMER SWATCHES 1. DIMMER SWITCHES SHALL BE MANUFACTURED BY LUTRON. 2 ALL DEVICES SHALL BE CAPABLE OF OPERATING AT RATED CAPACITY WITHOUT ADVERSELY AFFECTING DESIGN LIFETIME. 3. DIMMER CONTROL OF LIGHT INTENSITY SHALL BE VIA LINEAR SLIDE. 4. LINEAR SLIDE DIMMER SHALL PROVIDE INTENSITY AND ON /OFF CONTROL WITH MOVEMENT OF SLIDER. THIS SHALL APPLY TO SINGLE POLE AND 2- LOCATION DIMMERS. 5. ALL DIMMERS SHALL MEET UL20 AND BE APPROPRIATELY MARKED. 6. SWITCH RATING SHALL BE 20A, 12OVAC, FOR TUNGSTEN OR INDUCTIVE LOADS. 7. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A DIMMER SWITCH pA�N�D�W� WRING COMPATIBLE WITH LIGHT FIXTURE SPECIFICED IN ORDER TO F. WALL PLATESA COMPLETE AND FUNCTIONAL SYSTEM. 1. WALL PLATES SHALL BE PROVIDED FOR ALL SWITCHES, RECEPTACLES, BLANKS, TELEPHONE/1DATA, AND SPECIAL PURPOSE OUTLETS. THE WALL PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR WHICH IT IS TO COVER WITH COLOR MATCHING MOUNTING SCREWS. COLOR OF THE WALL PLATES SHALL MATCH THE DEVICE, U.N.O. 2 WALL PLATES SHALL BE THERMOPLASTIC, NON - COMBUSTIBLE, AND HIGH- IMPACT RESISTANT. THEY SHALL BE P -UNE SMOOTH PLATES. THEY SHALL BE OF THE SAME MANUFACTURER AS THE WIRING DEVICE IT IS TO COVER. 3. WEATHERPROOF: WIRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED WITH A HINGED OUTLET COVER/ENCLOSURE CLEARLY MARKED "SUITABLE FOR WET LOCATIONS WHILE IN USE" AND "UL LISTED ". THERE SHALL BE A GASKET BETWEEN THE COVER/ENCLOSURE AND THE MOUNTING SURFACE, AND BETWEEN THE HINGED COVER AND MOUNTING PLATE/BASE TO ASSURE PROPER SEAL THE COVER/ENCLOSURE SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY TAYMAC CORPORATION OR EQUAL G. INSTALLATION OF WIRING DEVICES 1. EACH WIRING DEVICE SHALL BE MOUNTED IN A METALLIC OUTLET BOX. IN GENERAL, DEVICES IN FINISHED SPACES SHALL BE FLUSH MOUNTED DEVICES AND DEVICES IN UNFINISHED SPACES SUCH AS ELECTRICAL AND MECHANICAL ROOMS SHALL BE SURFACE MOUNTED. VERIFY THE REQUIREMENTS OF ALL SPACES WITH ARCHITECT. 2 MOUNT RECEPTACLES A.F.F. TO THE DEVICE CENTERLINE, U.N.O. MOUNT SWATCHES A.F.F. TO THE DEVICE CENTERLINE AND 6" FROM A DOOR STRIKE, U.N.O. 3. MAINTAIN GROUNDING CONTINUITY BETWEEN DEVICES AND METALLIC RACEWAY SYSTEM IN ADDITION TO PROVIDING A GREEN EQUIPMENT GROUNDING CONDUCTOR RUN WITH ALL CIRCUIT CONDUCTORS AS INDICATED ON THE DRAWINGS. 4. MOUNT RECEPTACLES THROUGHOUT THE PROJECT WITH GROUND POLE AT THE TOP OF THE CONFIGURATION WHEN MOUNTED VERTICALLY AND ON THE RIGHT WHEN MOUNTED HORIZONTALLY. 5. ALL EXTERIOR RECEPTACLES SHALL BE GFCI WITH A WEATHERPROOF COVER/ENCLOSURE. 16160 - CABINET'S AND ENCLOSURES A. CABINETS SHALL BE GALVANIZED STEEL WITH GRAY BAKED ENAMEL FINISH AND SHALL BE SIZED AS REQUIRED OR INDICATED. FRONTS SHALL BE STEEL, FLUSH OR SURFACE TYPE INDICATED WITH CONCEALED HINGE, AND FLUSH LOCK KEYED TO MATCH BRANCH CIRCUIT PANEL.BOARD, FINISH WITH GRAY BAKED ENAMEL B. ENCLOSURES SHALL BE NEMA 250, TYPE 1 OR 3R, AS INDICATED ON DRAWINGS THEY SHALL HAVE CONTINUOS HINGED COVERS. PROVIDE INTERIOR METAL PANEL FOR MOUNTING TERMINAL BLOCKS AND ELECTRICAL COMPONENTS; FINISH WITH WHITE ENAMEL ENCLOSURE FINISH SHALL BE MANUFACTURER'S STANDARD ENAMEL 16190 - SUPPORTING DEVICES A. ACCEPTABLE MANUFACTURERS UNISTRUT CORP., B -LINE SYSTEMS, INC., AND MIDLAND ROSS- KINDORF. B. FURNISH AND INSTALL ALL HANGERS AND SUPPORTS REQUIRED BY RACEWAY SYSTEMS C. HANGERS SHALL BE SUPPORTED BY MEANS OF UNCOATED SOLID STEEL RODS WHICH ARE THREADED TO ALLOW VERTICAL ADJUSTMENTS. LOCK NUTS SHALL BE PROVIDED IN SUFFICIENT NUMBER AND LOCATION TO LOCK ALL ROD ADJUSTMENTS PERMANENTLY AT THE ADJUSTED HEIGHT. TWO LOCK NUTS SHALL BE USED UNLESS THE NUT TIGHTENS AGAINST A THREADED SOCKET. MINIMUM ROD DIAMETERS SHALL BE AS FOLLOWS: NOMINAL CONDUIT SIZE ROD DIAMETER 1/2" THROUGH 2" 1/4" 2 -1/2" THROUGH 3" 3/8" 4" AND 5" 1/2" D. HANGER SPACING SHALL BE AS REQUIRED FOR PROPER SUPPORT OF RACEWAY, BUT IN NO CASE SHALL BE LESS THAN ONE HANGER PER 8' -0" OF RACEWAY LENGTH EXCEPT THAT CONDUIT LESS THAN 1" DIAMETER SHALL BE SUPPORTED AT LEAST EVERY 6' -0". E WHERE NUMEROUS CONDUITS ARE RUN PARALLEL TO ONE ANOTHER, THEY MAY BE SUPPORTED FROM A TRAPEZE TYPE HANGER ARRANGEMENT WITH STRUT BOTTOM. F. SUPPORT OF HANGERS SHALL BE BY MEANS OF SUFFICIENT QUANTITIES OF INDIVIDUAL AFTER SET STEEL EXPANSION SHIELDS, OR BEAM CLAMPS ATTACHED TO STRUCTURAL STEEL G. STIFF -LEGS SHALL BE FURNISHED AND INSTALLED IN CASES WHERE SUPPORT FROM OVERHEAD STRUCTURE IS NOT POSSIBLE H. CEILING MOUNTED LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AT TWO OPPOSITE CORNERS. THE CONTRACTOR SHALL PROVIDE FIXTURE HANGERS TO PROPERLY INTERFACE WITH THE CEILING SYSTEM. L FURNISH AND INSTALL COMPLETE ANY ADDITIONAL STRUCTURAL SUPPORT STEEL, BRACKETS, FASTENERS, ETC. AS REQUIRED TO ADEQUATELY SUPPORT ALL RACEWAY AND EQUIPMENT. J. SUPPORT OF HANGERS FROM CONCRETE SLABS SHALL BE BY MEANS OF SUFFICIENT QUANTITY OF "U" BRACKETS ATTACHED WITH AFTER SET EXPANSION SHIELDS AND BOLTS. 16195 - ELECTRICAL IDENTIFICATION A. PROVIDE ELECTRICAL IDENTIFICATION FOR THE FOLLOWING: 1. SWITCHGEARS, SWITCHBOARDS, MOTOR CONTROL CENTERS, PANELBOARDS, MOTOR STARTERS, CONTACTORS, DISCONNECT SWITCHES, CIRCUIT BREAKERS, AND OTHER ELECTRICAL EQUIPMENT WITH NAMEPLATE IDENTIFYING THE ITEM OF EQUIPMENT SERVING THE SAME 2 RACEWAYS, JUNCTION BOXES, AND PULL BOXES 3. WIRING DEVICES, WIRING, AND THREE PHASE MOTOR ROTATION. B. PROVIDE THE FOLLOWING COLOR CODING FOR ALL EQUIPMENT NAMEPLATES: NORMAL SYSTEM - BLACK W/ WHITE LETTERS CRITICAL BRANCH - RED W/ WHITE LETTERS LIFE SAFETY BRANCH - YELLOW W/ WHITE LETTERS EQUIPMENT SYSTEM - GREEN W/ WHITE LETTERS C. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE, WIRE, BRANCH OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH BEVELED EDGES, MINIMUM 1/16" THICK. LETTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 1/4" HIGH, CUT THROUGH THE SURFACE TO THE WHITE CORE. NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL NOT BE USED. D. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE, WIRE, BRANCH OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH 1 BEVELED EDGES, MINIMUM 1/16" THICK. U=TTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 1/4" HIGH, CUT THROUGH THE SURFACE TO THE WHITE CORE. NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL NOT BE USED. E IDENTIFICATION OF JUNCTION AND PULL BOXES SHALL BE NTH A BLACK PERMANENT MARKING PEN ON THE TOP OF THE 4" X 4" JUNCTION BOX COVER OR ON THE BACK OF THE OUTLET BOX COVER PLATE IDENTIFYING THE BRANCH CIRCUITS AND SYSTEMS WITHIN THE CONDUIT. PULL BOXES SHALL BE PROVIDED WITH A NAMEPLATE STATING VOLTAGE AND SYSTEM SERVED. F. ON THE FACE OF THE WIRING DEVICE WALL PLATE, MACHINE ENGRAVE THERMOPLASTIC PLATES WITH THE PANELBOARD AND BRANCH CIRCUIT NUMBER THE DEVICE IS SERVED FROM. ADHESIVE LABELS ARE NOT ALLOWED. G. RACEWAY IDENTIFICATION SHALL BE PROVIDED AT A MINIMUM OF EVERY 50', AT EACH END IF LESS THAN 50', AND A MINIMUM OF ONCE PER ROOM OR SPACE THROUGH WHICH IT PASSES. H. CONDUIT, RACEWAYS AND BOXES SHALL BE SPOT PAINTED. CONDUIT SHALL BE IDENTIFIED WITHIN 6 INCHES OF THE BOX OR ENCLOSURE. THE ENTIRE BOX AND COVERPLATE SHALL BE PAINTED. USE THE FOLLOWING COLOR CODING SCHEME: - NORMAL SYSTEM WHITE FIRE ALARM - RED CRITICAL BRANCH - BRIGHT ORANGE COMMUNICATIONS - BROWN LIFE SAFETY BRANCH - BRIGHT YELLOW TELEPHONE /COMPUTER - BLACK EQUIPMENT SYSTEM - KELLY GREEN NURSE CALL - ROYAL BLUE TV - LIGHT PINK IN EVENT THAT THERE IS A DISCREPANCY BETWEEN THESE COLORS AND THE FACILITY STANDARD. CONTRACTOR SHALL SUBMIT AN RFI REQUESTING CLARIFICATION. 16440 - DISCONNECT SWITCHES A. ACCEPTABLE MANUFACTURERS: CUTLER HAMMER, GENERAL ELECTRIC, OR SQUARE D. B. SWITCHES SHALL BE HEAVY DUTY TYPE AND UL LISTED.. C. SWITCHES SHALL HAVE SWITCHBLADES WHICH ARE VISIBLE WHEN THE SWITCH IS OFF AND THE COVER IS OPEN. D. LUGS SHALL BE FRONT REMOVABLE AND UL LISTED 60 OR 75 DEGREES C FOR CONDUCTOR 30 -100A, AND 75 DEGREES C CONDUCTORS 200A AND UP, E. SWITCH OPERATING MECHANISM SHALL BE QUICK -BREAK SUCH THAT, DURING NORMAL OPERATION OF THE SWITCH, THE OPERATION OF THE CONTACTS SHALL NOT BE CAPABLE OF BEING RESTRAINED BY THE OPERATING HANDLE AFTER THE CLOSING OR OPENING ACTION OF THE CONTACTS HAS STARTED. F. THE OPERATING HANDLE SHALL BE AN INTEGRAL PART OF THE BOX, NOT THE COVER. G. SWITCHES SHALL HAVE A DUAL COVER INTERLOCK MECHANISM TO PREVENT UNINTENTIONAL OPENING OF THE SWITCH COVER WHEN THE SWITCH IS ON AND PREVENT TURNING THE SWITCH ON WHEN THE COVER IS OPEN. THE COVER INTERLOCK MECHANISM SHALL HAVE AN EXTERNALLY OPERATED OVERRIDE BUT THE OVERRODE SHALL NOT PERMANENTLY DISABLE THE INTERLOCK MECHANISM. THE TOOL USED TO OVERRIDE THE COVER INTERLOCK MECHANISM SHALL NOT BE REQUIRED TO ENTER THE ENCLOSURE IN ORDER TO OVERRIDE THE INTERLOCK. H. SWITCH COVERS SHALL BE ATTACHED WITH WELDED PIN -TYPE HINGES (NEMA TYPE 1) OR TOP HINGED, ATTACHED WITH REMOVABLE SCREWS AND SECURABLE IN THE OPEN POSITION (TYPE 3R). I. THE ENCLOSURE SHALL HAVE ON AND OFF MARKINGS STAMPED TO THE COVER. J. SWITCHES SHALL HAVE PROVISIONS TO ACCEPT UP TO 3/8" HASP PADLOCKS TO LOCK THE HANDLE IN THE OFF POSITION. K. TANGENTIAL KNOCKOUTS SHALL BE PROVIDED TO FACILITATE EASE OF CONDUIT ENTRY (NEMA TYPE 1). TYPE 3R ENCLOSURE SHALL CONTAIN NO KNOCKOUTS. SUPPLY WATERTIGHT HUBS. L SWITCHES SHALL BE HORSEPOWER RATED. M. INSTALL FUSES IN FUSIBLE DISCONNECT SWITCHES AS INDICATED OR AS REQUIRED BY MANUFACTURER OF EQUIPMENT THAT THE SWITCH IS SERVING. N. FUSIBLE SWITCHES: FOR 600 AMPERE AND SMALLER SWITCHES, PROVIDE UL LISTED REJECTION CLIPS TO REJECT ALL FUSES EXCEPT CLASS R; FOR 800 AMPERE AND LARGER SWITCHES, PROVIDE FUSE CUPS FOR CLASS L FUSES. ALL SWITCHES UL LISTED SHORT CIRCUIT RATING OF 200,00 AMPERES RMS SYMMETRICAL O. ENCLOSED CIRCUIT BREAKER ENCLOSURES: NEMA 1 OR NEMA 3R AS INDICATED ON THE DRAWINGS NEMA 1 ENCLOSURES: FURNISHED WITH KNOCKOUTS WHERE PRACTICAL; FABRICATED FROM SHEET STEEL, GALVANIZED AFTER FORMING; ELECTRODEPM ED, GRAY BAKED ENAMEL FINISH. PROVIDE PADLOCKING PROVISIONS TO ALLOW LOCKING THE CIRCUIT BREAKER IN THE "OFF" POSITION. NEMA 3R ENCLOSURES FOR CIRCUIT BREAKERS RATED THRU THE 225 AMPERE FRAME SIZE FURNISHED WITH PROVISIONS FOR INTERCHANGEABLE, BOLT -ON HUBS. NEMA 3R ENCLOSURE COVERS SECURABLE IN THE OPEN POSITION. PROVIDE PADLOCKING PROVISIONS TO ALLOW LOCKING THE ENCLOSURE COVER CLOSED. _ P. ALL ENCLOSED CIRCUIT BREAKER, FUSIBLE SWITCHES, AND DISCONNECT SWITCHES INSTALLED OUTSIDE OR IN WET OR DAMP LOCATIONS, SHALL BE IN A NEMA 3R ENCLOSURE. 16450 - GROUNDING A. EXPOSED METALLIC PARTS OF THE ELECTRICAL SYSTEM WHICH ARE NOT INTENDED TO CARRY CURRENT, INCLUDING SYSTEM COMPONENTS SUCH AS BUSDUCTS, SWITCHBOARDS, PANELBOARDS AND RACEWAY SYSTEMS, AND INCLUDING GROUNDING AND NEUTRAL CONDUCTORS OF THE VARIOUS HARING SYSTEMS, SHALL BE GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS., B. PROVIDE COPPER CLAD STEEL GROUND RODS 3/4 INCH DIAMETER 10 FEET LONG DESIGNED FOR DRIVEN INSTALLATION. C. PROVIDE EXOTHERMIC TYPE CHEMICAL WELDED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND RODS, GROUNDING PLATES AND SPLICING OF, CONDUCTORS. ,PROVIDE COMPRESSION AND BOLTED TYPE (:ONNECTORS FOR JOINING OF GROUNDING ELECTRODE 1. CONDUCTORS TO GROUNQ',BARS ,, �` D. PROVIDE MECHANICAL. TYPE CONNECTORS FOR JOINING OF''ALL EQUIPMENT AND ISOLATED GROUND CONDUCTORS E SIZE GROUNDING CONDlIC' 01 ' IN ACC()R- . ;WITH TABLES 250 -66 AND 250 -122 OF THE NEC. F. PROVIDE GROUNDING BUSHINGS ON, ALL RACEWAYS TERMINATING WITHIN ALL ELECTRICAL ENCLOSURES CONSTRUCTED "OF SEPARATE ENCLOSURE PANELS WHICH `ARE NOT INTEGRALLY WELDED TOGETHER. PROVIDE GROUNDING CONDUCTORS FROM SUCCH BUSHINGS PTO. ^THE„ FRAME ,OF THE ENCLOSURE, GROUND BUS AND EQUIPMENT GROUNDING STRAP `WHERE ~ ONE OCCURS G. PROVIDE A SEPARATE GREEN - INSULATED EQUIPMENT GROUNDING CONDUCT WITH INSULATION OF -THE SAME' RATING AS THCPHASE 'CONDUCTORS, FOR ALL FEEDERS AND BRANCH,CIRCUITS.,`INSTALL' THE GROUNDING CONDUCTORS IN THE RACEWAY WITH RELATED PHASE AND NEUTRAL CONDUCTORS WHERE, PARALLEL CONDUCTORS IN SEPARATE RACEWAYS OCCUR," PROVIDE "A ' ` - '` GROUNDING CONDUCTOR IN EACH RACEWAY. CONNECT ALL GROUNDING CONDUCTORS TO ,GROUND TERMINALS AT EACH END OF THE RUN,- 70.'1HC END;IHAT.-iHERE WILL`BE NO UNINiERRUPiED'GROUNDING CIRCUIT FROM TH POINT OF GROUND FAULT BACK TO A POINT OF CONNECTION OF THE EQUIPMENT GROUND AND SYSTEM NEUTRAL H. CONNECT THE SECONDARY NEUTRAL POINT AND THE ENCLOSURE IN EACH DRY TYPE TRANSFORMER TOGETHER AND RUN A GROUNDING ELECTRODE CONDUCTOR FROM THEIR COMMON POINT OF CONNECTION TO THE BUILDING GROUNDING ELECTRODE SYSTEM. . I. PERFORM THE FOLLOWING TESTS: 1. TEST THE CONTINUITY OF, AND THE PROPER CONNECTION OF, EACH GROUND CONDUCTOR AND SYSTEM, TO ASSURE THAT THE GROUNDING SYSTEM IS COMPLETE AND UNINTERRUPTED. TESTING SHALL BE PERFORMED USING LABORATORY - ACCURACY TEST INSTRUMENTS OF SUITABLE DESIGN FOR THE TESTS TO BE PERFORMED. TEST INSTRUMENTS SHALL BE PROVIDED UNDER DIVISION 16. 2 TEST GROUNDING CONDUCTORS, PHASE CONDUCTORS AND NEUTRAL CONDUCTORS FOR CONTINUITY AND FOR POSSIBLE DAMAGE TO INSULATION. EACH CONDUCTOR SHALL BE TESTED FOR INSULATION FROM GROUND AND FROM OTHER CONDUCTORS. 3. ANY PORTIONS OF THE INSTALLATIONS MICH FAIL TO PASS THESE TESTS SHALL BE REPLACED, REPAIRED OR OTHERWISE CORRECTED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, AND COMPLETELY RETESTED TO SHOW PROPER CONFORMITY. 4, CONTRACTOR IS RESPONSKE FOR TESTING THE EFFECTIVENESS OF THE GROUNDNG SYSTEM FOR ALL SLEC1RICAL. DEVICES N THE SCOPE OF WORK AREA BY VOLTAGE AND IMPEDANCE MEASUREIENITS AS INDICATED IN NFPA 99, 463.3.1.3 & 4`3.3.1.4 RESPECTIVELY. THE RESULTS SHALL. RECORDED WTH A METER THAT HAS BEEN CUNTED WIITHN THE LAST 12 MONTHS THE METER AND TYPED OR POM RECORDED RESULTS SHALL BE MADE AVAILABLE AT TIME OF FINAL INSPECTION. J. THE EQUIPMENT GROUNDING TERMINAL BUSES OF THE NORMAL AND ESSENTIAL BRANCH- CIRCUIT PANELBOARDS SERVING THE SAME INDIVIDUAL PATIENT VICINITY SHALL BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 AWG. WHERE TWO OR MORE PANELBOARDS SERVING THE SAME INDIVIDUAL PATIENT VICINITY ARE SERVED FROM SEPARATE TRANSFER SWITCHES ON THE EMERGENCY SYSTEM, THE EQUIPMENT GROUNDING TERMINAL BUSES OF THOSE PANELBOARDS SHALL BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 AWG. THIS CONDUCTOR SHALL BE PERMITTED TO BE BROKEN IN ORDER TO TERMINATE ON THE EQUIPMENT GROUNDING TERMINAL BUS IN EACH PANELBOARD. 6475 - OVERCURRENT PROTECTIVE DEVICES A. PROVIDE DATA SHEET'S SHOWING ELECTRICAL CHARACTERISTICS INCLUDING TiME- CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL B. FAULT CURRENT VALUES INDICATED ON THE DRAWINGS ARE BASED ON ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE CONFIGURATIONS INDICATED RATED FOR THE AVAILABLE FAULT CURRENT INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE C. CIRCUIT BREAKERS 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE SWITCHBOARD/PANELBOARD/MOTOR CONTROL CENTER MANUFACTURER. D. FUSES 1. ACCEPTABLE MANUFACTURERS: BUSSMAN, GOUL SHAWMUT, OR UTTLEFUSE 2. FUSES SHALL HAVE 200,000 RMS SYMMETRICAL AMPERE INTERRUPTING CAPACITY AT 600V OR LESS, CURRENT LIMITING TYPE, TIME DELAY CHARACTERISTICS - 10 SECONDS (MINIMUM) AT 500% RATED CURRENT; UL CLASS RK1. E SELF- CONTAINED CIRCUIT BREAKER ENCLOSURES SHALL BE PADLOCKABLE NEMA 1, EXCEPT FOR UNITS IN DAMP OR WET AREAS WHICH SHALL BE A NEMA 3R ENCLOSURE WITH CONDUIT HUBS. F. ENCLOSURES FOR SELF- CONTAINED UNITS SHALL BE SECURELY MOUNTED TO WALL AND SHALL BE LEVEL AND TRUE MOUNTING HEIGHT SHALL BE PLUS 54" A.F.F. TO CENTER OF BREAKER U.N.O. G. FURNISH A NUMBER OF SPARE FUSES EQUALING 10% OF QUANTITY INSTALLED BUT NOT LESS THAN THREE (3) FUSES OF EACH TYPE AND RATING. H. INSTALL FUSES WITH LABEL ORIENTED SUCH THAT THE MANUFACTURER, TYPE AND SIZE ARE EASILY READ. 16500 - LIGHTING FIXTURES A. CONTRACTOR SHALL QUOTE THE SPECIFIED LIGHT FIXTURES IN BASE BID. ANY PROPOSED ALTERNATES MUST BE SHOWN AS AN EXCEPTION TO BASE BID AND MUST BE ACCOMPANIED BY UNIT PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID. ANY PROPOSED ALTERNATE FIXTURES SHALL MATCH THE FOLLOWING SPECIFIED LIGHTING FIXTURE CHARACTERISTICS: PHYSICAL SIZE AND DIMENSIONS, CONSTRUCTION, MATERIAL, LAMP AND BALLAST TYPE, LENS AND REFLECTOR TYPE, PAINT APPLICATION PROCESS, AND PHOTOMETRIC CHARACTERISTICS. ALL RATINGS INCLUDING, BUT NOT LIMITED TO WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION RATINGS SHALL ALSO MATCH. ANY PROPOSED ALTERNATES NOT MEETING ANY OF THESE CHARACTERISTICS SHALL BE REJECTED. B. FIXTURES SHALL BE COMPLETE WITH LAMPS, BALLASTS AND RELATED AUXILIARY EQUIPMENT AND ACCESSORIES NECESSARY TO THE INTENDED OPERATION, INCLUDING MOUNTING DEVICES REQUIRED FOR EACH TYPE OF INSTALLATION. C. ALL LIGHTING FIXTURES SHALL BEAR THE UL LABEL D. WHERE LIGHTING FIXTURES ARE SCHEDULED WITH PLASTIC LENSES, PROVIDE ACRYLIC LENSES HAVING A THICKNESS OF 0.125 INCHES. E. LAMPS 1. EACH UGH71NG FIXTURE SHALL BE FURNISHED WITH A NEW SET OF LAMPS OF THE TYPES INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. LAMPS SHALL BE MANUFACTURED BY GENERAL ELECTRIC, PHILIPS, OR OSRAM- SYLVANIA, EXCEPT WHERE SCHEDULED OTHERWISE. 2. INCANDESCENT LAMPS: IN GENERAL, THEY SHALL INSIDE FROSTED, ENERGY SAVING STYLE DESIGNED FOR 130V OPERATION WITH A RATED LIFE OF 2,500 HOURS (EXTENDED SERVICE). WHERE REFLECTOR STYLE LAMPS ARE SCHEDULED, FURNISH BEAM PATTERN INDICATED. 3. FLUORESCENT LAMPS: IN GENERAL, THEY SHALL BE 3500K COLOR, 48 -INCH LENGTH, T8, RAPID START, ENERGY SAVING LAMPS WITH AN INITIAL NOMINAL OUTPUT OF 2,850 LUMENS AT 32W, AND AN AVERAGE RATED LIFE OF 20,000 HOURS. 4• HIGH INTENSITY DISCHARGE (HID) LAMPS: SHALL BE OF THE TYPE AND WATTAGES SCHEDULED. WHERE METAL HALIDE LAMPS ARE INDICATED, SELF - EXTINGUISHING LAMPS SHALL BE FURNISHED WHERE AVAILABLE IN THAT WATTAGE RANGE. F. FLUORESCENT BALLASTS SHALL BE EQUAL TO MOTOROLA LIGHTING INC. RAPID START HIGH PERFORMANCE ELECTRONIC TYPE. G. INSTALLATION 1. THE WEIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS. PROVIDE HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY IN PLACE. 2 THE WEIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS. PROVIDE HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY IN PLACE. 3. THE MOUNTING BRACKETS SHALL BE INSTALLED TO OVERLAP THE CEILING SUPPORT CHANNELS IN ORDER TO PREVENT THE CHANNELS FROM SHIFTING FROM UNDERNEATH THE FIXTURES. 4. THE LIGHTING FIXTURE INSTALLATION SHALL NOT INTERFERE WITH THE INSTALLATION OR REMOVAL OF ADJACENT CEILING PANELS. 5. RECESSED FIXTURES IN DROPPED CEILING AREAS SHALL BE CONNECTED USING FLDNBLE CONDUIT. CONDUIT SHALL BE CONNECTED TO FIXTURE AND OUTLET BOX. EACH PIECE SHALL HAVE A SEPARATE INSULATED GREEN GROUNDING CONDUCTOR ,#14 MIN. FOR GROUNDING CONTINUITY BETWEEN THE FIXTURE AND THE CONDUIT SYSTEM. GROUNDING CONDUCTOR SHALL BE MECHANICALLY CONNECTED IN A PERMANENT AND EFFECTIVE MANNER TO FIXTURE AND CONDUIT SYSTEM AND BE ELECTRICALLY CONTINUOUS. 16721 - FIRE ALARM SYSTEM (MODIFICATION) A. FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS AND RELOCATIONS AS INDICATED ON THE DRAWINGS, COMPATIBLE AND . CONSISTENT WITH THE EXISTING SYSTEM. B. THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING CONTINUAL SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR EXPANSION. C. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE EXPANDABLE MODULES, POWER SUPPLIES, HARDWARE, SOFTWARE, ETC. TO THE FIE ALARM SYSTEM N ORDER TO ACCOMMODATE THE ADDITIONAL FIRE ALARM DEVICES D. CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW SMOKE DETECTORS. OR, E. THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, DUCT AND HEAT DETECTORS. CONTRACTOR SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. F. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE E SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WITH DIVISION 15. G. VISUAL STROBE DEVICES SHALL MEET THE REQUIREMENTS OF ADA, UL, AND NFPA. H. AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS WITH A PEAK OUTPUT OF 96dB AT 10' -O ". I. ALL WIRING SHALL BE STRANDED AND IN CONDUIT. COLOR SHALL BE THE FACILITY'S STANDARD OR RED. J. PROVIDE NEW CONDUIT AND WIRING AS REQUIRED FOR NEW FIRE ALARM DEVICES CONNECT AND PROGRAM DEVICES IN EXISTING FIRE ALARM CONTROL. PANEL COORDINATE EXACT LOCATION OF EXISTING FIRE CONTROL PANEL WITH OWNER. NEW DEVICES ARE TO MATCH EXISTING ONES AND BE UL LISTED WITH EXISTING FIRE ALARM SYSTEM. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES OR ANY SOFTWARE OR HARDWARE ACCESSORIES REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. ALL DEVICES SHALL MEET ADA REQUIREMENTS K. CONTRACTOR SHALL SUBMIT SIGNED AND SEALED PLANS INDICATING EXACT LOCATION, TYPE, CABLING, AND BATTERY CALCULATIONS. L ALL WIRING SHALL BE IN 3/4 "C. MINIMUM. M. VENDOR SHAT RE- CERTIFY THE SYSTEM AND PROVDE CERiFiCATION AND .%M DETECTOR SEN9iMTY REPORT PRIOR 70 ANY INSPECTION. N. SYNCHRONIZE ALL AUDIOVISUAL DEVICES. 0. AUDIBLE DEVICES SHALL BE ON SEPARATE CIRCUITS THAN VISUAL DEVICES. BE P. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE AHU SHALL SHUT DOWN WHEN IN MANUAL OR AUTOMATIC POSITION. EXHAUST FAN SHALL BE INTERLOCKED WITH THE AHU STARTER. LOCATE FIRE ALARM RELAY WITHIN S -0" OF STARTER. 16741 - TELEPHONE AND DATA COMMUNICATIONS A. AT ALL WALL DATA/VOICE OUTLET LOCATIONS, PROVIDE A 4 11/16" SQUARE BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLATE 1" MIN. EMPTY CONDUIT SHALL RUN WITH PULL CORD TO 6" ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE WHERE CORRIDORS DO NOT HAVE ACCESSIBLE CEILINGS, PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM COVERING THE ENTIRE LENGTH OF NON - ACCESSIBLE COUNG CAVITY. NUMBER AND SIZE OF CONDUIT/SLEEVES SHALL BE PER MANUFACTURER'S CABLING REQUIREMENTS. B. PROVIDE A MINIMUM OF A 3/16" DIAMETER, TWISTED NYLON PLASTIC CORD IN ALL EMPTY RACEWAYS. PROVIDE A IDENTIFICATION TAG ON EACH END INDICATING THE LOCATION OF THE OTHER END. C. INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. D. WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 314" THICK APA A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) COATS OF LIGHT GRAY PAINT. BACKBOARDS SHALL BE MOUNTED SIX (6 ") INCHES A.F.F. AND EXTEND UPWARD A FULL EIGHT (8' -0 ") FEET OR TO THE CEILING GRID IF LESS THAN W -0 ". Project #:412469.000 ' ' - 2121 ?once de Leon Bouleva d �� Suite 350 I Coral Gables, Fl .i�) 34 4 phone: 305.569.1692 fax: 305.569.1693 Professional Consulting Engineers Austin • Pallns , U°nver . Nou ^ton . Kan ,as City . Miami Nashv.11e . Phodnix . Richmond • Wasningtur D.C. EC00oo;s53 16900 - EQUIPMENT CONNECTIONS AND CONTROL WIRING A. THE FURNISHING ANT' 'Ik :STALLP.T('X OF CORn. X POW-71 MIRING REQUIRED FOR EQU'PYN- f FURNISHEU UNDER DIVISION 15 P.ND NOT SHOWN ON THE ELFCTRIG4L DRAWINGS SHALL BF FURNISHE) UNDER DIVISION _15. CONTROL PO%a 4A" i3 DLI`6ED AS "ihE LINE VOLTAGE. (12OV) POWER WIRING FOR EQUIPMENT CONTROL CABINETS, TEMPERATURE CONTROL, ENERGY MANAGEMENT, OR BUILDING AUTOMATION SYSTEM PANELS AND LINE VOLTAGE SMOKE/FIRE DAMPERS. B. THE FURNISHING AND INSTALLATION OF THE TEMPERATURE CONTROL WIRING, ENERGY MANAGEMENT SYSTEM OR BUILDING AUTOMATION WIRING NOT SHOWiN ON THE ELECTRICAL DRAWINGS SHALL BE FURNISHED UNDER DIVISION 15. TEMPERATURE CONTROL, ENERGY MANAGEMENT SYSTEM AND BUILDING AUTOMATION SYSTEM WIRING IS DEFINED AS THE INTERLOCK OR INTERCONNECTING WIRING REQUIRED BETWEEN SYSTEM CONTROL DEVICES, APPURTENANCES AND CONTROL PANELS TO ALLOW THE SYSTEM TO FUNCTION AUTOMATICALLY. THIS INCLUDES WIRING BETWEEN THE FIRE ALARM SYSTEM, =SMOKE EXHAUST SYSTEMS, DOOR ENTRY SYSTEMS AND ANY OTHER SYSTEM REQUIRING INTERFACE WITH THE TEMPERATURE CONTROL;'ENERGY MANAGEMENT AND BUILDING AUTOMATION C. PROVIDE POWER WIRING TO EACH MOTOR -DRIVE AND /OR ELECTRICALLY- OPERATED SYSTEM OR UNIT OF EQUIPMENT. THE WIRING SHALL ALLOW THE MOTOR(S) OR EQUIPMENT TO OPERATE IN A MANUAL MODE. D. CONTROL WIRING WILL, UNLESS SPECIFICALLY NOTED OTHERWISE, WILL BE FURNISHED AND INSTALLED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS. E EXCEPT FOR ITEMS THAT ARE FURNISHED WITH FACTORY - INSTALLED, INTEGRAL MOTORS, AN ELECTRIC MOTOR OF REQUIRED SIZE AND ELECTRICAL CHARACTERISTICS WILL BE PROVIDED AND INSTALLED UNDER OTHER DIVISIONS FOR EACH ITEM OF MOTOR- DRIVEN EQUIPMENT. COMPLETE THE ELECTRICAL INSTALLATION OF THESE MOTORS IN ACCORDANCE WITH .APPROVED WIRING DIAGRAMS AND INSTRUCTIONS. F. WHERE DISCONNECT SWITCHES OR CIRCUIT BREAKERS ARE NOT PROVIDED INTEGRAL WITH CONTROL EQUIPMENT FOR MOTORS AND OTHER ELECTRICAL APPURTENANCES, PROVIDE AND INSTALL ALL DISCONNECT SWITCHES REQUIRED BY THE NATIONAL ELECTRICAL CODE AND /OR INDICATED, G. WHERE POSSIBLE, TERMINATE CONDUITS IN CONDUIT BOXES ON MOTORS. WHERE MOTORS ARE NOT PROVIDED WITH CONDUIT BOXES, TERMINATE THE CONDUITS IN CONDUIT FITTINGS AT THE MOTORS. ROVISIM& A QV :., _4 A _'', 1 A �._ _,�,,�,,' '�, _` 1"�,�.,i"A I �_` ,,,, 11 1!1,,� , y _J ", 11 I _­1 F- z LAJ ::E LAJ V Q a LAJ oC V 0< z rwC V 04 a V) 0 x H z a 0 U z a r--) F:.I . g*I M n 0. � Ln 9"" 2 9 o r Sz,. 3 A s �` ti I. H. a "G- �i'lleI� q i0 z : ;, N x K:: I 6 L ^` 7, Ao 4 0 (A w Q V ""! L ; > , *I ,ice+ 0 rI >1 "1-- -� irk ,l y4`. 1 I *7� �0 !j .d W :E .,i .wv VII 4" � '­'N 0 I;0 �`_ 1, � , r wi 1... Q ,1& w +_;fi :3 IZ,, F t .; ,, W.. ,: 41 o A�r z z wX "A z(A V Z Z ,. 0.4 11 � 0 Q !� V) PERMIT SET 0"vin RR QlitKMIN LEN DIATFA 1 -23 -2012 SCAIA AS SHOWN i a.. d O ' 1 i'O� � f; :'a1 G' Hy �..'. 8 " ,; �. tt)). ELECTKICALltF GlkER '' :' I E5.00 I JOB f 20113.1 1