13-185-026FLOOR PLAN
SCALES 1/8' = 1' -0'
EXISTING KITCHEN HOOD WORK NOTES:
1 PROVIDE A MANUAL ACTUATION DEVICE FOR THE HOOD FIRE SUPPRESSION SYSTEM
LOCATED NEAR EVERY MEANS OF EGRESS AND A MINIMUM OF 10 FEET AND
A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM.
2 VERIFY THAT EXISTING HOOD FIRE SUPPRESSION SYSTEM IS UL300 LISTED.
VERIFY OPERATION OF EXISTING HOOD FIRE SUPPRESSION SYSTEM.
CONTRACTOR SHALL ADVISE OWNER, ARCHITECT AND ENGINEER OF ANY
EXISTING HOOD FIRE SUPPRESSION SYSTEM DEFICIENCIES.
3 VERIFY SHUTDOWN OF GAS SUPPLY TO COOKING EQUIPMENT UPON FIRE ALARM.
VERIFY OPERATION OF SOLENOID VALVES AS REQUIRED. CONTRACTOR SHALL
ADVISE OWNER, ARCHITECT AND ENGINEER OF ANY SYSTEM DEFICIENCIES.
3 UPON FIRE ALARM ACTIVATION, KITCHEN AHU (18) SHALL SHUT DOWN, CONDENSATE
HOOD EXHAUST FAN SHALL SHUT DOWN. KITCHEN HOOD EXHAUST FAN AND
MAKE -UP AIR FAN SHALL REMAIN IN OPERATION.