Loading...
13-185-038LIGHTING SYMBOLS LEGEND SYMBOL DESCRIPTION 2'x4' FLUORESCENT LIGHT FIXTURE ON NORMAL CIRCUIT. ® 2'x4' FLUORESCENT LIGHT FIXTURE ON LIFE SAFETY CIRCUIT. DESCRIPTION 2'x4' FLUORESCENT LIGHT FIXTURE ON CRITICAL CIRCUIT. SYMBOL E0 SEE FIXTURE 2'x4' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON NORMAL CIRCUIT AND SINGLE RECEPTACLE - 2OA/125V/2P/3W/G NEMA 5-208 18' AFF Q OUTBOARD OUTBOARD LAMPS ON NORMAL CIRCUIT. SCHEDULE SCHEDULE DEVICES AS THEY RELATE TO OTHER (NON -FIRE ALARM) SYSTEMS AND FOR PERMITTING PURPOSES. THE 2'x4' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON LIFE SAFETY CIRCUIT AND ATS AUTOMATIC TRANSFER SWITCH Coral Gables, FL 33134 SEE FIXTURE SCHEDULE OUTBOARD LAMPS ON NORMAL CIRCUIT. DUPLEX RECEPTACLE - 2OA/125V/2P/3W/G NEMA 5 -20R 18' AFF 18" AFF 2'x4' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON CRITICAL CIRCUIT AND 80" TO THE BOTTOM OF THE LENS OR 6' BELOW FINISHED CEIUNG SEE FIXTURE SCHEDULE C OUTBOARD LAMPS ON NORMAL CIRCUIT. 18' AFF 2'x2' FLUORESCENT LIGHT FIXTURE ON NORMAL CIRCUIT. ® 2'x2' FLUORESCENT LIGHT FIXTURE ON LIFE SAFETY CIRCUIT. ® 2'x2' FLUORESCENT LIGHT FIXTURE ON CRITICAL CIRCUIT. 18" AFF ® SMOKE DETECTOR CEIUNG OR WALL MOUNTED, PHOTOELECTRIC TYPE UNO 2'x2' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON NORMAL CIRCUIT AND 80" TO THE BOTTOM OF THE LENS SCHEDULE 0:1 OUTBOARD LAMPS ON NORMAL CIRCUIT. 18' AFF ® FIRE ALARM VISIBLE NOTIFICATION APPLIANCE 2'x2' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON LIFE SAFETY CIRCUIT AND 18" AFF (p� I �p SINGLE TATION SMOKE DETECTOR - FOR PATIENT SLEEPING ROOM, CEIUNG OR WALL OUTBOARD LAMPS ON NORMAL CIRCUIT. RCPT(S) OR RECEPTACLE(S) ® ELEC ELECTRIC 2'x2' FLUORESCENT LIGHT FIXTURE W/INBOARD LAMPS ON CRITICAL CIRCUIT AND SS(,'FIFIIXTURE EDULE � OUTBOARD LAMPS ON NORMAL CIRCUIT. 8* AFAFFOR WALL MOUNTED LINEAR FIXTURE ON NORMAL CIRCUIT. SMOKE DETECTOR CONNECTED TO INITIATE ELEVATOR RETURN SEQUENCE WALL MOUNTED LINEAR FIXTURE ON LIFE SAFETY CIRCUIT. SF SUPPLY AIR FAN WALL MOUNTED LINEAR FIXTURE ON CRITICAL CIRCUIT. ® RECESSED /SURFACE MOUNTED LINEAR FIXTURE ON NORMAL CIRCUIT. ® RECESSED /SURFACE MOUNTED LINEAR FIXTURE ON LIFE SAFETY CIRCUIT. ® RECESSED /SURFACE MOUNTED LINEAR FIXTURE ON CRITICAL CIRCUIT. is SUSPENDED PENDANT FIXTURE ON NORMAL CIRCUIT. 0 RECESSED /SUSPENDED DOWNUGHT FIXTURE ON NORMAL CIRCUIT. F0 WALL MOUNTED FIXTURE ON NORMAL CIRCUIT 0 RECESSED /SUSPENDED DOWNLIGHT FIXTURE ON LIFE SAFTEY CIRCUIT. F0 WALL MOUNTED FIXTURE ON LIFE SAFETY CIRCUIT. 0 RECESSED /SUSPENDED DOWNUGHT FIXTURE ON CRITICAL CIRCUIT. F0 WALL MOUNTED FIXTURE ON CRITICAL CIRCUIT. 0 RECESSED DOWNLIGHT FIXTURE WITH WALL WASH TRIM ON NORMAL CIRCUIT. 90 RECESSED DOWNLIGHT FIXTURE WITH WALL WASH TRIM ON LIFE SAFETY CIRCUIT. 0 RECESSED DOWNUGHT FIXTURE WITH WALL WASH TRIM ON CRITICAL CIRCUIT. F 4 CEIUNG, WALL OR END MOUNTED EXIT SIGN. SHADING INDICATES DOUBLE OR SINGAL FA SUPPRESSION ARROWS INDICATE CHEVRON DIRECTIONS. u WALL MOUNTED EMERGENCY BATTERY - POWERED EGRESS LIGHTING. SMOKE DOOR MECHANICAL HOLD OPEN, CONNECT TO FIRE ALARM SYSTEM - STUB 3/4' WALL SWITCH SPST, 20A, 120/277V $2 DOUBLE POLE TOGGLE SWITCH, 20A/120/277V $3 3 -WAY WALL SWITCH, 20A, 120/277V $4 4 -WAY WALL SWITCH, 20A, 120/277V $D WALL BOX DIMMER SWITCH $K KEY OPERATED WALL SWITCH $T WALL SWITCH WITH ADJUSTABLE COUNTDOWN 11MER $3D 3-WAY WALL DIMMER SWITCH, 20A, 120/277V $311K 3 -WAY, KEY OPERATED WALL SWITCH, 20A, 120/277V $0 LIGHTING CONTROL SWITCH BANK FOR MUIIPLE SWITCHES, REFER TO DETAIL FOR VP VAPOR PROOF REFER TO ARCM. ELEVATIONS FOR MOUNTING HEIGHT QUANTITY OF SWITCHES IN BANK. $LV LOW VOLTAGE WALL SWITCH - MOMENTARY CONTECT U.N.O. ® CEILING MOUNTED OCCUPANCY SENSOR PROVIDE POWER PACKS AS REQUIRED REFER TO SPECIFICATIONS FOR REQUIREMENTS. - 1000 SQUARE FEET) CLOCK HANGER OUTLET WITH NEMA 5-15R RECEPTACLE. CONFIRM BACKBOX SIZE WITH (600 $L ILLUMINATED WALL SWITCH - ILLUMINATED WHEN SWITCH IS IN OFF /OPEN POSITION $P PILOT LIGHT WALL SWITCH $OS WALL MOUNTED OCCUPANCY SENSOR SWITCH REFER TO SPECIFICATIONS FOR REQUIREMENTS. 0 CEIUNG MOUNTED PASSIVE INFRARED (PIR) OCCUPANCY SENSOR WITH 450SF COVERAGE JB JUNCTION BOX WT WATER TIGHT 050Q CEIUNG MOUNTED PASSIVE INFRARED (PIR) OCCUPANCY SENSOR WITH 15M COVERAGE XFMR TRANSFORMER CEILING WITH NYLON PULLCORD FOR DATA /SIGNAL CABLE. 0p CEIUNG MOUNTED DUAL TECHNOLOGY (ULTRASONIC + PIR) OCCUPANCY SENSOR WITH 500 500SF COVERAGE 0-1> 500 CEIUNG MOUNTED ULTRASONIC OCCUPANCY SENSOR WITH 500SF COVERAGE CEIUNG MOUNTED DUAL TECHNOLOGY ULTRASONIC + PIR OCCUPANCY SENSOR WITH T�000 1000SF COVERAGE K000 1 CEILING NG MOUNTED ULTRASONIC OCCUPANCY SENSOR WITH 1 OOSF COVERAGE AS REQUIRED CEIUNG MOUNTED DUAL TECHNOLOGY (ULTRASONIC + PIR) OCCUPANCY SENSOR WITH 2000 2000SF COVERAGE 0 PUSHBUTTON -000 2 CEIUNG MOUNTED ULTRASONIC OCCUPANCY SENSOR WITH 1000SF COVERAGE Q POWER PACK FOR 120/230/277VAC SYSTEM. DIM 1 DIMMING SYSTEM CONTROL UNIT MVIRING DEVICE SYMBOLS LEGEND FIRE ALARM SYMBOLS LEGEND MTG. HT. UNO SEE NOTE 1 SYMBOL DESCRIPTION MTG. HT. UNO (SEE NOTE 1) SYMBOL MTG. HT UNO DESCRIPTION SEE NOTE 1 SEE FIXTURE Q- SINGLE RECEPTACLE - 2OA/125V/2P/3W/G NEMA 5-208 18' AFF Q MANUAL FIRE ALARM BOX (PULL STATION) 48'AFF SCHEDULE SCHEDULE DEVICES AS THEY RELATE TO OTHER (NON -FIRE ALARM) SYSTEMS AND FOR PERMITTING PURPOSES. THE COVERPLATE) ATS AUTOMATIC TRANSFER SWITCH Coral Gables, FL 33134 SEE FIXTURE SCHEDULE SEE SCHEDULE FIXTURE DUPLEX RECEPTACLE - 2OA/125V/2P/3W/G NEMA 5 -20R 18' AFF 18" AFF FIRE ALARM COMBINATION AUDIBLE/VISIBLE NOTIFICATION APPLIANCE 80" TO THE BOTTOM OF THE LENS OR 6' BELOW FINISHED CEIUNG SEE FIXTURE SCHEDULE C DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT - 2OA/125V/2P/3W/G NEMA 5-20R 18' AFF ® FIRE ALARM AUDIBLE NOTIFICATION APPLIANCE W TO THE BOTTOM OF THE LENS OR 6' BELOW FINISHED CEILING SEE FIXTURE TRANSIENT VOLTAGE SURGE SUPPRESSOR RCPT - 2OA/125V/2P/3W/G NEMA 5 -20R 18" AFF F�D SMOKE DETECTOR CEIUNG OR WALL MOUNTED, PHOTOELECTRIC TYPE UNO SS(',FIFIIXTURE EDULE 80" TO THE BOTTOM OF THE LENS SCHEDULE 0:1 DUPLEX RCPT GFl - 20A/125V/2P/3W/G NEMA 5-20R 18' AFF OQ FIRE ALARM VISIBLE NOTIFICATION APPLIANCE OR 6' BELOW FINISHED CEILING 48' AFF -0 EQUIPMENT CONNECTION - 48" AFF CIRCUIT CONDUCTOR INDICATION (NEUTRAL, PHASE, EQUIPMENT GROUND, ISOLATED - GROUND, SWITCH LEG) DEVICE W HOMERUN: CIRCUIT HOMERUN TO PANELBOARD 2f12, 1 f12G, 3/47C. 20A 1P CO UNO AFF 48" DEVICE W/O HOMERUN: REFER TO FEEDER AND PANEL SCHEDULES FOR WIRE, BREAKER SIZE AND - NUMBER OF POLES UNO. EACH 120V CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL 48" AM - - - - - CONDUIT INSTALLED IN CEIUNG SPACE OF FLOOR BELOW - BID NOTE 48' AFF X,X,X THREE SINGLE POLE DEVICE CIRCUIT NUMBERS - THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO. VISIT THE SITE AND 48" AFF X/X /X MULTI -POLE DEVICE CIRCUIT NUMBERS _ ASCERTAIN THE EXISTING CONDITIONS.. REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE EMERGENCY POWER OFF BUTTON. WALL MOUNTED - STUB 3/4" C. ABOVE ACCESSIBLE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING PO 48" AFF �-D E CEIUNG FROM OUTLET BOX AS REQUIRED INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE 48' AFF DHTA DECONTAMINATION HOLDING TANK ALARM - PANEL PROVIDED UNDER OTHER DIVISION AS REQUIRED EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK. CEIUNG MOUNTED GAP GENERATOR ANNUNCIATOR PANEL AS REQUIRED UNO 48' AFF ATSA AUTOMATIC TRANSFER SWITCH ANNUNCIATOR PANEL AS REQUIRED 48' AFF GROUND BAR - ElSTEP -DOWN TRANSFORMER - TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR DEVICE - MOTORIZED DAMPER - COORDINATE BETWEEN TRADES - - Fv-A--Q HVAC CONTROL PANEL - PANEL PROVIDED UNDER OTHER DIVISION - 48" AFF 48" AFF 48" AFF MTG. HT UNO SEE NOTE 1 15" AFF 15' AFF 15' AFF 15" AFF 48" AFF 15" AFF FI 412469.000 SCALE FIRE ALARM SYSTEM Project Y SEE FIXTURE y ". QUADRAPLEX RECEPTACLE (TWO DUPLEX RCPTS. UNDER ONE 18" AFF ®S FIRE ALARM SPRINKLER FLOW SWITCH SCHEDULE DEVICES AS THEY RELATE TO OTHER (NON -FIRE ALARM) SYSTEMS AND FOR PERMITTING PURPOSES. THE COVERPLATE) ATS AUTOMATIC TRANSFER SWITCH Coral Gables, FL 33134 FINAL FIRE ALARM PLANS TO BE SUBMITTED FOR AHJ APPROVAL SHALL BE PRODUCED AND SEALED BY A SEE SCHEDULE FIXTURE NC (N.C.) NORMALLY CLOSED DUPLEX RECEPTACLE MOUNTED HORIZONTALLY 18" AFF © FIRE ALARM SPRINKLER TAMPER SWITCH SEE FIXTURE SCHEDULE @r.Wp DUPLEX RECEPTACLE WITH WEATHERPROOF ENCLOSURE AND GCFI PROTECTED OUTLET 18" AFF ® FIRE ALARM SPRINKLER PRESSURE SWITCH SSCHmUURE � s TRANSIENT VOLTAGE SURGE SUPPRESSOR RCPT - 2OA/125V/2P/3W/G NEMA 5 -20R 18" AFF F�D SMOKE DETECTOR CEIUNG OR WALL MOUNTED, PHOTOELECTRIC TYPE UNO SS(',FIFIIXTURE EDULE � DUPLEX RCPT, TAMPER PROOF- 20A/125V/2P/3W/G NEMA 5-20R 18" AFF �=�1ZF-©IZ SMOKE DETECTOR CEIUNG OR WALL MOUNTED, IONIZATION TYPE UNO SEE FIXTURE SCHEDULE ® SPECIAL PURPOSE RECEPTACLE (NEMA NO. AS INDICATED) 18" AFF (p� I �p SINGLE TATION SMOKE DETECTOR - FOR PATIENT SLEEPING ROOM, CEIUNG OR WALL EC EMPTY CONDUIT RCPT(S) OR RECEPTACLE(S) ELEC ELECTRIC P SS(,'FIFIIXTURE EDULE � DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERTOP 8* AFAFFOR `-DER vER SMOKE DETECTOR CONNECTED TO INITIATE ELEVATOR RETURN SEQUENCE SEE FIXTURE SF SUPPLY AIR FAN QUADRAPLEX RECEPTACLE (TWO DUPLEX RCPTS. UNDER ONE 8" AFC OR O �-G HEAT DETECTOR CEIUNG OR WALL MOUNTED SCHEDULE SP SPARE COVERPLATE) MOUNTED ABOVE COUNTERTOP 42" AFF ST (S.T.) SHUNT TRIP SEE FIXTURE SCHEDULE SW SWITCH DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERTOP ON EMERGENCY CIRCUIT 8" AFC OR _ `r DUCT SMOKE DETECTOR FCU FAN COIL UNIT TF TRANSFER FAN 42' AFF TP TAMPER PROOF SEE FIXTURE SCHEDULE SEX DUPLEX RECEPTACLE EXPLOSION PROOF 18" AFF � F<S FIRE ALARM SPEAKER CEIUNG OR WALL MOUNTED SEE FIXTURE. SUPPRESSION CEIUNG MOUNTED RECEPTACLE - DUPLEX CONFIGURATION UNO RUSH W/ DH SMOKE DOOR MECHANICAL HOLD OPEN, CONNECT TO FIRE ALARM SYSTEM - STUB 3/4' SCHEDULE 1' CLG SURFACE UH UNIT HEATER C. ABOVE ACCESSIBLE CEIUNG FROM OUTLET SS(.'FIFIIXTURE EDULE � FLOOR MOUNTED RECEPTACLE/DATA DEVICE - REFER TO NOTES AND SPECIFICATIONS. FLU FLUSH R / F _AC P FIRE ALARM CONTROL PANEL SEE FIXTURE &rV DUPLEX RCPT, TELEVISION - PROVIDE UNDER SAME COVERPLATE AS CABLE OUTLET - 88' AFF FAAP FIRE ALARM ANNUNCIATOR PANEL SCHEDULE VP VAPOR PROOF REFER TO ARCM. ELEVATIONS FOR MOUNTING HEIGHT HV HIGH VOLTAGE VV VARIABLE VOLUME UNIT SEE FIXTURE SCHEDULE W WIRE CLOCK HANGER OUTLET WITH NEMA 5-15R RECEPTACLE. CONFIRM BACKBOX SIZE WITH IC INTERRUPTING CAPACITY FPAP FIRE PUMP ANNUNCIATOR PANEL ICAND INCANDESCENT © F-© VENDOR SHOP DRAWINGS. PROVIDE 3/4" CONDUIT STUBBED ABOVE NEAREST ACCESSIBLE 80• AFF WP WEATHER PROOF JB JUNCTION BOX WT WATER TIGHT SEE FIXTURE XFMR TRANSFORMER CEILING WITH NYLON PULLCORD FOR DATA /SIGNAL CABLE. LTG LIGHTING OF-C-P-1 FIREFIGHTER'S CONTROL PANEL SCHEDULE UNO. EXP EXPLOSION PROOF SEE FIXTURE SCHEDULE Q F-@ JUNCTION BOX - SIZE & MOUNTING AS REQUIRED AS REQUIRED FAPE I FIRE ALARM NAC POWER EXTENDER PANEL SEE FIXTURE SCHEDULE 0 PUSHBUTTON 48' AFF V JACK FOR FIREMAN'S PHONE (BY FIRE ALARM CONTRACTOR) SEE FIXTURE APP POWER POLE _ OF WARDEN STATION TELEPHONE FOR FIREMAN'S PERMANENT HANDSET (BY FIRE ALARM SCHEDULE NOTE 1: ALL MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE, UNLESS OTHERWISE INDICATED. A) 48" AFF INDICATES TO TOP OF DEVICE; B) 15" AFF INDICATES TO BOTTOM OF DEVICE; SYSTEM) SEE FIXTURE [EP 30/3/ * /3R DISCONNECT SWITCH - 30/3/ * /3R INDICATES 30A, 3 POLE, * FUSED, NEMA TYPE AS REQUIRED OF POINT OF CONNECTION TO FIRE ALARM SYSTEM SCHEDULE * PROVIDE FUSES AS PER MANUFACTURERS RECOMMENDATIONS DOCUMENTS FOR DEFINITION AND REQUIREMENTS. SEE FIXTURE 30/3/ - /3R DISCONNECT SWITCH - 30/3/ - /3R INDICATES 30A, 3 POLE, NON FUSE, NEMA TYPE AS REQUIRED T E L E / DATA SYMBOLS LEGEND SCHEDULE LJ ® - EQUIPMENT (ID) NUMBER FOR OWNER PROVIDED EQUIPMENT. REFER TO OWNER'S EQUIPMENT SEE FIXTURE CB 0­1130/3 CIRCUIT BREAKER DISCONNECT SWITCH - THERMAL MAGNETIC CB IN NEMA 1 ENCLOSURE; AS REQUIRED SYMBOL DESCRIPTION SCHEDULE AMPS/POLES AS INDICATED 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR TIME TELEPHONE OUTLETS . SEE FIXTURE 92 MOTOR STARTER FVNR UNO; NUMBER INDICATES NEMA SIZE AS REQUIRED SCHEDULE STUB 314" C. ABOVE ACCESSIBLE (FLUNG FROM OUTLET BOX SEE FIXTURE COMBINATION MOTOR CONTROLLER /DISCONNECT SWITCH d 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR ONE DATA OUTLET. STUB 3/4" SCHEDULE CB 9J 30/3 AMPS/POLES AS INDICATED. MOTOR STARTER AS PER MANUFACTURER'S RECOMMENDATIONS AS REQUIRED Q ABOVE ACCESSIBLE CEIUNG FROM OUTLET BOX. G 4" SQUARE BOX WITH SINGE GANG ADAPTER FOR TWO TELEPHONE OUTLETS AND SEE FIXTURE SCHEDULE $m MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD AND PILOT LIGHT AS REQUIRED ONE DATA OUTLET. STUB 3/4" C. ABOVE ACCESSIBLE CEIUNG FROM OUTLET BOX. 4" SQUARE BOX WITH SINGE GANG ADAPTER FOR TWO TELEPHONE OUTLETS AND TWO SEE FIXTURE MOTOR - DATA OUTLETS . STUB 3/4' C. ABOVE ACCESSIBLE CEILING FROM OUTLET BOX. SCHEDULE /W 4" SQUARE BOX WITH SINGE GANG ADAPTER FOR ONE WALL MOUNTED TELEPHONE OUTLE . SEE FIXTURE EXISTING PANELBOARD _ STUB 3/4' C. ABOVE ACCESSIBLE CEIUNG FROM OUTLET BOX SCHEDULE 4" SQUARE BOX WITH SINGLE GANG ADAPTER FOR CATV/MATV SYSTEM OUTLET - 48' AFF 208/120V PANELBOARD _ STUB 3/4 C. ABOVE ACCESSIBLE CEIUNG FROM OUTLET BOX WIRING DEVICE NOTE 48' AFF �■ 480/277v PANELBOARD - ALL NEW WIRING DEVICES AND ASSOCIATED DEVICE PLATES ON NORMAL POWER SHALL MATCH COLOR OF EXISTING NORMAL 48' AFF D DISTRUBUTTON PANELBOARD _ POWER WIRING DEVICES. THROUGHOUT THE BUILDING. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS. 48' AFF -0 EQUIPMENT CONNECTION - 48" AFF CIRCUIT CONDUCTOR INDICATION (NEUTRAL, PHASE, EQUIPMENT GROUND, ISOLATED - GROUND, SWITCH LEG) DEVICE W HOMERUN: CIRCUIT HOMERUN TO PANELBOARD 2f12, 1 f12G, 3/47C. 20A 1P CO UNO AFF 48" DEVICE W/O HOMERUN: REFER TO FEEDER AND PANEL SCHEDULES FOR WIRE, BREAKER SIZE AND - NUMBER OF POLES UNO. EACH 120V CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL 48" AM - - - - - CONDUIT INSTALLED IN CEIUNG SPACE OF FLOOR BELOW - BID NOTE 48' AFF X,X,X THREE SINGLE POLE DEVICE CIRCUIT NUMBERS - THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO. VISIT THE SITE AND 48" AFF X/X /X MULTI -POLE DEVICE CIRCUIT NUMBERS _ ASCERTAIN THE EXISTING CONDITIONS.. REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE EMERGENCY POWER OFF BUTTON. WALL MOUNTED - STUB 3/4" C. ABOVE ACCESSIBLE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING PO 48" AFF �-D E CEIUNG FROM OUTLET BOX AS REQUIRED INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE 48' AFF DHTA DECONTAMINATION HOLDING TANK ALARM - PANEL PROVIDED UNDER OTHER DIVISION AS REQUIRED EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK. CEIUNG MOUNTED GAP GENERATOR ANNUNCIATOR PANEL AS REQUIRED UNO 48' AFF ATSA AUTOMATIC TRANSFER SWITCH ANNUNCIATOR PANEL AS REQUIRED 48' AFF GROUND BAR - ElSTEP -DOWN TRANSFORMER - TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR DEVICE - MOTORIZED DAMPER - COORDINATE BETWEEN TRADES - - Fv-A--Q HVAC CONTROL PANEL - PANEL PROVIDED UNDER OTHER DIVISION - 48" AFF 48" AFF 48" AFF MTG. HT UNO SEE NOTE 1 15" AFF 15' AFF 15' AFF 15" AFF 48" AFF 15" AFF FOR SYSTEM FUNCTIONALITY, COMPLIANCE WITH NATIONAL AND LOCAL CODES OR APPROVAL OF THE AHJ, DWG No. 412469.000 SCALE FIRE ALARM SYSTEM Project Y EO.01 y ". 2121 Ponce de Leon dould'lard THESE DRAWINGS ARE INTENDED TO SHOW GENERAL GUIDELINES FOR THE PLACEMENT OF FIRE ALARM AFC ABOVE FINISHED COUNTER ti'' suite 350 DEVICES AS THEY RELATE TO OTHER (NON -FIRE ALARM) SYSTEMS AND FOR PERMITTING PURPOSES. THE 1/8111 = 1' -0' ATS AUTOMATIC TRANSFER SWITCH Coral Gables, FL 33134 FINAL FIRE ALARM PLANS TO BE SUBMITTED FOR AHJ APPROVAL SHALL BE PRODUCED AND SEALED BY A BFC BELOW FINISHED CEIUNG NC (N.C.) NORMALLY CLOSED phone; 305.569.1692 fax: 305,569.1693 NICET LEVEL III CERTIFIED DESIGNER; REFER TO THE SPECIFICATIONS FOR FURTHER REQUIREMENTS. THE Professions nsulting Engineers C CONDUIT DESIGNER SHALL PROVIDE ALL DEVICES SHOWN ON THESE DRAWINGS AND ANY ADDITIONAL DEVICES OR Austin • Dallas • Denver . Houston • Kanscs Cite . 'Miami COMPONENTS REQUIRED FOR A COMPLETE SYSTEM. IF OTHER DEVICES ARE ANTICIPATED TO BE REQUIRED Nash isle .Phoenix •Richmond • Wishincton D.C. CKT CIRCUIT NO (N.O.) NORMALLY OPEN Ea00007s5a FOR SYSTEM FUNCTIONALITY, COMPLIANCE WITH NATIONAL AND LOCAL CODES OR APPROVAL OF THE AHJ, DWG No. THE CONTRACTOR SHALL QUALIFY THEIR BID AND SHALL PROVIDE AN ADD ALTERNATE PRICE MAKING NOTE SCALE OF THE SPECIFIC ANTICIPATED ADDITIONAL REQUIREMENTS GENERAL INFORMATION - ELECTRICAL BUILDING CODE: 2007 FBC WITH 2008 AND 2009 REVISIONS EO.01 ELECTRICAL CODE: 2008 NFPA 70 (NEC) NTS ELECTRCIAL ABBREVIATIONS AFC ABOVE FINISHED COUNTER MLO MAIN LUGS ONLY AFF ABOVE FINISHED FLOOR MTD MOUNT OR MOUNTED 1/8111 = 1' -0' ATS AUTOMATIC TRANSFER SWITCH N NEW DEVICE NTS BFC BELOW FINISHED CEIUNG NC (N.C.) NORMALLY CLOSED NTS BOF BOTTOM OF FIXTURE NEC NATIONAL ELECTRIC CODE NTS C CONDUIT NF NONFUSED z�Q CB,C /B OR CIRCUIT BREAKER NIC NOT IN CONTRACT lid CKT BKR NIL NIGHT LIGHT CKT CIRCUIT NO (N.O.) NORMALLY OPEN CCTV CLOSED CIRCUIT T.V. PB PULL BOX CLG CEIUNG PNL PANEL CR CRITICAL (EMERGENCY SYSTEM) PWR POWER CUH CABINET HEATER R RELOCATED DEVICE EC EMPTY CONDUIT RCPT(S) OR RECEPTACLE(S) ELEC ELECTRIC RECEPT E EMERGENCY RF RETURN AIR FAN EMS ENERGY MANAGEMENT SYSTEM SEF SMOKE EXHAUST FAN EP EXPLOSION PROOF SF SUPPLY AIR FAN EWC ELECTRIC WATER COOLER SO (S.O.) SPACE ONLY EX EXISTING SP SPARE F FUSE ST (S.T.) SHUNT TRIP FA FIRE ALARM SW SWITCH FACP, FAP FIRE ALARM CONTROL PANEL TEL TELEPHONE FCU FAN COIL UNIT TF TRANSFER FAN FIXT FIXTURE TP TAMPER PROOF FLR FLOOR TV TELEVISION FLUOR FLUORESCENT TVSS TRANSIENT VOLTAGE SURGE FTP, FTS FAN TERMINAL UNIT SUPPRESSION FTU FAN TERMINAL UNIT OF UNDERFLOOR FUT FUTURE UG UNDERGROUND G, GND GROUND (EQUIPMENT) UH UNIT HEATER GEF GENERAL EXHAUST FAN UNO (U.N.O.) UNLESS NOTED OR INDICATED GEN GENERATOR OTHERWISE WPWIU WEATHERPROOF WHILE -IN -USE V VOLTAGE GFCI, GFI GROUND FAULT CIRCUIT INTERRUPTER VFD VARIABLE FREQUENCY DRIVE HP HORSE POWER VP VAPOR PROOF HV HIGH VOLTAGE VV VARIABLE VOLUME UNIT HWAT HEAT TRACE W WIRE IC INTERRUPTING CAPACITY W/ WITH ICAND INCANDESCENT WG WIRE GUARD IG ISOLATED GROUND WP WEATHER PROOF JB JUNCTION BOX WT WATER TIGHT KEF KITCHEN EXHAUST FAN XFMR TRANSFORMER LTG LIGHTING +xx MOUNTING HEIGHT IN INCHES. AFF LTS LIGHTS UNO. EXP EXPLOSION PROOF LV LOW VOLTAGE MATV MASTER ANTENNA MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANEL MH MANHOLE GENERAL NOTATIONS AND MOUNTING HEIGHTS NOTE 1: ALL MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE, UNLESS OTHERWISE INDICATED. A) 48" AFF INDICATES TO TOP OF DEVICE; B) 15" AFF INDICATES TO BOTTOM OF DEVICE; C) 60" AFF INDICATES TO BOTTOM OF DEVICE; D) 80' AFF INDICATES TO BOTTOM OF DEVICE; NOTE 2: CONFIRM ALL BACKBOX SIZE WITH VENDOR SHOP DRAWINGS PRIOR TO ELECTRICAL ROUGH -IN. 0 - LEGEND NOTES: DENOTES 'SEE LEGEND NOTE NO. 2" -© - EQUIPMENT (ID) NUMBER FOR FOOD SERVICE EQUIPMENT. REFER TO FOOD SERVICE DOCUMENTS FOR DEFINITION AND REQUIREMENTS. DENOTES: REFERENCE DETAIL 02 ON DRAWING (SHEET) E7.01 E50.201/E7.01- - DENOTES: REFERENCE ENLARGED DETAIL PLAN 02 ON DRAWING (SHEET) E5.01 LJ ® - EQUIPMENT (ID) NUMBER FOR OWNER PROVIDED EQUIPMENT. REFER TO OWNER'S EQUIPMENT BOOK / FF&E DOCUMENTS FOR DEFINITION AND REQUIREMENTS. NOTE: 1. CONTRACTOR SHALL REFER TO MECHANICAL/ELECTRICAL SYSTEM COORDINATION SCHEDULE FOR CONTRACTOR RESPONSIBILITY MATRIX CODES AND STANDARDS THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO: 1. STATE OF FLORIDA 2. CITY OF MIAMI 3. LIFE SAFETY CODE - NFPA 101 (2009) 4. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) 5. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 7. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 9. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 10. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 11. NATIONAL ELECTRICAL SAFETY CODE (NBS Hanctiook 81) 12. REQUIREMENTS OF LOCAL UTILITY COMPANY 13. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2007) 14. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005) 15. THE STATE FIRE PREVENTION CONE, 4A60 (2001) 16. BUILDING CODE: FLORIDA BUILDING CONE (2010) 17. GUIDELINES (2010) 18. NFPA 110 (2005) 19. NFPA 780 STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2011) ELECTRICAL SHEET LIST DWG No. DRAWING TITLE SCALE EO.00 GENERAL INFORMATION - ELECTRICAL NTS EO.01 GENERAL INFORMATION - ELECTRICAL NTS ED2.01 PARTIAL SECOND FLOOR PLAN - ELECTRICAL 1/8w = 1' -0' E2.01 PARTIAL SECOND FLOOR PLAN - ELECTRICAL 1/8111 = 1' -0' E3.00 PARTIAL ELECTRICAL ONE -LINE DIAGRAM NTS E4.00 ELECTRICAL DETAILS AND STUDIES NTS E5.00 ELECTRICAL SCHEDULES NTS 0 0 !� i z " CIO; w V 0 �w <x r� W � �z V � x0 w z A T, '.{ c a 0 to Q V d F O � � w) wi 2 rz/i N Q zAz Z .� � W � z�Q lid Q V vi ' =7 1 1=1i DRAWL RR CXKCKIU LEN DATL 1 -23 -2012 ICJ" AS 111� ni ®e���� "Safi l!94(d ts�Ojif. Tc Q :r � ya LEA RIC t E' GIN ER Sheet No. E0.00 I JM * 201131 I