10-685-038STANDARD 3" WIDE HANGERS
Hanget extension to be the sum
of the distances between the hanging
wires and the duct size, ID (Smacna)
CHANNEL SECTION
If Total Minimum Minimum
Extension is Channel Channel
not greater than_ Gauge Profile
b" 24 3" X 15" '..
18" 22 3" X 2"
30" It 3" X 2"
USE OF 2" WIDE
22 gauge 2'x I.5" hangars may be substituted
for 3" hangars for ducts with widths not over 48"
and depths not over 24" provided that not more
than one Joint occurs between hangers and the
maximum hanger spacing Oft. Exception: When
duct perimeter is 80" or less and does not
require reinforcement two Joints are permitted
between hangars
0
dW
tv
HANGERS AND SUFFORTS
0
SiTE iNVE6TiG ATiOil NOTE
EXAMINATION OF CONTRACT DOCUMENTS AND SiTE OF WORK: THE BIDDER IS REQUIRED,
BEFORE SUBMITTING HIS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND
FAMILIARIZE HIM OR HERSELF WITH THE NATURE AND EXTENT OF THE WORK AND
ANY LOCAL CONDITIONS THAT MAY iN ANY MANNER AFFECT THE WORK TO BE DONE
AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES
NEW AND /OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL
BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING
STRUCTURES FAMILIARIZE TO HIMSELF WITH ALL EXISTING CONDITIONS. SLIGHT VARIATION
OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID
CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE
WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART
OF THE CONTRACTOR WILL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY
ASSUMED UNDER THIS CONTRACT,
AiR VENT —
FLANGED —
UNION (TYP.)
3/4" DRAIN
NOSE -1511513
VALVE
BALANCING
VALVE
PRESS. TEMP.
TEST PORT (TYie.)
CONTROL
VALVE /
GAUGE
COCK
CIRCUIT SETTER
CALANCING VALVE
W/ TEST PORT.
BUTTERFLY
VALVE (TYP-)
Y STRAINER W/
BLOW -OFF BALL
VALVE
AHU =7 CONNECTION DETAIL
N.T.63.
IN CASE OF TIRE ALARM ACTIVATION VIA SMOKE
DETECTOR OR VIA FLOW SWITCH ALL EXHAUST
FANS AND FAN COiL SERVING THiS AREA SHALL
SHUT -DOWN.
FINAL MECHANICAL PLAN-
SCALE:
OUTSIDE AIR INTAKE CALCULATIONS
AS PER ASHRAE -62 -2001 & FBC -2004.
AHU -7
1057 SF NURSE STATION
Q 890 SF CORRIDORS
O 872 SF OFFICE AREA
CALCULATIONS
O1 1057 X 10 X 15 = 159 CFM O.A.I.
1000
890 X 0.1 = 89 CFM O.A.I.
102 X 7 X 20 = 122 CFM O.A.I.
370 CFM O.A.I. REQUIRED
370 CFM O.A.I. PROVIDED
GENERAL H! V.A.G. NOTES
1. The contractor shall furnish all labor, material and equipment
for a complete H.V.A.C. system in accordance with these drawings.
The Florida Building Code 2004 and the latest edition of the
following,, publications:
(o ANS 9.1 Mechanical Refrigeration (b) NFPA Pamphlets 90A & 91
c) SMACNA (d) ASHRAE.
2. All air conditioning ductwork shall be gmd(26go) with I" exterior
wrapped insulation.
3. All exhaust ductwork shall be code gage galvanized sheet metal.
4. Duct size shown are net free area inside.
5. All air devices (diffusers, registers and grilles) shall be all
aluminum construction, with exposed surface chemically treated to
receive paint to match color or AIRGUIDE or approved equal.
6. Provide opposed blade dampers at all diffusers and registers.
7. Thermostats shall be combination cooling /heating with system
Coot /Auto /Heat /Off and Fan On /Auto selector switches.
8. Air filters for replaced fan coils shall be two beds type, filter No.1
307. efficiency, Mery 8, filter No.2 9099 efficiency, Mery 14.
LINED R/A DUCT
20X16 GMD(26GA
FOR O/A INTAKE (E)
40X20 S/A DUCT
32X8
FD
r
L_ r-
-
� I
L - -J
F- -�
.D VD
X I --
/ \ II I
v L- -J
SiDE
Maximum Hanger
Duct sixes, Inches
spacing
48: Wide or rater
4 ft
Less the 48" wide
bft
and less than 46"
f 0
0 • !Y• 6 • 6 • !
% • •
deep
Y • 0W
!6• • • y 0 6 1
•
Width between 28"
Eft
4 4a" and greater
y Y•• • W i 9y V Y +
• 9 J iY
than 16" deep
X
Less than 29" wide
art
and 16" depth or less
CHANNEL SECTION
If Total Minimum Minimum
Extension is Channel Channel
not greater than_ Gauge Profile
b" 24 3" X 15" '..
18" 22 3" X 2"
30" It 3" X 2"
USE OF 2" WIDE
22 gauge 2'x I.5" hangars may be substituted
for 3" hangars for ducts with widths not over 48"
and depths not over 24" provided that not more
than one Joint occurs between hangers and the
maximum hanger spacing Oft. Exception: When
duct perimeter is 80" or less and does not
require reinforcement two Joints are permitted
between hangars
0
dW
tv
HANGERS AND SUFFORTS
0
SiTE iNVE6TiG ATiOil NOTE
EXAMINATION OF CONTRACT DOCUMENTS AND SiTE OF WORK: THE BIDDER IS REQUIRED,
BEFORE SUBMITTING HIS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND
FAMILIARIZE HIM OR HERSELF WITH THE NATURE AND EXTENT OF THE WORK AND
ANY LOCAL CONDITIONS THAT MAY iN ANY MANNER AFFECT THE WORK TO BE DONE
AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES
NEW AND /OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL
BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING
STRUCTURES FAMILIARIZE TO HIMSELF WITH ALL EXISTING CONDITIONS. SLIGHT VARIATION
OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID
CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE
WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART
OF THE CONTRACTOR WILL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY
ASSUMED UNDER THIS CONTRACT,
AiR VENT —
FLANGED —
UNION (TYP.)
3/4" DRAIN
NOSE -1511513
VALVE
BALANCING
VALVE
PRESS. TEMP.
TEST PORT (TYie.)
CONTROL
VALVE /
GAUGE
COCK
CIRCUIT SETTER
CALANCING VALVE
W/ TEST PORT.
BUTTERFLY
VALVE (TYP-)
Y STRAINER W/
BLOW -OFF BALL
VALVE
AHU =7 CONNECTION DETAIL
N.T.63.
IN CASE OF TIRE ALARM ACTIVATION VIA SMOKE
DETECTOR OR VIA FLOW SWITCH ALL EXHAUST
FANS AND FAN COiL SERVING THiS AREA SHALL
SHUT -DOWN.
FINAL MECHANICAL PLAN-
SCALE:
OUTSIDE AIR INTAKE CALCULATIONS
AS PER ASHRAE -62 -2001 & FBC -2004.
AHU -7
1057 SF NURSE STATION
Q 890 SF CORRIDORS
O 872 SF OFFICE AREA
CALCULATIONS
O1 1057 X 10 X 15 = 159 CFM O.A.I.
1000
890 X 0.1 = 89 CFM O.A.I.
102 X 7 X 20 = 122 CFM O.A.I.
370 CFM O.A.I. REQUIRED
370 CFM O.A.I. PROVIDED
GENERAL H! V.A.G. NOTES
1. The contractor shall furnish all labor, material and equipment
for a complete H.V.A.C. system in accordance with these drawings.
The Florida Building Code 2004 and the latest edition of the
following,, publications:
(o ANS 9.1 Mechanical Refrigeration (b) NFPA Pamphlets 90A & 91
c) SMACNA (d) ASHRAE.
2. All air conditioning ductwork shall be gmd(26go) with I" exterior
wrapped insulation.
3. All exhaust ductwork shall be code gage galvanized sheet metal.
4. Duct size shown are net free area inside.
5. All air devices (diffusers, registers and grilles) shall be all
aluminum construction, with exposed surface chemically treated to
receive paint to match color or AIRGUIDE or approved equal.
6. Provide opposed blade dampers at all diffusers and registers.
7. Thermostats shall be combination cooling /heating with system
Coot /Auto /Heat /Off and Fan On /Auto selector switches.
8. Air filters for replaced fan coils shall be two beds type, filter No.1
307. efficiency, Mery 8, filter No.2 9099 efficiency, Mery 14.
LINED R/A DUCT
20X16 GMD(26GA
FOR O/A INTAKE (E)
40X20 S/A DUCT
32X8
FD
r
L_ r-
-
� I
L - -J
F- -�
.D VD
X I --
/ \ II I
v L- -J
SiDE
A PLENUM
FILTER CUBIC
PULL OUT SPACE
WV
COIL PULL
OUT SPACE
42X8
� � I
—� -- —J
FD 1- �-1/2" CHWS
do CHWR CONNECT
TO EXIST. MAIN
PARTiAL FLAN AHU -1
SCALE= I/2 " =1' -0"
AIR BALANCE CALCULATIONS
MARK SUPPLY AIR RETURN AIR EXHAUST AiR UNDER CUT DOOR AIR OUTSIDE AIR INTAKE
TO OTHER AREAS
AHU -7 3000 2630 370 0 .370
370 TOTAL EXH. 370 TOTAL INTAKE
AHU -7
YES
MANUF.
•+ W� y + ' Y 9 ra
•W Y • W
MODEL
6006 0•• • •
• "066
•
• 60
+ W'V Y
01006 0606
f 0
0 • !Y• 6 • 6 • !
% • •
•
Y • 0W
!6• • • y 0 6 1
•
• •
• U V U i i r 9 i • Y + + 6
•
y Y•• • W i 9y V Y +
• 9 J iY
X
FIRE STOPPING
Y W
• + 9 +
y + Y
960
4 Y
• • 6
LEGEND
r !
• Y W •
+YW + Wy
:::.:
w
�.� �L'ARKING HOSPITA
j.• ::24XZ4 CD'(SEE SCHEDftQ Y ": •`
' •
: • r • 6 • DUCT TCr M TCH NECK SIZE TYN. 6 00
•
�y SEE
EMERGENCY DEP.
DUCT TO ,$�E TYP_U• r • 4-0-
Y r • 6
INTERIOR RENOVATION
: """9
•� . " "r�STUR'�T'�r GRILL :..•' •' y
x,666
o
_ • v • • • ti
W : VOLUVE &PER " • :•6• •
i 90904 r 000 .966
r
• •W•6 Y
7031 S.W. 62nd AVE.
•000
QQ THERMOSTAT
SOUTH MIAMI, FLORIDA 33143
DUCT MOUNTED SMOKE DETECTOR
SEE F.A. RISER FOR SPECS.
AIR FLOW DIRECTION ( ARROWS DENOTE
Owner
--- 1 WAY, 2 WAY, ETC., SEE PLANS
--Av— RETURN OR EXHAUST, SEE PLANS.
WALL MOUNTED SIDE REGISTER.
General Contractor
EXHAUST FAN
L7J
PLANNING
ARCIi
041. OUTSIDE AIR INTAKE
EERING
b E DALY I N T E R ISO R S N G
3.R SIDE REGISTER
0
EST, 1915
co CEILING DIFFUSER
C6 CEILING GRILL
3390 Mary Street, Suite 216
NP HEAT PUMP UNIT
Miami Florida 33133 USA
T. 305.461.9480 F: 305.461.3686
U.0K UNLESS OTHERWISE NOTED.
Architect
RIU ROOF TOP UNiT
AW AIR HANDLER UNIT
CU CONDENSING UNIT
Associate Architect
EXHAUST FAN
CR1 CUBIC FEET PER MINUTE
A PLENUM
FILTER CUBIC
PULL OUT SPACE
WV
COIL PULL
OUT SPACE
42X8
� � I
—� -- —J
FD 1- �-1/2" CHWS
do CHWR CONNECT
TO EXIST. MAIN
PARTiAL FLAN AHU -1
SCALE= I/2 " =1' -0"
AIR BALANCE CALCULATIONS
MARK SUPPLY AIR RETURN AIR EXHAUST AiR UNDER CUT DOOR AIR OUTSIDE AIR INTAKE
TO OTHER AREAS
AHU -7 3000 2630 370 0 .370
370 TOTAL EXH. 370 TOTAL INTAKE
AHU -7
YES
MANUF.
TRANS
MODEL
LPCAD08P
AIR FLOW
3000 CFM
ELECT. SERVICE
208 3 60
WATER CONN.
1-112- CWS, CWR
HVAC DESIGN REQUIRE:
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPER(S)
X
SMOKE DAMPERS
X
FIRE RATE ENCLOSURE
X
FIRE RATED ROOF /FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
X
r
m�anNmas�a
pammaam6
ffa�suQUSea
P.E. No 53288
Jose Antonio Mendez.
Professional Engineer m O M m 0 II
1385 Coral Way Suite #203 Miami, FL 33145 P 0 ff [# 110@ m 6 a
PH:(305)854-8824 FAX(305)856-1797 ffm0lm91111U11(1 60111p.
jose01189801 -mm CA 00008324
Scale-
nai
Drawing Issue
REVISIONS
N0. DESCRIPTION DATE
LEO A DALY COMPANY Cop"ht 2007
Number
M -6