12-1046R-007SCOPE
INSTALL 4 NEW SIDEWALL SPKRS. BOTTOM OF •
HOSPITAL EXISTING REMAINING i
NO WORK TO BE DO I
SYMBOLS LEGEND GENERAL NOTES
EXISTING PIPE - - - --
EXISTING AREA WITH CONCRETE SLAB CONSTRUCTION CEILING FULLY SPRINKLERED
NEW PIPE SIMPLEXGRINNELL TO ADD NEW FIRE SPRINKLERS ACCORDING TO NEW LAYOUT.
NEW HANGER -- NEW LAYOUT TO BE DESIGNED AS ORDINARY HAZARD GRP II AT THE BOTTOM OF THE ELEVATORS
PIPE TO BE DEMO. WITH A MAXIMUM COVERAGE OF: 130 SQ.FT. PER FIRE SPRINKLER.
NEW. SIDEWALL SPKR. HEAD. N Q PIPING 1" TO 2" TO BE SCH40 AND CI FITTINGS. ALL PIPING 2 1/2- OR LARGER
EXISTING PD. HEAD TO REMAIN E ':;
® - SHALL BE SCH. 10 PIPE WITH GROOVED ENDS AND FITTINGS.
ALL WORK SHALL BE IN ACCORDANCE WITH NFPA -13 (2007).
N
O
S.W. 62 AVE.
RESPONSIBILITY
• • • • •
tIVI1 16
IMPORTANT TO
HYDRAULIC
SG DESCRIPTION OF WORK
OUT X IN
OUT IN
OUT IN
0 OUT IN
1 I 1 11
;• 6- :i11.; .:111
•
• y
HAZARD CLASSIFICATION
.
• .
•
•
•
-,i a•
•
GPM
REVISIONS
�—
!
Y ,
En 1 REVISION DESCRIPTION
1 12-05 -12 AS PER FELD COMMONS ¢9 SYSTEM RISER
PERMITTED BY LAW, DEFEND, INDEMNIFY, AND HOLD SIMPLEXGRINNELL HARMLESS FROM
MURING(THMORGRV4) ANY AND ALL CLAIMS FOR LOSS, DAMAGE OR INJURY ARISING DIRECTLY OR INDIRECTLY
-+- FLANGED CC)NNECTION THEREFROM.
IN LOCALITIES SUBJECT TO FREEZING CONDITIONS, THE OWNER MUST MAINTAIN HEAT
-- 2- WAYEARiHQUAKEBRACE THROUGHOUT WET PIPE SPRINKLER SYSTEMS AREAS, AND IN ENCLOSURES WHERE DRY
+ MAY EARMAKE BRACE PIPE, DELUGE OR OTHER VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS WATER SUPPLY INFO: STATIC PRESSURE PSI - RESIDUAL PRE :SURE: PSI WITH GPM FLOWING
-�-
PIPE HANGER ARE LOCATED.
2009 SIMPLEXGRINNELL LP - ALL RIGHTS RESERVED TEST LOGATION: BY: TEST DATE:
1/2" Orifice 5.6K
200 degrees
SOLID CONCRETE CONSTRUCTION
ROD COUPL POWDER DRIVEN
STUD
ALL THREAD ROD
I HANGER DETAIL
FP - I N.T.S.
SOLID CONCRETE CONSTRUC ION
a p.
CONCRETE ANCHOR
'--',ALL THREAD ROD
' r
%--PIPE RING.
.. 4 its ^A •�• a !,• «
s.
DRILLED CONC.
ANCHOR
0�1 exempted from the special arrangemet ts of
inhibiting waterflow until elevator
occurred.
ONO
ELEVATOR PIT SPRINKLER DETAIL
No Scale
� y
•
TOTAL SPRINKLERS NOZZLES
-- NOZZLES
—_
E ESCUTCHEON /SPRINKLER NOTE SCALE: S No�D
Sim e e x
Gr ®n
n
e / B SAFE.
DRAWN BY: A Tyco International Company
E_ JAR LOCAL OFFICE: 10550 Commerce Parkway Miramar, FL 33025
CHECKED BY: JOB NAME AND LOCATION:
®.a LARKIN 4 HEADS IN PIT
CONTRACT WITH: LARKIN H4SPIT
7031 SW 62ND A E
SHEET DESCRIPTION:
CONTRACT NO: SOUTH MIAMI, FL 3 143
966045701 FIRE SPRINKLER DRA INGS
DATE: REV. #: LATEST REV. DESCRIPTION: DRAWING O.
09-05- F P -O 1