13-185-035;;"�. 'R V V %*jL;ALt: N 15 GENERAL NOTES: 1. SPACE SENSORS LOCATED AS PER PLANS. 2. FIRE ALARM CONTACTS TO BE PROVIDED BY ELECTRICAL CONTRACTOR. WIRE FROM LOCAL FIRE ALARM CONTACTS TO THE MOTOR FOR FAN SHUTDOWN. 3. CONTROLLERS SHALL HAVE INTEGRATED HOA SWATCHES. 4. SMOKE DETECTOR INSTALLED BY FIRE ALARM CONTRACTOR. R �•_ 2 —POS. N.C. RA PRE — FILTER BANK H N L CHILLED WATER CONTROL VALVE MOD. N.C. CHWR N.C. CHWS E — VFD NETWORK INTERFACE ALL POINTS SHALL BE ACCESSIBLE THROUGH THE DDC CONTROL SYSTEM. PROVIDE THE FOLLOWING AS HARDWIRED CONTROLS/VFD INTERFACE DO START —STOP ®0 SPEED CONTROL (X FULL) DI GENERAL VFD ALARM VFD SAF C C _ --- SUPPLY AIR FAN (SAF) AFS -1 TO FIRE ALARM SYSTEM TDISCHARGE AIR TEMPERATURE ol AHU CONTROL DIAGRAM SCALE: NTS CONTROLS SHALL BE TIED TO CANCER CENTER CONTROLS: BASIS OF DESIGN: ADVANCED CONTROLS. CONSTANT VOLUME AIR HANDLING UNIT: 1. CONNECT AHU CONTROLLER REMOTELY TO THE EXISTING CONTROLS SYSTEM IN THE CANCER CENTER. BASIS OF DESIGN: ADVANCED CONTROLS. 2. START /STOP: WHEN THE AHU IS INDEXED TO OPERATE BY AUTOMATIC OR OPERATOR, THE ASSOCIATED EXHAUST FANS SHALL START. AFTER AN ADJUSTABLE TIME DELAY, THE AHU SUPPLY FAN SHALL START THROUGH THE VFD AND ALL SAFETIES AND INTERLOCKS SHALL OPERATE THROUGH THE AUTOMATIC VFD AND BYPASS CONTACTOR. 3. TEMPERATURE CONTROL: DDC CONTROLLER SHALL MODULATE NC CHILLED WATER VALVE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE (ADJUSTABLE). 4. ALARMING: ALARM THE FOLLOWING POINTS: FAN FAILURE, STATIC PRESSURE FAILURE, MINIMUM OUTSIDE AIR FLOW FAILURE, LOW LIMIT SWITCH, FILTER STATIC PRESSURE LIMIT (DIRTY FILTER), SUPPLY AIR TEMPERATURE HIGH LIMIT ALARM (WITH FAN OPERATING). 5. HEATING COIL: UPON A CALL FOR HEATING, THE CHILLED WATER VALVE SHALL BE CLOSED, THE VFD SHALL MODULE THE FAN TO THE MINIMUM OUTSIDE AIR CFM SETPOINT AND THE ELECTRIC HEATING COIL SHALL BE ENERGIZED. 6. EMERGENCY SHUTDOWN /SMOKE DETECTION: THE UNIT SHALL SHUT DOWN UPON RECEIVING AN EMERGENCY SHUTDOWN /SMOKE DETECTION SIGNAL 7. AIRFLOW STATION: THE CONTROLLER SHALL MEASURE THE SUPPLY AIRFLOW AND SEND A SIGNAL TO THE UNIT CONTROLLER WHICH MODULATE THE SUPPLY AIR FAN VFD SPEED TO MAINTAIN THE SUPPLY AIR FLOW SETPONT. & OA DAMPER: THE OA DAMPER SHALL OPEN DURING OCCUPIED MODE AND CLOSE DURING UNOCCUPIED MODE. EF EA /O, I EF /SF r___ > EA /OA DI Fan status STR D❑ Fan start/stop DFANS CONTROL DIAGRAM. Z SCALE: NTS SEQUENCE OF OPERATION: EXHAUST FAN 1. RUN CONDITIONS, INTERLOCKED: THE EF SHALL RUN WHENEVER ITS ASSOCIATED AHU SUPPLY FAN IS RUNNING AND OA DAMPER IS OPEN UNLESS SHUTDOWN ON SAFETIES. 2. FAN STATUS: THE CONTROLLER SHALL MONITOR FAN STATUS. ALARMS SHALL BE PROVIDED FOR FAN FAILURE (COMMANDED ON BUT THE STATUS IS OFF). MAKE —UP AIR FAN (MUA) 1. RUN CONDITIONS, INTERLOCKED: THE SF SHALL RUN WHENEVER THE KITCHEN HOOD IS ACTIVATED. INTERLOCK WITH HOOD CONTROLS AND THE HOOD EXHAUST FAN. 2. FAN STATUS: THE CONTROLLER SHALL MONITOR FAN STATUS. ALARMS SHALL BE PROVIDED FOR FAN FAILURE (COMMANDED ON BUT THE STATUS IS OFF). Project #,412469.000 •; ^': 2121 Ponce de l eon Boulevard Suite 350 Coral Gables, FL 33131 F; phone: 305.569.1692 fax: 305.569.1693 Professional Consulting Engineers Austin . Dallas - Denver . Houston . KGnscs CiLy • Miami Nashville . Phoenix . Richmond . W-ish+ngtnn D.C. EB00007658 SA SPACE TEMPERATURE TRANSMITTER —1 AI ;k� 'G D D Kn M F' z< . V 0 <x 0-i� a�w� �z V � x 0 w z H a. O w I V Q V�� 0 V) 0 a z 0 V V z V w DRAWK RR OINK Dr LEN DATE, 1-23 -2012 ECAlh All SH� -- P D W2 'T, cl o tla� + ..�MECA t9INEER g'•. X487 f7 .. u... v at't° C"""7 °sJ� "[1Ekiw M9.01 I PB * 201131 1