Loading...
13-185-046GREEN HEX HEAD GROUNDING SCREW uI�Y Al &ArU I\IT\I11 071MAA AE DE/1CnTAMC n'^'JNDED METAL .ET BOX CEILING HANGER WARE — BONDING JUMPER FIXTURE SUPPORT - HANGER WIRE MINIMUM OF 2 POINTS (OPPISITE CORNERS, SIDES OR ENDS) FOR FIXTURE UP TO 48" IN LENGTH. SEPARATE FROM CEILING SUPPORTS. LIGHT FIXTURE OR OTHER CEILING MOUNTED EQUIPMENT NEUTRAL BUILDING MOUND (MEEN WIRE) 07NOSCALE STANDARD RECEPTACLE GROUNDING DETAIL Project #:412469.000 ,w L 2121 "cnc2 de Lean BoilevafJ Suite 150 Coral Gables, FL ?3134 SUPPORT CONDUIT WITHIN 3 phone; 305.569.1692 FT. OF J-BOX AND AT J __ L a fax: 305.569.1693 INTERVALS REQUIRED BY Austin al consulting D dEngineers SPECIFICATIONS. Austin . DaJas . Denver . Houston .Kansas city •Miami J-BOX SECURED FROM STRUCTURE EXHAUST Nashv;;le . Pho�ni;:E 9000755Q Nas iingtcn D.C. FIRE/SMOKE OR SMOKE TUBE EMT CONDUIT TO OTHER DAMPER J-B INLET HOLES FACING INTO Aik FLOW CEILING FIXTURE WHIPS MAXIMUM 6 FT. IN LENGTH SUPPORT WHIPS WITHIN 12 IN. FROM J-BOX AND AT 4 1/2 FT. INTERVAL FIXTURE SHALL NOT BE USED AS THROUGH WARE WAYS. LAY -IN T -BAR LAY -IN FIXTURE MOUNTING DETAIL 06NO SCALE (UFE SAFETY BRANCH) 120V PHASE CONDUCTOR 120V NEUTRAL CONDUCTOR FROM PANEL (DIVISION 16) FROM PANEL (DIVIISION 16) REFER TO FLOOR PLANS FOR CIRCUIT NUMBER. TYPICAL SMOKE ZONE CONTROL RELAY MODULE FOR FIRE ALARM INTERFACE. MODULE BY FIRE ALARM CONTRACTOR. -120V PHASE CONDUCTOR (DIVISION 16) TO FIRE ALARM SYSTEM 12V do OR 24V do (TO BE DETERMINED BY FIRE ALARM CONTRACTOR) (LIFE SAFETY BRANCH) AIR FLOW — LI DUCT MOUNTED DETECTOR ACCESS HOUSING DOOR CLUNG 1oj �-- REMOTE LED DETECTOR STATUS GENERAL NOTES INDICATOR ON WALL MOUNTED AT 80" AFF OR CEILING A. THIS DETAIL SHALL PERTAIN TO DAMPERS INSTALLED IN SUPPLY AIR DUCTS, RETURN AIR DUCTS, AND RETURN AIR MOUNTED. OPENINGS AS REQUIRED BY THE SPECIFICATIONS AND GOVERNING CODES. B. PROVIDE SMOKE DETECTORS AT BLL FIRE/SMOKE AND SMOKE DAMPER LOCATIONS. COORDINATE EXACT LOCATION OF ALL FIRE /SMOKE AND SMOKE DAMPERS WITH DIVISION 15 FLOOR PLANS. AS REQUIRED BY LOCAL AUTHORITY HOUSING JURISDICTION. C. INSTALL DUCT DETECTORS IN ACCORDANCE WITH DUCT MOUNTED SMOKE DETECTOR DETAIL D. DUCT SMOKE DETECTORS PROVIDED AND INSTALLED BY FIRE ALARM CONTRACTOR. FINAL LOCATION TO BE COORDINATED WITH THE MECHANICAL CONTRACTOR. DUCT SMOKE DETECTOR DETAIL AT ALL SMOKE AND FIRE/SMOKE DAMPERS 03-NO SCALE GENERAL NOTES COMBINATION FIRE /SMOKE AND SMOKE DAMPERS UTILIZING A. DAMPERS PROVIDED AND INSTALLED BY DIVISION 15. B. FIRE ALARM CONTROL RELAY MODULE AND CONTROL WRING FURNISHED AND INSTALLED BY FIRE ALARM VENDOR, C. 120V POWER WIRING AND TERMINATIONS BY ELECTRICAL CONTRACTOR. TYPICAL SMOKE AND SMOKE /FIRE DAMPER WIRING DIAGRAM PIPE PENETRATION PIPE PENETRATION FOR EXPOSED ARES I - FOR EXPOSED AREA INTERIOR WALL CUT SMOOTH HOLE PACK TIGHT W /FIRE SAFING CHROME PIPE COLLAR f - -. ; ____'_`SCHEDULE 40 PIPE SLEEVE PROVIDE 1" MINIMUM CLEARANCE 1" THICK 3M -FIRE STOP OR EQUAL U.S. GYPSUM THERMA -FIBER OUND ALL PIPES (TYPICAL) 1" MINIMUM U.L SYSTEM NO. W -L -1054 F RATING - 1 HOUR AND 2 HOUR T RATING - 0 HOUR QFIRE PENETRATION DETAIL 2NO SCALE Ub SCALE: NONE INSTALLATION DETAILS BELOW SHALL PERTAIN TO SMOKE DETECTORS IN ETU N AIR DUC AND RETURN AIR OPENINGS EMT TO PANEL PROPERLY SECURED TO OR SUPPORTED FROM STRUCTURE BY DIVISION 16 PROVIDE HOA STARTER OR COMBINATION STARTER DISCONNECT, FUSED OR NON -FUSED AS INDICATED MOUNTED WITHIN SIGHT OF EQUIPMENT. (SUPPORTED BY UNISTRUT OR ALL- THREAD AFFIXED TO THE STRUCTURE, ENSURE PROPER NEC CLEARANCES ARE MET AT TIME OF INSTALLATION. COORDINATE WITH OTHER ITEMS LOCATED IN THE CEILING PLENUM SPACE FLEXIBLE CONDUIT STRUCTURE TYPICAL TERMINAL BOX OR UNIT HEATER WITH ELECTRIC HEAT. TYPICAL CAV OR FCU WITH HOA STARTER /DISCONNECT 04 � sC,� CEILING SUPPLY AIR DUCTS, R R TS, AS REQUIRED BY THE SPECIFICATIONS AND GOVERNING CODES. PROVIDE QUANTITIES AND MOUNTING LOCATIONS PER MANUFACTURERS RECOMMENDATIONS. MAXIMUM SIZE DUCT FOR r 7 SINGLE DETECTOR w 3 0 36" _ w -�k nD nD 36" SMOKE DETECTOR MOUNTED IN CENTER OF DUCT MAXIMUM SIZE DUCT FOR (2) DETECTORS W/4 ol DUCT MOUNTED, NO SCALE 14, W/4 IF DUCT IS GREATER THAN 36" TALL, PROVIDE (1) ADDITIONAL ROW OF DETECTORS PER 36" OF WIDTH OVER 36" 72" 24 "-- �D OD OD 36" IF DUCT IS GREATER THAN 72" WIDE, PROVIDE (1) ADDITIONAL DETECTOR PER 24" OF WIDTH OVER 72' ', DETECTOR DETAILS Revidom 0 0 0 0 0 C" ZI a V 0w <x 0.4� �z V � x0, z V � X W � F-" < N �. 'U f � O � V � W a 4.0 �d M V�� 16, O m vi ,, i gilt �w ~ Q 0 W in z z= � a V w � � z�A V c/1 m II)RAVM RR CtICKM LEN DiATFA 1-23 -2012 WWFs AS SHOWN Ai 11311 ' V Sheet No. FA.00 JM 0 201131