13-185-033OUTSIDE AIR CALCULATIONS ABASED ON
SHRAE 62.1 -2004
AHU
OCCUPANCY
CATEGORY
AREA
OCCUPANT
DENSITY
OCCUPANTS
COMBINED
OA RATE
AREA
OA RATE
OA
REQUIRED
OA
PROVIDED
RPM
DRIVE
H.P.
RPM
VOLT/PH/HZ
STARTER
EXISTING TO BE REMOVED
AHU -18
(KITCHEN)
3100
DINING
DINING
1464
-
54
7.5
0.18
668
700
TOTAL AHU -19
-
700
-
( 0 )
CENTRIFUGAL
2424
NO
WHITE
N/A
NOTE 1
TITUS / 350FL
KITCHEN
KITCHEN
1274
-
10
20
-
200
630
TOTAL AHU -18 (SEE AIR BALANCE CALCULATIONS FOR TOTAL OA REQUIRED)
-
630
AIR BALANCE CALCULATIONS
MARK
SUPPLY
RETURN
OUTSIDE
EXHAUST
TRANSFER
MAKE -UP
PRESSURIZATION
TYPE
RPM
DRIVE
H.P.
RPM
VOLT/PH/HZ
STARTER
EXISTING TO BE REMOVED
AHU -18
(KITCHEN)
3100
2635
465
-1940
75
1400
SEE NOTE 2
AHU -19
(DINING)
2350
1650
700
-625
-75
-
( 0 )
CENTRIFUGAL
2424
NO
WHITE
N/A
NOTE 1
TITUS / 350FL
ALUMINUM RETURN GRILLE/2,3,4,5,6,7,8
NOTES:
1. KITCHEN IS NEGATIVELY PRESSURIZED IN RELATIONSHIP TO ADJACENT AREAS. KITCHEN IS NEUTRAL (0)
WITH AIR TRANSFERRED IN FROM ADJACENT SPACES.
FAN SCHEDULE
DESIG.
SERVES
CFM
EXT.
S.P.
FAN DATA
ELECTRICAL MOTOR DATA
MANUF/MODEL NO.
REMARKS/NOTES
TYPE
RPM
DRIVE
H.P.
RPM
VOLT/PH/HZ
STARTER
EXISTING TO BE REMOVED
S1
24x24
NO
WHITE
4 -WAY
NOTE 1
TITUS / TDC -AA
ALUMINUM LOUVERED SUPPLY DIFFUSER /2,3,4,5,6,8
S2
24x24
NO
WHITE
2 -WAY
NOTE 1
TITUS / TDC -AA
ALUMINUM LOUVERED SUPPLY DIFFUSER /2,3,4,5,6,8
CENTRIFUGAL
2424
NO
WHITE
N/A
NOTE 1
TITUS / 350FL
ALUMINUM RETURN GRILLE/2,3,4,5,6,7,8
E1
MUA -1
KITCHEN HOOD
2520
1.0
SQUARE
2150
BELT
1.5
-
208/3/60
YES
COOK 135 -SQNB
SEE NOTES 1,2,3,4
Y
N
EXISTING TO REMAIN
INLINE
1614
1805
TYPE COIL
CHW
CHW
CFM
2350
3100
CENTRIFUGAL
AX. AIR P.
500 /0.66
500/1.00
TOTAL /SENS
97.5/57.1
EF -K1
GENERAL DINING
625
0.5
SQUARE
1871
BELT
1/4
-
120/1 /60
YES
COOK 80 -SQNB
SEE NOTES 1,2,3,4,5
INLINE
LAT F DB/WB
55.8/55.6
55.9/55.0
z
EWT 'F/LWT F
45/55
ROOF MTD.
8
EF -14
KITCHEN HOOD
3150
2.0
CENTRIFUGAL
1425
BELT
2.0
-
208/3/60
YES
COOK 180 -VCR
SEE NOTES 1,2,3,4,6,7,8
[MIN- ROWS/MAX. FINS PER FOOT
6/11
6/11
UPBLAST
TYPE COIL
NONE
NONE
CFM
NOTES:
O1 INTEGRAL STARTER/ FUSED DISCONNECT.
O2 BACK DRAFT DAMPER.
O3 BIRD SCREEN.
O4 INTERLOCK FANS AS FOLLOWS (COORDINATE WITH CONTROLS):
INTERLOCK EF -14 AND MUA -1 WITH KITCHEN HOOD.
INTERLOCK EF -K1 WITH AHU -K1.
O5 PROVIDE FILTERED INTAKE (30% FILTER) AND MAGNAHELIC GAUGE ACROSS FILTER BANK.
O PROVIDE GREASE ,DRAIN, HINGED CONNECTION AND HOLD OPEN RETAINER.
O7 FAN SHALL BE MIAMI -DADE APPROVED, MARKED WITH NOA NUMBER.
OS EF -14 SHALL REMAIN OPERATIONAL DURING FIRE ALARM.
AIR DEVICE SCHEDULE
DESIG.
FRAME SIZE
OBD
FINISH
THROW
NECK SIZE
MANUFACTURER /MODEL NO.
REMARKS/NOTES
331 -450 CFM
14 "0
451 -600 CFM
RETURN
CFM
OUTSIDE
AIR CFM
1395
0
EXISTING TO BE REMOVED
S1
24x24
NO
WHITE
4 -WAY
NOTE 1
TITUS / TDC -AA
ALUMINUM LOUVERED SUPPLY DIFFUSER /2,3,4,5,6,8
S2
24x24
NO
WHITE
2 -WAY
NOTE 1
TITUS / TDC -AA
ALUMINUM LOUVERED SUPPLY DIFFUSER /2,3,4,5,6,8
R1
2424
NO
WHITE
N/A
NOTE 1
TITUS / 350FL
ALUMINUM RETURN GRILLE/2,3,4,5,6,7,8
E1
2424
NO
WHITE
N/A
N/A
TITUS / 350FL
ALUMINUM RETURN GRILLE/2,3,4,5,6,7.8
►• 1
NECK*
AIRFLOW
6 "0
0 -100 CFM
8 00
101 -200 CFM
10 "0
201 -330 CFM
12 "0
331 -450 CFM
14 "0
451 -600 CFM
*AND /OR DUCT RUNOUT
2. DIFFUSER RUNOUT SIZE SHALL BE DIFFUSER NECK SIZE, UNLESS OTHERWISE
NOTED ON PLANS
3. PROVIDE LAY -IN MOUNT HARDWARE IN ALL SUSPENDED CEILING SYSTEMS
4. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOC. OF DIFFUSERS
5. PROVIDE SELECTION BASED ON I A MAXIMUM RADIATED NOISE OF NC -25
6• PROVIDE DIFFUSERS, GRILLES, AND REGISTERS MANUFACTURED FROM ALUMINUM
7. 35 DEGREE BLADES, 0.50" SPACING.
8. OPPOSED BLADE VOLUME DAMPERS AT BRANCH NECK AS SHOWN ON PLANS
EXISTING AHU SCHEDULE
DESIG./
SERVES
UNIT TYPE
EXISTING CFM
NEW CFM
PRE
FILT.
FINAL
FI LT.
MANUFACTURER /MODEL NO.
SUPPLY
CFM
RETURN
CFM
OUTSIDE
AIR CFM
SUPPLY
CFM
RETURN
CFM
OUTSIDE
AIR CFM
1395
0
EXISTING TO BE REMOVED
MUA -2
ESP / TSP ( "WG)
2.0/3.0
KITCHEN HOOD
0
0
EXISTING TO BE REMOVED
AHU -18
KITCHEN
HORIZONTAL
1680
1680
0
0
0
0
Y
N
EXISTING TO BE REMOVED
AHU -19
DINING
HORIZONTAL
1615
1615
0
0
0
0
Y
N
EXISTING TO BE REMOVED
AHU -14
PHARMACY
HORIZONTAL
1350
1350
0
1200
1200
0
Y
N
EXISTING TO REMAIN
NOTES:
1. CONTRACTOR SHALL REBALANCE EXISTING UNITS AS REQUIRED.
EXISTING EF SCHEDULE
DESIG./
EXISTING DESIGN
NEW DESIGN
NOTES:
SERVES
CFM
CFM
MUA -1
KITCHEN HOOD
1395
0
EXISTING TO BE REMOVED
MUA -2
ESP / TSP ( "WG)
2.0/3.0
KITCHEN HOOD
0
0
EXISTING TO BE REMOVED
EF -14
5
11KITCHEN HOOD
1940
0
EXISTING TO REPLACED
AIR HANDLING UNIT SCHEDULE
MARK
AHU -19
AHU -18
DINING
KITCHEN
SERVES
DESIGN CFM
2350
3100
ESP / TSP ( "WG)
2.0/3.0
2.0/3.0
zz
FAN MOTOR HP (MIN)
5
5
}
POWER SUPPLY (VOLTS /PHASE)
208/3
208/3
J
MCA/MOCP
16.2/25
16.2/25
0
FAN WHEEL TYPE
FORWARD CURVE
FORWARD CURVE
DRIVE
BELT
BELT
FAN RPM
1614
1805
TYPE COIL
CHW
CHW
CFM
2350
3100
AX. AIR P.
500 /0.66
500/1.00
TOTAL /SENS
97.5/57.1
106.2/67.9
EAT F DB/WB
78.1/68.6
76.1/66.4
LAT F DB/WB
55.8/55.6
55.9/55.0
z
EWT 'F/LWT F
45/55
45/55
8
S
GPM
19.5
21.2
v
WATER PD (FT.) (MAX)
2.0
2.1
[MIN- ROWS/MAX. FINS PER FOOT
6/11
6/11
TYPE COIL
NONE
NONE
CFM
FACE
MAX, MAX. AIR P.D. G
TOTAL CAPACITY
-
-
a
EAT F DB/WB
-
-
LAT F DB/WB
-
-
v
EWT F/LWT F
-
-
z
GPM (MAXIMUM)
-
-
=
WATER PD (FT.) (MAX)
-
-
MIN. ROWS /MAX. FINS PER FOOT
-
-
DESIGN OA CFM
700
630
TYPE (PANEL)
2" FLAT FILTER
2" FIAT FILTER
o
EFFICIENCY (X) ( ASHRAE 52)
30% MERV 8
30X MERV 8
Of Of
MAX. VELOCITY (FPM)
500
500
P.D. (CLEAN /DIRTY) (INCHES W.G.)
0.25/0.50
0.25/0.50
MANUFACTURER/MODEL NO.
CARRIER /39MO6
CARRIER /39MO6
WEIGHT (LBS.) (INCLUDING PLENUMS)
1400
1400
UNIT MAXIMUM DIMENSIONS (INCHES)
LENGTH x WIDTH x HEIGHT
54x46x70
54x46x70
NOTES
ALL
ALL
GENERAL NOTES (AHU-S):
A. ESP EQUALS SP LOSSES OF DUCTS PLUS DIRTY FILTERS MINUS
CLEAN FILTERS. ISP EQUALS AHU SP LOSS WITH CLEAN FILTERS.
TSP EQUALS ESP + ISP.
B. FAN MOTOR NAMEPLATE HORSEPOWER SHALL NOT BE EXCEEDED
AT SCHEDULED CFM AND TSP.
C. IF ANY MANUFACTURER'S COOLING COIL PROMOTES MOISTURE
CARRYOVER AT THE ALLOWABLE MAXIMUM FACE VELOCITY
THEY SHALL OVERSIZE COOLING COIL FACE AREA TO
PREVENT MOISTURE CARRYOVER AT THESE CONDITIONS.
D. COILS: NO COATINGS
E. COOLING COIL SENSIBLE HEAT RATIO TOLERANCE EQUALS
PLUS OR MINUS 0.03.
EXAMPLE: CSHR - 0.79
MINIMUM = 0.76
MAXIMUM = 0.82
F. 1/2" O.D. TUBES
G. FILTERS SHALL BE FRONT LOAD TYPE WITH SUPPORT ON ALL
FOUR SIDES.
H. EXCEPT WHERE INDICATED OTHERWISE, ACCESS DOORS SHALL BE MINIMUM 24"
WIDTH. FOR THE FAN SECTION, THE ACCESS DOOR SHALL BE SUITABLE SIZE TO
ALLOW FOR REMOVAL OF EACH FAN MODULE ASSEMBLY.
I. EXTEND COOLING COIL PIPING TO EXTERIOR OF UNIT IN FACTORY.
NOTES AHU SCHEDULE:
1. VERTICAL DRAW -THRU.
2. DOUBLE WALL CONSTRUCTION; R -13
3. INTERNALLY ISOLATED FAN, DRIVE, AND MOTOR.
4. SINGLE POINT POWER CONNECTION WITH REDUNDANT DRIVE PACKAGE.
5, AHU SECTIONS
FILTER SECTION
CHW COIL SECTION
FAN SECTION
6. OUTSIDE AIRFLOW MEASURING STATION SHALL BE FACTORY MOUNTED.
7. GALVANIZED EXTERIOR PANELS, LEVEL II THERMAL BREAK, 4" TALL BASE RAIL,
& 304 STAINLESS STEEL DRAIN PAN.
9. LEFT SIDE ACCESS AND CONNECTIONS, UPBLAST REAR DISCHARGE.
10. PROVIDE VFD FOR EACH AIR HANDLER.
11. PROVIDE MAGNAHE IC FILTER GAUGE ACROSS EACH FILTER BANK.
Project #;412469.000
"i 2121 Ponce de Leon 3)�Javc.rd
u Suite 350
a Coral Gables, FL 33134
,phone: 305.569.1692
.. fax: 305.569.1693
Professional Consulting Enginee s
Austin . Dallas . Denver . Houston . Kansas Coy . M.an,i
Nashville . Phoenix . Richmond . Washingtc.n D.C.
EB00007658
0
0
en Ln
n
v
V 0
<x
W �
�z
V �
x0
z V �g
w z ��
1
V
IIn
rr " IVAO
Ipil
t
0 �
V
+, �
Q �
0
V)
LLI
A
u
h
u
Z
V
w
DRAV04 RR
CIRCIM LEN
DIAT& 1 -23 -2012
y-
zz
r
T .tl
' MECHANICA NG1NEER 7
_ �ryr`
Sheet No.
M&01
JM f 201131