10-685-037le" 22 BY X 211
30" le 3" X 2"
USE OF 2" WIDE
22 gauge 21x 15" hangers may be substituted
for 3" hangers for ducts with widths not over 48
and depths not over 24" provided that not more
than one joint occurs between hangers and the
maximum hanger spacing Oft. Exception: When
duct perimeter is e0" or. less and does not
require reinforcement two joints are permitted
bet
hangers
e en ha s
0
AIR VENT
FLANGED
UNION (TYP.)
SITE iNVE ST iGAT i ON NOTE
EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: THE BIDDER 1S REQUIRED,
BEFORE SUBMITTING HiS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND
FAMILIARIZE HIM OR HERSELF WiTH THE NATURE AND EXTENT OF THE WORK AND
ANY LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE WORK TO BE DONE
AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES
NEW AND/OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL
BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING
STRUCTURES FAMILIARIZE TO HIMSELF WiTH ALL EXISTING CONDITIONS. SLIGHT VARIATION
OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID
CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE
WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART
OF THE CONTRACTOR WiLL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY
ASSUMED UNDER THIS CONTRACT.
BALANCING
VALVE
PRE55. TEMP.
TEST PORT (TYP.)
CONTTREOL
VALV
GAUGE
COCK
CIRCUIT SETTER
BALANCING VALVE
W/ TEST PORT.
I G"WS
BUTTERFLY
VALVE (TYP.)
3/4" DRAIN Y STRAINER W/
BLOW -OFF BALL
HOSE -BIBS VALVE
VALVE
AHU =7 CONNECTION DETAIL
. N.T.S.
iN CASE OF FIRE ALARM ACTIVATION VIA SMOKE
DETECTOR OR VIA FLOW SWITCH ALL EXHAUST
FANS AND FAN COIL SERViNG THIS AREA SHALL
SHUT -DOWN.
Maximum Hanger
Duct size, incites
Spacing
48: Wide or orator
4 ft
Less tha 4e" wide
Eft
and less than 48"
1 4"
deep
113
Width between 28"
Eft
4 4e" and greater
1
than 16" deep
Extension is
Less than 29" wide
- eft
and 4" depth or less '
le" 22 BY X 211
30" le 3" X 2"
USE OF 2" WIDE
22 gauge 21x 15" hangers may be substituted
for 3" hangers for ducts with widths not over 48
and depths not over 24" provided that not more
than one joint occurs between hangers and the
maximum hanger spacing Oft. Exception: When
duct perimeter is e0" or. less and does not
require reinforcement two joints are permitted
bet
hangers
e en ha s
0
AIR VENT
FLANGED
UNION (TYP.)
SITE iNVE ST iGAT i ON NOTE
EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: THE BIDDER 1S REQUIRED,
BEFORE SUBMITTING HiS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND
FAMILIARIZE HIM OR HERSELF WiTH THE NATURE AND EXTENT OF THE WORK AND
ANY LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE WORK TO BE DONE
AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES
NEW AND/OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL
BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING
STRUCTURES FAMILIARIZE TO HIMSELF WiTH ALL EXISTING CONDITIONS. SLIGHT VARIATION
OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID
CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE
WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART
OF THE CONTRACTOR WiLL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY
ASSUMED UNDER THIS CONTRACT.
BALANCING
VALVE
PRE55. TEMP.
TEST PORT (TYP.)
CONTTREOL
VALV
GAUGE
COCK
CIRCUIT SETTER
BALANCING VALVE
W/ TEST PORT.
I G"WS
BUTTERFLY
VALVE (TYP.)
3/4" DRAIN Y STRAINER W/
BLOW -OFF BALL
HOSE -BIBS VALVE
VALVE
AHU =7 CONNECTION DETAIL
. N.T.S.
iN CASE OF FIRE ALARM ACTIVATION VIA SMOKE
DETECTOR OR VIA FLOW SWITCH ALL EXHAUST
FANS AND FAN COIL SERViNG THIS AREA SHALL
SHUT -DOWN.
TF -1
MANUFAC.
GRENHECK
TYPE
IN LINE
CFM
CHANNEL SECTION
STATIC FIRE55UiRE IN.
1 4"
H.P.
113
If Total
Minimum
Minimum
1
RPM
Extension is
Channel
Channel
WANCsERS AND SUFF'OIR S
iw �/
not greater than:
Gauge
Profile
f_ f I�
6 +'
24
3" X 1.51,
C2~I'1
le" 22 BY X 211
30" le 3" X 2"
USE OF 2" WIDE
22 gauge 21x 15" hangers may be substituted
for 3" hangers for ducts with widths not over 48
and depths not over 24" provided that not more
than one joint occurs between hangers and the
maximum hanger spacing Oft. Exception: When
duct perimeter is e0" or. less and does not
require reinforcement two joints are permitted
bet
hangers
e en ha s
0
AIR VENT
FLANGED
UNION (TYP.)
SITE iNVE ST iGAT i ON NOTE
EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: THE BIDDER 1S REQUIRED,
BEFORE SUBMITTING HiS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND
FAMILIARIZE HIM OR HERSELF WiTH THE NATURE AND EXTENT OF THE WORK AND
ANY LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE WORK TO BE DONE
AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES
NEW AND/OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL
BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING
STRUCTURES FAMILIARIZE TO HIMSELF WiTH ALL EXISTING CONDITIONS. SLIGHT VARIATION
OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID
CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE
WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART
OF THE CONTRACTOR WiLL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY
ASSUMED UNDER THIS CONTRACT.
BALANCING
VALVE
PRE55. TEMP.
TEST PORT (TYP.)
CONTTREOL
VALV
GAUGE
COCK
CIRCUIT SETTER
BALANCING VALVE
W/ TEST PORT.
I G"WS
BUTTERFLY
VALVE (TYP.)
3/4" DRAIN Y STRAINER W/
BLOW -OFF BALL
HOSE -BIBS VALVE
VALVE
AHU =7 CONNECTION DETAIL
. N.T.S.
iN CASE OF FIRE ALARM ACTIVATION VIA SMOKE
DETECTOR OR VIA FLOW SWITCH ALL EXHAUST
FANS AND FAN COIL SERViNG THIS AREA SHALL
SHUT -DOWN.
OUTSIDE AIR INTAKE CALCULATIONS
AS PER ASHRAE -62 -2001 is FBC -2004.
AHU- 7
1057 SF NURSE STATION
0 890 SF CORRIDORS
O 872 SF OFFICE AREA
CALCULATIONS
1057 X 10 X 15 — 159 CFM O.A.1.
1000
Q 890 X 0.1 = 89 CFM O.A.I.
O 1000 X 7 X 20 122 CFM O.A.I.
370 CFM O.A.I. REQUIRED
370 CFM O.A.I. PROVIDED
FAN SCHEDULE
ITEM
TF -1
MANUFAC.
GRENHECK
TYPE
IN LINE
CFM
600
STATIC FIRE55UiRE IN.
1 4"
H.P.
113
VOLTS
115
see
1
RPM
1835
REFERENCE MODEL
BSQ -80
REMARKS
1
THERMOSTAT
CONDENSING UNIT
- r
OUTSIDE AIR INTAKE CALCULATIONS
AS PER ASHRAE -62 -2001 is FBC -2004.
AHU- 7
1057 SF NURSE STATION
0 890 SF CORRIDORS
O 872 SF OFFICE AREA
CALCULATIONS
1057 X 10 X 15 — 159 CFM O.A.1.
1000
Q 890 X 0.1 = 89 CFM O.A.I.
O 1000 X 7 X 20 122 CFM O.A.I.
370 CFM O.A.I. REQUIRED
370 CFM O.A.I. PROVIDED
FAN SCHEDULE
ITEM
TF -1
MANUFAC.
GRENHECK
TYPE
IN LINE
CFM
600
STATIC FIRE55UiRE IN.
1 4"
H.P.
113
VOLTS
115
PHASES
1
RPM
1835
REFERENCE MODEL
BSQ -80
REMARKS
1
MECHANICAL PLAN PHASE 5
1. The contractor shall furnish all labor, material and equipment
for a complete H.V.A.C. system in accordance with these drawings.
The Florida Building Cods 2004 and the latest edition of the
following publications:
(a )ANS B9.1 Mechanical Refrigeration (b) NFPA Pamphlets 90A k 91
c) SMACNA (d) ASHRAE.
2. All air conditioning ductwork shall be gmd(26g@) with I" exterior
wrapped insulation.
3. All exhaust ductwork shall be code gage galvanized sheet metal.
4. Duct size shown are net free area inside.
5. All air devices (diffusers, registers and grilles) shall be all
aluminum construction, with exposed surface chemically treated to
receive paint to match color or AIRGUIDE or approved equal.
6. Provide opposed blade dampers at all diffusers and registers.
•Y•V •YU •
LEL;`EIS. •.f
•'•.. Y • c
Y Y •
•
•••• 00664, YYY Y•••
• • . V • •
V G • V • • • • • • Y • • • C
• . Y.
• • • • Y V Y •
*000 f • f ♦ • • 000 • ***e u' • YYY • `
Y •
EXISTING DUCT :Y•. •:L
----- - - ---- TO REMAIN
EXISTING DUCT TO
BE ELIMINATED
NEW DUCT
EXISTING RETURN OR
EXHAUST GRILL TO REMAIN
EXISTING RETURN OR
V7 EXHAUST GRILL TO BE
ELIMINATED
NEW EXHAUST OR
RETURN GRILL
j j EXISTING SUPPLY GRILL
TO REMAIN
V. _.V
EXISTING SUPPLY GRILL
TO BE ELIMINATED
• NEW SUPPLY GRILL
SCOPE OF WRK FOR PHASE 5
- INSTALL EXHAUST GRILL CONNECTED TO TF -I
IN AREA OF WORK TO MAINTAIN NEGATIVE
PRESSURE.
- INSTALL NEW SUPPLY AND RETURN GRILLS
AS SHOW IN PLANS.
7. Thermostats shall be combination cooling /heating with system
Cool /Auto /Heat /Off and Fan On /Auto selector switches. - CONNECT THE RETURN DUCT UNFINISHED IN
8- Air filters for replaced fan coils shall be two beds type, filter No.1 PHASE 3 TO MECHANICAL ROOM W/NEW FIRE
3OX efficiency, Mery 8, filter No.2 9OX efficiency, Mery 14. DAMPER
14 GA.
LiNK (
R/A PLENUM
FILTER CUBIC
L32XB 11—PULL OUT SPACE
LINED R/A DUCT - _ _ D
ALL FOR101 MD(TAKE( ?E)
1 1
U.L. 555
FIRE DAMPER L _ J A r -1 COIL PULL
COLLAR 1 \ / I I I OUTS ACE
42x8
FD ISD VD
RECTANGULAR DUCT /X\
30X8 FROM NURSE
STATION, 40X20 S/A D CT I — — — —
ACCESS DOOR �
/ \ I I
I I
FIRE DAMPER DETAIL —WALL - FD I V WR CCONNECT
N.T.S. TO EXIST. MAIN
ft/A SiDE
PARTIAL PLAN AHU -1
SCALE: 1/2 " =1' -fd"
AIR BALANCE CALCULATIONS
MARK SUPPLY AIR RETURN AIR EXHAUST AiR UNDER CUT DOOR AIR OUTSIDE AIR INTAKE
TO OTHER AREAS
AHU -7 3000 2630 370 0 370
370 TOTAL EXH. 370 TOTAL INTAKE
CALCULATION OF TEMPORARY FAN
TO MAINTAIN NEGATIVE PRESSURE IN AREA
OF WORK DURING CONSTRUCTION TIME
(BASED ON PHASE 5 AS LARGER AREA).
5904 C.F AT 3 COMPLETE
CHANGES PER HOURS
5904 X 3 – 300 CFM MINIMUN REQUIRED
60
600 CFM PROVIDED
AHU —T
LEGEND
SIDE REGISTER
TRANE
24X24 CD —(SEE SCHEDULE
CEILING DIFFUSER
AIR FLOW
DUCT TO MATCH NECK SIZE TYP.
CEILING GRILL
�y
CEILING GRILLE SEE SIZE SCHEDULE
HEAT PUMP UNIT
FiRE RATE ENCLOSURE
DUCT TO MATCH NECK SIZE TYP.
UNLESS OTHERWISE NOTED.
FIRE RATED ROOF FLOOR CEILING ASSEMBLY
RETURN AIR GRILL
ROOF TOP UNIT
+
VOLUME DAMPER
AIR HANDLER UNIT
QQ
THERMOSTAT
CONDENSING UNIT
DUCT MOUNTED SMOKE DETECTOR
EXHAUST. FAN
C2~I'1
SEE F.A. RISER FOR SPECS.
GENERAL H• V.A.C.
NOTES
AIR FLOW DIRECTION ( ARROWS DENOTE
--�
1 WAY, 2 WAY, ETC., SEE PLANS
-��
RETURN OR EXHAUST, SEE PUNS.
p
WALL MOUNTED SIDE REGISTER,
r
Ln
EXHAUST FAN
OAJ
OUTSIDE AIR INTAKE
1. The contractor shall furnish all labor, material and equipment
for a complete H.V.A.C. system in accordance with these drawings.
The Florida Building Cods 2004 and the latest edition of the
following publications:
(a )ANS B9.1 Mechanical Refrigeration (b) NFPA Pamphlets 90A k 91
c) SMACNA (d) ASHRAE.
2. All air conditioning ductwork shall be gmd(26g@) with I" exterior
wrapped insulation.
3. All exhaust ductwork shall be code gage galvanized sheet metal.
4. Duct size shown are net free area inside.
5. All air devices (diffusers, registers and grilles) shall be all
aluminum construction, with exposed surface chemically treated to
receive paint to match color or AIRGUIDE or approved equal.
6. Provide opposed blade dampers at all diffusers and registers.
•Y•V •YU •
LEL;`EIS. •.f
•'•.. Y • c
Y Y •
•
•••• 00664, YYY Y•••
• • . V • •
V G • V • • • • • • Y • • • C
• . Y.
• • • • Y V Y •
*000 f • f ♦ • • 000 • ***e u' • YYY • `
Y •
EXISTING DUCT :Y•. •:L
----- - - ---- TO REMAIN
EXISTING DUCT TO
BE ELIMINATED
NEW DUCT
EXISTING RETURN OR
EXHAUST GRILL TO REMAIN
EXISTING RETURN OR
V7 EXHAUST GRILL TO BE
ELIMINATED
NEW EXHAUST OR
RETURN GRILL
j j EXISTING SUPPLY GRILL
TO REMAIN
V. _.V
EXISTING SUPPLY GRILL
TO BE ELIMINATED
• NEW SUPPLY GRILL
SCOPE OF WRK FOR PHASE 5
- INSTALL EXHAUST GRILL CONNECTED TO TF -I
IN AREA OF WORK TO MAINTAIN NEGATIVE
PRESSURE.
- INSTALL NEW SUPPLY AND RETURN GRILLS
AS SHOW IN PLANS.
7. Thermostats shall be combination cooling /heating with system
Cool /Auto /Heat /Off and Fan On /Auto selector switches. - CONNECT THE RETURN DUCT UNFINISHED IN
8- Air filters for replaced fan coils shall be two beds type, filter No.1 PHASE 3 TO MECHANICAL ROOM W/NEW FIRE
3OX efficiency, Mery 8, filter No.2 9OX efficiency, Mery 14. DAMPER
14 GA.
LiNK (
R/A PLENUM
FILTER CUBIC
L32XB 11—PULL OUT SPACE
LINED R/A DUCT - _ _ D
ALL FOR101 MD(TAKE( ?E)
1 1
U.L. 555
FIRE DAMPER L _ J A r -1 COIL PULL
COLLAR 1 \ / I I I OUTS ACE
42x8
FD ISD VD
RECTANGULAR DUCT /X\
30X8 FROM NURSE
STATION, 40X20 S/A D CT I — — — —
ACCESS DOOR �
/ \ I I
I I
FIRE DAMPER DETAIL —WALL - FD I V WR CCONNECT
N.T.S. TO EXIST. MAIN
ft/A SiDE
PARTIAL PLAN AHU -1
SCALE: 1/2 " =1' -fd"
AIR BALANCE CALCULATIONS
MARK SUPPLY AIR RETURN AIR EXHAUST AiR UNDER CUT DOOR AIR OUTSIDE AIR INTAKE
TO OTHER AREAS
AHU -7 3000 2630 370 0 370
370 TOTAL EXH. 370 TOTAL INTAKE
CALCULATION OF TEMPORARY FAN
TO MAINTAIN NEGATIVE PRESSURE IN AREA
OF WORK DURING CONSTRUCTION TIME
(BASED ON PHASE 5 AS LARGER AREA).
5904 C.F AT 3 COMPLETE
CHANGES PER HOURS
5904 X 3 – 300 CFM MINIMUN REQUIRED
60
600 CFM PROVIDED
AHU —T
S.R
SIDE REGISTER
TRANE
CD
CEILING DIFFUSER
AIR FLOW
CG
CEILING GRILL
2081316!0 0
HP.
HEAT PUMP UNIT
FiRE RATE ENCLOSURE
aox
UNLESS OTHERWISE NOTED.
FIRE RATED ROOF FLOOR CEILING ASSEMBLY
R1U
ROOF TOP UNIT
FIRE STOPPING
ANU
AIR HANDLER UNIT
SMOKE CONTROL
CJ
CONDENSING UNIT
EF
EXHAUST. FAN
C2~I'1
CUBIC FEET PER MINUTE
GENERAL H• V.A.C.
NOTES
1. The contractor shall furnish all labor, material and equipment
for a complete H.V.A.C. system in accordance with these drawings.
The Florida Building Cods 2004 and the latest edition of the
following publications:
(a )ANS B9.1 Mechanical Refrigeration (b) NFPA Pamphlets 90A k 91
c) SMACNA (d) ASHRAE.
2. All air conditioning ductwork shall be gmd(26g@) with I" exterior
wrapped insulation.
3. All exhaust ductwork shall be code gage galvanized sheet metal.
4. Duct size shown are net free area inside.
5. All air devices (diffusers, registers and grilles) shall be all
aluminum construction, with exposed surface chemically treated to
receive paint to match color or AIRGUIDE or approved equal.
6. Provide opposed blade dampers at all diffusers and registers.
•Y•V •YU •
LEL;`EIS. •.f
•'•.. Y • c
Y Y •
•
•••• 00664, YYY Y•••
• • . V • •
V G • V • • • • • • Y • • • C
• . Y.
• • • • Y V Y •
*000 f • f ♦ • • 000 • ***e u' • YYY • `
Y •
EXISTING DUCT :Y•. •:L
----- - - ---- TO REMAIN
EXISTING DUCT TO
BE ELIMINATED
NEW DUCT
EXISTING RETURN OR
EXHAUST GRILL TO REMAIN
EXISTING RETURN OR
V7 EXHAUST GRILL TO BE
ELIMINATED
NEW EXHAUST OR
RETURN GRILL
j j EXISTING SUPPLY GRILL
TO REMAIN
V. _.V
EXISTING SUPPLY GRILL
TO BE ELIMINATED
• NEW SUPPLY GRILL
SCOPE OF WRK FOR PHASE 5
- INSTALL EXHAUST GRILL CONNECTED TO TF -I
IN AREA OF WORK TO MAINTAIN NEGATIVE
PRESSURE.
- INSTALL NEW SUPPLY AND RETURN GRILLS
AS SHOW IN PLANS.
7. Thermostats shall be combination cooling /heating with system
Cool /Auto /Heat /Off and Fan On /Auto selector switches. - CONNECT THE RETURN DUCT UNFINISHED IN
8- Air filters for replaced fan coils shall be two beds type, filter No.1 PHASE 3 TO MECHANICAL ROOM W/NEW FIRE
3OX efficiency, Mery 8, filter No.2 9OX efficiency, Mery 14. DAMPER
14 GA.
LiNK (
R/A PLENUM
FILTER CUBIC
L32XB 11—PULL OUT SPACE
LINED R/A DUCT - _ _ D
ALL FOR101 MD(TAKE( ?E)
1 1
U.L. 555
FIRE DAMPER L _ J A r -1 COIL PULL
COLLAR 1 \ / I I I OUTS ACE
42x8
FD ISD VD
RECTANGULAR DUCT /X\
30X8 FROM NURSE
STATION, 40X20 S/A D CT I — — — —
ACCESS DOOR �
/ \ I I
I I
FIRE DAMPER DETAIL —WALL - FD I V WR CCONNECT
N.T.S. TO EXIST. MAIN
ft/A SiDE
PARTIAL PLAN AHU -1
SCALE: 1/2 " =1' -fd"
AIR BALANCE CALCULATIONS
MARK SUPPLY AIR RETURN AIR EXHAUST AiR UNDER CUT DOOR AIR OUTSIDE AIR INTAKE
TO OTHER AREAS
AHU -7 3000 2630 370 0 370
370 TOTAL EXH. 370 TOTAL INTAKE
CALCULATION OF TEMPORARY FAN
TO MAINTAIN NEGATIVE PRESSURE IN AREA
OF WORK DURING CONSTRUCTION TIME
(BASED ON PHASE 5 AS LARGER AREA).
5904 C.F AT 3 COMPLETE
CHANGES PER HOURS
5904 X 3 – 300 CFM MINIMUN REQUIRED
60
600 CFM PROVIDED
AHU —T
YES
MANUF.
TRANE
MODEL
LPCAD08P
AIR FLOW
3000 CFM
ELECT. SERVICE
2081316!0 0
WATER CONN.
1 -1 2" CWS, CWR
HVAC DESIGN REQUIRE:
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPERS)
X
SMOKE DAMPERS
X
FiRE RATE ENCLOSURE
X
FIRE RATED ROOF FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
X
tiro
Yry f^
■a0�1gIR�l
maml� mama
�taa><ala�a
P.E. No 5328E
Jose Antonio Mendez.
Professional Engineer m Q m m 0 II
�omff�eelmm�a
1385 Coral Way Suite *203 Miami, FL 33145
PH:(305)854 -9824 FAX(305)856 -1797
. jose01188891./Mm CA 00008324
r � r r ♦
.Y .-LARKING HOSPITAL
• �•W ,EMERGENCY DEP.
INTERIOR RENOVATION
l � Y Y i • •
: 7031 S.W. 62nd AVE
• ° t0(J11i • MIAMI. FLORIDA 33143
General Contractor
K-DADA V IN TER e0RSNG E
•
EST. 1915
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T. 305.461.9480 F: 305.461.3686
Architect
A9eeciete Architect
soil:
061- 10026 -000
Arehitects Pre*t Number
Drawing Issue
REVISIONS
NO. DESCRIPTION DATE
Shoat Number