13-185-029OPEN NIPPLE ABOVE TOP OF DRAIN PAN. C.O. O EVERY CHANGE IN DIRECTION GREATER THAN 450 AND AT MAX. OF 25 FEET INTERVALS. DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE NIPPLE ON THE DRAIN PAN, 1 1/4" MIN. FOR AHU, 1" MIN FOR FCU. C.O. U =8" J = 4" DRAIN PAN u u — PITCH DOWN TOWARD DRAIN, MIN. 1/8" AHU = 8" PER ft. FCU — 2" �— FLOOR CLEANOUT WITH THREADED PLUG PROVIDE DRAIN PIPING FROM EVERY COOLING DRAIN COIL TO NEAREST DRAIN. 8CONDENSATE DRAIN TRAP DETAIL- NO O SCALE O R � 3 S1 O Y � 5 S1 S1 INCREASER AS — REQUIRED (TYP -2) 2 -WAY MOD. VALVE WITH DDC ACTUATOR AND POSITION FEEDBACK UNION (TYP.) -� 3/4" BALL VALVE WITH THREADED HOSE CONNECTION. (TYP. OF 2) S �r O MANUAL AIR VENT VALVES, 3/4" THERMOMETER WELL WITH /— THERMOMETER (TYP) JK C, O S2 �' FULL SIZE COIL DRAIN LINE. O S2 S2 FU LL SIZE COIL VENT LINE COIL 4R PLOW S1 S1 O S2 S2 1 AI0R 1 I r S2 � ,II S2 � O � 1 \ 2 TO FLOOR f S1 DRAIN OS2 1 2" PETES —PLU I / G LOCATED AT FLANGE. S2 AS CLOSE TO COIL CONNECTION AS POSSIBLE. NOTES: 1. COIL SHALL BE PIPED COUNTER FLOW REGARDLESS OF VERTICAL CONNECTION CONFIGURATION. 2. STACKED COILS INDICATED. SINGLE COILS PIPED SIMILARLY. 3. PIPING CONFIGURATION SHALL ALLOW REMOVAL OF EACH COIL SECTION WHILE OTHER SECTION REMAINS CONNECTED. 4. REFER TO SPECIFICATIONS FOR VALVE TYPES, VALVE LEGEND REFER TO VALVE SCHEDULE ON M1.00 PIPE SIZING O COIL SECTION O UNIT S1 —PIPE SIZE AS SHOWN ON PLANS TO SERVE UNIT ISOLATION VALVE ISOLATION VALVE S2 — SAME SIZE AS MANUFACTURER'S COIL CONNECTION. O COIL SECTION BALANCE VALVE AIR HANDLING UNIT nm7CHILLED WATER COIL V I NO SCALE HCA.083103 � SIZE PER RADIUS X RADIUS 2X PLANS L -1.5X X i X+Y Y a —20 DEGREE (MAX)(TYP.) AA - X/Y SPUTTER DAMPER - SUPPLY DUCTS CONICAL TAP r— ROUND DUCT FLUME DAMPER ,T DIRECTION OF AIR FLOW TYPICAL CONICAL TAP TYPICAL TAP 6LOW PRESSURE DUCT DETAILS- NO 0 SCALE FLEXIBLE DUCT SUPPORT DETAIL O 5NO SCALE GALVANIZED SHEET METAL DUCT MIN 26 GAUGE 1" STRAP HANGER 4ANUAL VOLUME DAMPER I \—TURN STRAP HANGER UNDER SHEET METAL SCREW DUCT A MIN OF 1" DUCT SUPPORT DETAIL Q4 NO SCALE NOTE: MINIMUM SHEET METAL GAUGE SHALL BE 26. ALL DUCTWORK REINFORCING SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE. THIRD EDITION 2005. Project #;412469.000 2121 Ponce de Leor; 3Julevard Suite 350 Coral Gables, FL 3313+ phone: 305.569.1692 .. fax: 305.569.1693 Professional Consulting Engineers Austin . Dallas . Denver . Houston - Kansas City . Miami Nashville - Phoenix - Richmond - Washing"'or. D.C. EB00007658 RETURN AIR DUCT SEE PLAN FOR SIZE SHEET METAL PLENUM FULL SIZE OF GRILLE NECK & MINIMUM OF 3" TALL PAINT INSIDE OF PLENUM BLACK LAY —IN T —BAR CEILING BY OTHERS TYPE —I GRILLES 03 EXHAUST /RETURN GRILLE DUCT CONNECTION NO SCALE CONICAL TAP WITH --' Menu lei Vni Mir VII 1 WJ"I\ 02 DIFFUSER CONNECTION DETAIL NO SCALE POWDER ACTUATED FASTENERS NOT ALLOWED SECURE W/ CONCRETE ANCHORS SIZED PER SMACNA (TYP) NDER ACTUATED slENERS NOT .OWED :ADED ROD PER SMACNA (TYP) EET METAL DUCT TYPICAL LARGE DUCT SUPPORT DETAIL NO SCALE NOTE: MINIMUM SHEET METAL GAUGE SHALL BE 26. ALL DUCTWORK REINFORCING SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE. THIRD EDITION 2005. ILA �'"'O 04 � A Z < �" 1 w V 0 LLd WF �z V � x 0 < in x ~ 41 o� F" < N aG � c V 4-0� Q V� 0 (13 �1 W Q V z X V Ya �' =1 DRAWN RR 011CM LEN DiATL 1 -23 -2012 WA ir, AS Alf MECHANICAL E DEER Sheet No. M7.01 �$ * 201131