13-185-026FLOOR PLAN SCALES 1/8' = 1' -0' EXISTING KITCHEN HOOD WORK NOTES: 1 PROVIDE A MANUAL ACTUATION DEVICE FOR THE HOOD FIRE SUPPRESSION SYSTEM LOCATED NEAR EVERY MEANS OF EGRESS AND A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. 2 VERIFY THAT EXISTING HOOD FIRE SUPPRESSION SYSTEM IS UL300 LISTED. VERIFY OPERATION OF EXISTING HOOD FIRE SUPPRESSION SYSTEM. CONTRACTOR SHALL ADVISE OWNER, ARCHITECT AND ENGINEER OF ANY EXISTING HOOD FIRE SUPPRESSION SYSTEM DEFICIENCIES. 3 VERIFY SHUTDOWN OF GAS SUPPLY TO COOKING EQUIPMENT UPON FIRE ALARM. VERIFY OPERATION OF SOLENOID VALVES AS REQUIRED. CONTRACTOR SHALL ADVISE OWNER, ARCHITECT AND ENGINEER OF ANY SYSTEM DEFICIENCIES. 3 UPON FIRE ALARM ACTIVATION, KITCHEN AHU (18) SHALL SHUT DOWN, CONDENSATE HOOD EXHAUST FAN SHALL SHUT DOWN. KITCHEN HOOD EXHAUST FAN AND MAKE -UP AIR FAN SHALL REMAIN IN OPERATION. Project #:412469.000 2121 Ponce de Leon souldyard Suite 350 Coral Gables, FL 3313 phone: 305.569.1692 fax: 305.569.1693 Professional Consulting Engineers Austin • Dallas • Denver . Houston . Kansas City . Mi31Ti Nashville . Phoenix • Richmond . Washington [I.C. EB00007658 ^AHCA COMVENTS 01.04.2013 IA I. ' l� z <" V 0 =w <x 0--i� w� Ciez V 7 � � x 0 Z V �8 X U 0 R < NAn r,N i ELL 0 V .4,Md Q 0 914 Oz o <� < �..�V V) "' �ce z H w � z a PERNrr SU DRAVIN >00< DATL 1 -23 -2012 sCAlirs AS Sheet No. M2.01 JM * 201131