Loading...
13-185-023MECHANICAL SYMBOLS ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE. --- HPS HIGH PRESSURE STEAM -HPR HIGH PRESSURE CONDENSATE RETURN SYMBOL DESCRIPTION - -LPS - -- LOW PRESSURE STEAM q NEW EQUIPMENT DESIGNATION (TOP - EQUIP. ABBREV., BOTTOM - MARK) - -LPR - -- LOW PRESSURE CONDENSATE RETURN -PCR PUMPED CONDENSATE RETURN e NEW DIFFUSER DESIGNATION (TOP - SCHEDULE DESIG., BOTTOM - CFM) GC DOMESTIC COLD WATER 171 NEW EQUIPMENT -- -- DOMESTIC HOT WATER BG DOMESTIC HOT WATER RETURN GSF EXISTING EQUIPMENT NEW DUCT CD SANITARY WASTE UNE CONDENSATE DRAIN P PUMPED SANITARY UNE CRU EXISTING DUCT - - - VENT UNE - -- i' EXISTING DUCT TO BE REMOVED OR RELOCATED � DIRECTION OF SLOPE CU DIRECTION OF FLOW ® NEW SUPPLY DIFFUSER IF EXPANSION LOOP RA RETURN AIR DO EXISTING SUPPLY DIFFUSER 10 4 GATE VALVE -}- DISCONNECT SWITCH BUTTERFLY VALVE RELIEF AIR EXISTING SUPPLY DIFFUSER TO BE REMOVED OR RELOCATED - BALL VALVE zNEW R/A OR EXHAUST GRILLE -- 064 GLOBE VALVE UNIT HEATER TEMPERATURE AND PRESSURE RELIEF VALVE ELECTRIC UNIT HEATER C -18 D -20 EXISTING R/A OR EXHAUST GRILLE C -24 AUTOMATIC 2 -WAY CONTROL VALVE Ic _ J EXISTING R/A OR EXHAUST GRILLE TO BE REMOVED OR RELOCATED EXHAUST FAN AUTOMATIC 3 -WAY CONTROL VALVE WATER HEATER NEW SLOT DIFFUSER SUPPLY FAN PLUG VALVE/BALANCING COCK -- FLEXIBLE DUCT_ EXHAUST AIR SOLENOID VALVE FILTER MIXING BOX EXISTING SLOT DIFFUSER - CHECK VALVE -- - - - EXISTING SLOT DIFFUSER TO BE REMOVED OR RELOCATED CHILLED WATER HYDRAULIC SHOCK ARRESTOR OT THERMOSTAT -or+ VALVE IN VERTICAL T, EXISTING THERMOSTAT TO BE REMOVED OR RELOCATED -- }��- -- UNION THERMOSTATIC R VENT 25,26" E -26 45' PRESSURE TAP W/ VOLUME DAMPER D -26 --a-- VACCUUM BREAKER MA CONICAL TAP WITH VOLUME DAMPER 3p P -TRAP �- CONICAL TAP W/O VOLUME DAMPER 31 -36" FLOOR DRAIN W/ P -TRAP ® SQUARE TO ROUND DUCT TRANSITION Oo HUB DRAIN J MANUAL VOLUME DAMPER --fp FLOOR CLEANOUT OR GRADE CLEANOUT -' FIRE DAMPER ---� I CLEANOUT OR WALL CLEANOUT --' SMOKE DAMPER 55 -60" PETE'S PLUG - -� FIRE /SMOKE DAMPER -}� GAUGE COCK ❑M MOTORIZED DAMPER n THERMOMETER ® BAROMETRIC DAMPER - CHS - CHILLED WATER SUPPLY PIPE If THERMOMETER WELL - CHR - CHILLED WATER RETURN PIPE L -181 STRAINER WITH BLOW -OFF VALVE CS CONDENSER WATER SUPPLY PIPE ---�- F & T STEAM TRAP CR CONDENSER WATER RETURN PIPE -�_ K -1811 I J-1 8H K -181 STEAM BUCKET TRAP RL REFRIGERANT UQUID PIPE CONNECT TO EXISTING RS REFRIGERANT SUCTION PIPE EP ELECTRIC PNEUMATIC SWITCH HS HEATING WATER SUPPLY HR HEATING WATER RETURN CHANICAL BREVIATIONS AC ABOVE CEILING DRAWING TITLE SCALE AFF ABOVE FINISHED FLOOR FCU FAN COIL UNIT AI ANALOG INPUT FPB FAN POWERED BOX AO ANALOG OUTPUT FPI FINS PER INCH BFC BELOW FINISHED CEILING GC GENERAL CONTRACTOR BF BELOW FLOOR, BLIND FLANGE GEF GENERAL EXHAUST FAN BG BELOW GRADE GSF GENERAL SUPPLY FAN BV BUTTERFLY VALVE MVD MANUAL VOLUME DAMPER CRU COMPUTER ROOM UNIT N NEW CRU CONDENSATE RETURN UNIT OBD OPPOSED BLADE DAMPER CU CONDENSING UNIT R RELOCATED DI DIGITAL INPUT RA RETURN AIR DO DIGITAL OUTPUT RCA RECIRCULATED (RETURN) AIR DS DISCONNECT SWITCH RLA RELIEF AIR E EXISTING SA SUPPLY AIR EDH ELECTRIC DUCT HEATER UH UNIT HEATER EUH ELECTRIC UNIT HEATER C -18 D -20 D -22 C -24 VAV VARIABLE AIR VOLUME EF EXHAUST FAN WH WATER HEATER SF SUPPLY FAN NIP WATER -SOURCE HEAT PUMP EA EXHAUST AIR FMB FILTER MIXING BOX OA OUTSIDE AIR IN HG INCHES MERCURY (PRESSURE) CHW CHILLED WATER IN WC INCHES WATER COLUMN (PRESSURE) UNO UNLESS NOTED OTHERWISE IBT INVERTED BUCKET TRAP PRV PRESSURE RELIEF VALVE TAY THERMOSTATIC R VENT 25,26" E -26 E -26 D -26 SV SAFETY VALVE MA MIXED AIR 29,30" E -26 LE LAUNDRY EQUIPMENT MECHANICAL SHEET LIST DWG No. DRAWING TITLE SCALE MO.00 GENERAL INFORMATION - MECHANICAL NTS MD2.01 PARTIAL FIRST FLOOR DEMOLITION PLAN - MECHANICAL 1/8 " =1' M2.01 PARTIAL FIRST FLOOR NEW WORK PLAN - MECHANICAL 1/8 " =1' M3.01 PARTIAL FIRST FLOOR PIPING AND CONTROLS - MECHANICAL 1/8 " =1' M7.01 MECHANICAL DETAILS NTS M7.02 MECHANICAL DETAILS NTS M7.03 MECHANICAL DETAILS AND SPECIFICATIONS NTS M8.01 MECHANICAL SCHEDULES NTS M9.01 MECHANICAL CONTROLS NTS M -ICRA PARTIAL FIRST FLOOR - MECHANICAL ICRA PLAN NTS B -26 ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, 9,10'. INFECTION CONTROL NOTE CONTRACTOR SHALL OBTAIN A COPY OF THE INFECTION CONTROL RISK ASSESMENT FOR THIS PROJECT. ALL WORK SHALL BE IN COMPLIANCE WITH THE REPORT. ALL WORK OUTSIDE THE SCOPE OF WORK AREA REQUIRED FOR THIS PROJECT, SHALL BE COORDINATED WITH OWNER AND BE IN COMPLIANCE WITH THE ICRA REPORT AND BE SUPERVISED BY THE OWNER'S REPRESENTATIVE. GENERAL NOTES: A. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE FLORIDA UNIFORM STATEWIDE BUILDING CODE STATE AND LOCAL CODES IBC, AIA, IMC, NEC THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA). AND THE LOCAL AUTHORITIES HAVING JURISDICTION. ALL EQUIPMENT, MATERIALS, CONTROLS, ETC.SHALL BE NEW UNLESS NOTED OTHERWISE AND SHALL MATCH ALL FACILITY STANDARDS OR IF APPROVED BY THE OWNER, BE OF THE SAME QUALITY AS REPRESENTED BY THE SCHEDULED ITEM. B. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, PAY ALL FEES, AND COMPLY WITH ALL NATIONAL, STATE, AND MUNICIPAL LAMS, CODES, AND ORDINANCES RELATING TO BUILDING AND PUBLIC SAFETY. C. CONTRACTOR SHALL FURNISH ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED FOR A COMPLETE WORKING AND COORDINATED SYSTEM. D. COORDINATE THE EXACT LOCATION OF MECHANICAL AND PLUMBING EQUIPMENT NTH THE LOCATIONS OF LIGHT FIXTURES, PIPING, CONDUIT, AND OTHER CONSTRUCTION, TO ALLOW FOR PROPER ACCESS TO SERVICE EQUIPMENT. E. COORDINATE THE LOCATION OF DUCTWORK AND PIPING WITH OTHER TRADES AND PROVIDE OFFSETS IN DUCTWORK AND PIPING AS REQUIRED. F. IT IS THE INTENT OF THESE DOCUMENTS TO ALLOW ALL CEILING CONSTRUCTION AND HEIGHTS TO BE AS SHOWN ON THE ARCHITECTURAL DRAWINGS. COORDINATE THE LOCATION OF DUCTWORK AND PIPING AND PROVIDE OFFSETS IN DUCTWORK AND PIPING AS REQUIRED TO MEET THIS INTENT. G. CONDUIT, PIPING, AND DUCTWORK SHALL BE INDEPENDENTLY SUPPORTED, AND EACH SUPPORT SHALL BE INDEPENDENT OF PARTITION AND CEILING SYSTEM SUPPORTS. WHERE INDEPENDENT SUPPORT IS NOT POSSIBLE AN ENGINEERED SUPPORT SYSTEM SHALL BE UTILIZED. H. ALL WORK SHALL BE SCHEDULED AND PERFORMED IN STRICT COORDINATION WITH ARCHITECTURAL PHASING PLANS AND WITH HOSPITAL SCHEDULES, OCCUPANCIES, AND WORK. I. PROTECT EQUIPMENT AND WORK FROM DAMAGE DURING HANDLING AND INSTALLATION UNTIL COMPLETION OF CONSTRUCTION. J. REMOVE ALL EXCESS MATERIAL AND DEBRIS AND CLEAN ALL EQUIPMENT UPON COMPLETION OF WORK. TOUCH UP WITH PAINT WHERE REQUIRED. K. ALL CONNECTION BETWEEN PIPES OF DISSIMILAR MATERIALS SHALL BE MADE WITH DIELECTRIC UNIONS. L ARCHITECT SHALL HAVE FINAL APPROVAL OF ALL GRILLE, DIFFUSER, AND THERMOSTAT LOCATIONS. M. COORDINATE ALL AIR DEVICE LOCATIONS AND MOUNTING FRAME STYLES WITH LIGHTING PLANS AND ARCHITECTURAL REFLECTED CEILING PLANS. N. COORDINATE ALL WALL MOUNTED DEVICE LOCATIONS WITH ARCHITECTURAL INTERIOR ELEVATIONS. 0. DUCT SIZES ARE NET FREE AREA. P. PROVIDE ROUND DUCTS TO ALL AIR DEVICES UNLESS NOTED OTHERWISE. DUCT SIZE SHALL MATCH AIR DEVICE NECK SIZE OR THE TABLE IN AIR DEVICE SCHEDULE, WHICHEVER IS LARGER FLEXIBLE DUCTS SHALL BE SIZED SIMILARLY. Q. PROVIDE MANUAL VOLUME DAMPER IN EACH AIR DEVICE RUNOUT DUCT AS FAR FROM AIR DEVICE AS POSSIBLE. R. INSTALL SPACE THERMOSTAT ADJACENT TO LATCH SIDE OF DOOR IN SPACE INDICATED. U.N.O. INDICATED LOCATIONS ARE APPROXIMATE. AVOID HEAT PRODUCING EQUIPMENT. FINAL SPACE THERMOSTAT /SENSOR LOCATIONS SHALL BE AS DIRECTED BY THE ARCHITECT. S INSTALL TURNING VANES IN ALL 90 DEGREE SQUARE ELLS IN SUPPLY, RETURN, AND EXHAUST DUCTS. (NONE ALLOWED IN COMBUSTION AIR DUCTS). T. MULTI -BLADE DAMPERS OF ANY TYPE INSTALLED WITHIN 36" OF AN ELL OR OTHER FITTING SHALL BE INSTALLED WITH THE DAMPER BLADE SHAFTS PARALLEL TO THE AIRSTREAM FLOW DIRECTION UPSTREAM OF THE FITTING. U. FIRE, SMOKE, AND FIRE/SMOKE DAMPERS WILL BE REQUIRED AT ALL DUCT PENETRATIONS THRU RATED WALLS. COORDINATE WITH ARCHITECTURAL DRAWINGS. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PRICING ALL FIRE, SMOKE, AND FIRE /SMOKE DAMPERS REQUIRED BY CODE. MECHANICAL CONTRACTOR SHALL REPORT EXISTING FIRE, SMOKE, FIRE /SMOKE DAMPERS TO THE ARCHITECT AND ENGINEER BEFORE PRICING. V. DEMONSTRATE TO OWNER'S REPRESENTATIVE THAT ALL INSTALLED CONTROLS ARE WORKING PROPERLY WITHOUT ERRORS PRIOR TO RELEASING SYSTEM TO OWNER. W. THE CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCNG THE SYSTEMS AS REQUIRED TO OBTAIN INDICATED AIR FLOWS AT EACH PIECE OF EQUIPMENT. X. DUCTWORK FOR HOODS AND GREASE EXHAUST SHALL BE INSTALLED PER NFPA 96. PROVIDE DUCT FIRE WRAP FOR GREASE DUCTS AS REQUIRED. Y. MAINTAIN S -0' CLEAR IN FRONT OF VFD'S AND CONTROL PANELS. Z. DRYWELL SHALL BE 24'0 CONCRETE PIPE, 2 FEET DEEP, FILLED WITH GRAVEL AA. FOR ICRA REQUIREMENTS, REFER TO THIRD PARTY ICRA CONSULTANT DRAWINGS AND DOCUMENTS AND REFER TO ARCHITECTURAL PLANS FOR FURTHER ICRA REQUIREMENTS. COORDINATE NEGATIVE AIR PRESSURE REQUIREMENTS WITH ICRA CONSULTANTS REQUIREMENTS. AB. COORDINATE ALL MECHANICAL PHASING WITH ARCHITECTURAL PHASING PLAN AND LIFE SAFETY PLAN. AC. FLEXIBLE DUCTWORK SHALL HAVE CONTINUOUS METAL INNER LINER ENCASED BY INSULATING MATERIAL WITH OUTER VAPOR JACKET AND SHALL CONFORM TO UL181. AD. ATTACHMENT SYSTEMS FOR THE ROOFTOP EQUIPMENT SHALL BE STRUCTURALLY ENGINEERED TO MEET WIND LOAD REQUIREMENTS OF THE FLORIDA BUILDING CODE. ALL ATTACHMENTS SHALL BE CONNECTED DIRECTLY TO THE UNDERLYING ROOF STRUCTURE OR ROOF SUPPORT STRUCTURE. THE FASTENING SYSTEMS SHALL MEET THE WIND LOAD REQUIREMENTS. ALL ROOFTOP EQUIPMENT SHALL BE MIAMI DADE APPROVED AND SHALL HAVE ACCOMPANYING NOA NUMBER. PROVIDE NOA ACCEPTANCE STICKER ON ALL EQUIPMENT. PROJECT DESIGN CRITERIA LOCATION: CITY /STATE SOUTH MIAMI, FL LATITUDE: DEG. N. LAT. 26.41 LONGITUDE: DEG. W. LONG. 80.06 ELEVATION: FT. ABOVE SEA LEVEL 15.0 ASHRAE SUMMER DESIGN COND111ONS 0.4% DB MWB 92/78 ASHRAE WINTER DESIGN CONDITIONS 99% DB BUILDING SPACE DESIGN TEMPERATURES SUMMER DB WINTER DB 41 72 68 ROOF: U FACTOR - WALL U FACTOR 0.24 SUPPLY AIR TEMPERATURE: DEG. F. DRY BULB 55 GENERAL AE PIPING NOTES 1. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON THIS SHEET IS INTENDED TO PROVIDE THE OVER- ALL ENGINEERING DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS, ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACT. 2. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE GENERAL CONTRACTOR. 3. COORDINATE THE PIPING AND ACCESSORIES SHOWN ON THIS SHEET WITH ALL TRADES. THIS PIPING LAYOUT IS INTENDED TO PROVIDE THE OVERALL ENGINEERING DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS, ETC. REQUIRED BY FIELD COORDINATION OF TRADES. THESE SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACT. 4. REFER TO DETAIL SHEETS FOR MISC. PIPING DETAILS. 5. THE CONTRACTOR SHALL PROVIDE DETAILED AND DIMENSIONED PIPING FABRICATION DRAWINGS FOR APPROVAL BY THE ARCHITECT/ENGINEER. ONE BLUE -UNE SET OF THE APPROVED DRAWINGS SHALL BE KEPT ON -SITE AT ALL TIMES AND ANY CHANGES REQUIRED IN THE FIELD SHALL BE MARKED ON THESE DRAWINGS. AT THE END OF THE PROJECT, ALL CHANGES SHALL BE TRANSFERRED TO A REPRODUCIBLE DRAWING TO BE GIVEN TO THE OWNER FOR "AS- BUILT' DRAWINGS. REPRODUCTIONS OF THIS DRAWING WILL NOT BE CONSIDERED AS PIPING FABRICATION DRAWINGS. 6. ALL PIPING SHALL BE IDENTIFIED IN ACCORDANCE WITH SECTION 23 OF THE SPECIFICATIONS. 7. ALL VALVES AND ACCESSORIES REQUIRING ACCESS THAT IS LOCATED ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE GENERAL CONTRACTOR. 8. ALL FLOOR MOUNTED EQUIPMENT TO BE PROVIDED WITH ACCESS AND SERVICE SPACES AS INDICATED AND PER FMC 306.1. 9. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE DMV, DRAWN - TEMPER COPPER TUBING, WROUGHT- COPPER FITTINGS, AND SOLDERED JOINTS, INSULATED (SEE PLUMBING DRAWINGS) CODES AND STANDARDS THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO: 1. STATE OF FLORIDA 2. CITY OF MIAMI 3. LIFE SAFETY CODE - NFPA 101 (2009) 4. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) 5. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 7. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 9. NA11ONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 10. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 11. NATIONAL ELECTRICAL SAFETY CODE (NBS Handbook 81) 12. REQUIREMENTS OF LOCAL UTILITY COMPANY 13. FLORIDA ADMINISTRATIVE CODE 59A -3, (March 2003) 14. NATIONAL FIRE PROTECTION ASSOCIATION 13 (2007) 14. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2007) 15. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005) 16. NATIONAL FIRE PROTECTION ASSOCIATION 101 (2009) 16. THE STATE FIRE PREVENTION CODE, 4A60 (2001) 17. BUILDING CODE: FLORIDA BUILDING CODE (2010) 1& MECHANICAL CODE: FLORIDA MECHANICAL CODE (2010) 19. PLUMBING CODE: FLORIDA PLUMBING CODE (2010) 1& GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTHCARE FACILITIES (2010) 19. NFPA 110 (2005) 20. FIRE MARSHAU_'S RULE 69A -3.012 F.A.C. ADOPTED DECEMBER 31, 2011 HVAC DESIGN REQUIRES YES NO DUCT SMOKE DETECTOR X Suite 350 FIRE DAMPER(S) X REINFORCEMENT SMOKE DAMPER(S) Professional Consulting Engineers X FIRE RATED ENCLOSURE Nashville . Phoenix X FIRE RATED ROOF/ FLOOR CEILING ASSEMBLY EB00007658 X FIRE STOPPING X 6' SMOKE CONTROL 4' X Project #:412469,000 < r 2121 Ponce de Leon 6ouiev -ird 'u p; Suite 350 NO REINFORCE- MENT REQUIRED Coral Gables, FL 33134 REINFORCEMENT Phone: 305.569.1692 Professional Consulting Engineers fax: 305.569.1693 Austin Dallas • Denver . Houston • Kansas C.y , Miami Nashville . Phoenix . Richmond - Washington O.C. ALL TABLES AND DATA SHOWN REFER TO SMACNA HVAC DUCT CONSTRUCTION STANDARDS 2005 EB00007658 EDITION. ALL DUCT MATERIALS, CONSTRUCTION, AND INSTALLATION TO BE IN ACCORDANCE WITH 10' THOSE STANDARDS. DUCTWORK SEAL CLASS SHALL BE "A'. 6' DIMENSIONS OTHER THAN GAGE ARE IN INCHES. 4' TABLES ALLOW FOR DUCT WEIGHT, 1 LB /SF INSULATION WEIGHT AND 2'12' NORMAL REINFORCEMENT AND TRAPEZE WEIGHT, BUT NO EXTERNAL LOADS. 8 "dn FOR CUSTOMDESIGN OF HANGERS, DESIGNERS MAY CONSULT SMACNA'S NOT REQUIRED "RECTANGULAR INDUSTRIAL DUCT STANDARDS", THE AISI "COLD FORMED B -26 STEEL DESIGN MANUAL" AND THE AISC "STEEL CONSTRUCTION MANUAL ". B -26 STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL. B -26 ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, 9,10'. EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (W) IS OVER 60" THEN P/2 B -24 MAXIMUM IS 1.25 W. B -26 12, 10, OR 8 GA. WIRE STEEL OF BLACK ANNEALED, BRIGHT BASIC, OR B-26 GALVANIZED TYPE. 11, 12" STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED B -22 STEEL; WIRE IS BLACK ANNEALED, BRIGHTBASIC, OR GALVANIZED STEEL. ALL C -24 ARE ALTERNATIVES. C -26 TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS B -26 PLUS ONE LB /SF (4.89 KG /M) INSULATION WEIGHT. IF HEAVIER DUCTS ARE 13, 14 " TO BE INSTALLED, ADJUST HANGER SIZED TO BE WITHIN THEIR LOAD LIMITS; C -20 SEE ALLOWABLE LOADS WITH TABLE 4 -1. HANGER SPACING MAY BE C -22 ADJUSTED BY SPECIAL ANALYSIS. C -26 DESIGNERS: FOR INDUSTRIAL GRADE SUPPORT, INCLUDING SADDLES, SINGLE LOAD TRAPEZE LOADS, LONGER SPANS AND FLANGE JOINT LOADS, SEE SMACNA'S "ROUND INDUSTRIAL DUCT CONSTRUCTION STANDARDS '. 4 < TABLE 1- 7 RECTANGULAR DUCT REINFORCEMENT W.G. STATIC POS.OR NEG. NO REINFORCE- MENT REQUIRED REINFORCEMENT CODE FOR DUCT GAGE NO. REINFOCEMENT SPACING OPTIONS DUCT DIMENSION 10' 8" 6' 5' 4' 3' 2'12' 2` 8 "dn 24 ga. NOT REQUIRED B -26 B -26 B -26 B -26 B -26 B -26 9,10'. 22 ga. B -24 B -26 B -26 B -26 B-26 B -26 11, 12" 20 ga. B -22 B -22 C -24 C -26 C -26 C -26 B -26 B -26 13, 14 " 18 ga. C -20 C -22 C -22 C -24 C -26 C -26 C -26 C -26 15,16" 18 ga. C -18 D -20 D -22 C -24 C-26 C -26 C-26 C -26 17,18" 16 ga. D -18 D -20 D -22 D -24 D -26 C -26 G26 C -26 19, 20 " E -18 E -20 E -1$ E -18 F -18 F -18 G -18 G -18 H -16G G -18 L H -16G H -18G NOT DESIGNED E -22 E -20 F -20 F -20 G -20 G -18 H -18G 1 -16G E -24 E -24 E -22 F -22 F -22 G -22 H -20 1 -18G 1 -18G 1 -16H J-161 D -24 E -24 E -24 E -24 F -24 F -24 G-22 H -20G 1 -18G 1 -18G 1 -16H D -26 C -26 C -26 21,22" D -26 D -26 C -26 23, 24" E -26 D -26 D -26 25,26" E -26 E -26 D -26 27,28" E -26 E -26 D -26 29,30" E -26 E -26 E -26 31 -36" F -24 F -26 E -26 37 -42" G -22 G-24 F -26 43 -48" H -22G -24G G -24 49 -54" 1 -20G _H H -22G H -24G 55 -60" 1 -20G 1 -22G H -24G 61 -72" J -18H 1 -20H 1 -22G 73 -84" K -161 J -181 1 -20H 85 -96" F -24 -181 J -201 97 -108" _K L -181 L -181 109 -120" L -18J L18J 2,. < TABLE 1- 5 RECTANGULAR DUCT REINFORCEMENT W.G. STATIC POS.OR NEG. NO REINFORCE- MENT REQUIRED REINFORCEMENT CODE FOR DUCT GAGE NO, REINFOCEMENT SPACING OPTIONS DUCT DIMENSION 10' 8" 6' 5' 4" 3' 2'/2' 2" 10 "dn 26 ga. � NOT REQUIRED 11, 12" 24 ga. 0 B -26 B -26 B -26 B -26 B -26 B -26 B -26 13,14" 22 ga. N eV B -24 B -26 B -26 B -26 B -26 B -26 B -26 15, 16" 20 ga. C -22 C -24 C -24 C -26 C -26 C -26 B -26 -� B -26 17,18" 20 ga. C -22 C -24 C -24 C -26 C -26 C -26 C -26 B -26 19, 20" 18 ga. C -20 C -22 C -24 C -26 C -26 C -26 C -26 C -26 21,22" 16 ga. D -20 D -22 D -24 D -26 C -26 C -26 C -26 C -26 23,2411 16 ga. E -20 E -22 D -24 D -26 D -26 C -26 C -26 C -26 25,26" E -20 F -18 F -18 G -16 NOT DESIGNED E -22 E -20 F -20 G -18 H -16 1 -16 E -24 E -22 E -22 F -20 G -18 H -18G 1 -16G I -16G D -26 E -24 E -24 F -22 G -20 H -20 H -18 1 -18G J -16H D -26 D -26 E -26 E -24 F -24 G -22 HH -20G H -18G 1 -18G 1 -18G J -18H C -26 C -26 C -26 27, 28" D -26 C -26 C -26 29, 30" D -26 D -26 C -26 31 -36" E -26 D -26 D -26 37-42" E -24 E -26 E -26 43-48" F -24 F -24 E -24 49-54" G-24 F -24 F -24 55 -60" G-22 G -24 F -24 61-72" H -22G H -22G H -24 73-84" 1 -20G 1 -22G 1 -22G 85-96" 1 -18H 1 -20H 1 -22H 97 -108" K -1811 I J-1 8H K -181 1 -18H J -181 109 -120" it Aavl�bnsAM-M .. L� v D z < 9" v V 0 Q•n �z V � x 0 w _z N eV O � Q V o� Q � V 0 0 z 0 MEMO V 0 z z< Pon"x "a oG 2 ' i DRAW% RR CHRCKUh LEN DIAM 1-23 -2012 SEAL ',,, MKHAN16L INE Ra:` b Sheet No. MO-00 I JM 0 201131 I