10-349-002INSTALLATION NOTES 1. FIRE DETECTION AND SUPPRESSION SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) CODES 72, 70 - ARTICLE 780, 2001, MANUFACTURES INSTRUCTIONS AND LOCAL CODES 2. FIELD VERIFY ROOM SIZE, CEILING HEIGHT AND EQUIPMENT LAYOUT. 3. FUNCTION TESTING OF THE DETECTION AND CONTROL EQUIPMENT SHALL BE PERFORMED ACCORDING TO NFPA 72 AND 2001. 4. ENCLOSURE INTEGRITY TESTING OF THE PROTECTED ENCLOSE SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 2001 5. ROOM SEALING AND INTEGRITY IS THE RESPONSIBILITY OF THE OWNER OR GENERAL CONTRACTOR. 6. ALL DOORS OR OPENINGS IN THE PROTECTED ENCLOSURE MUST BE CLOSED OR CLOSE UPON SYSTEM ACTUATION. DOOR CLOSING DEVICES MAY BE ELECTRICALLY CONNECTED THROUGH THE FIRE ALARM CONTACTS. 7. ALL AIR MOVING DEVICES AND CRITICAL EQUIPMENT MUST BE SHUT DOWN THROUGH THE EQUIPMENT CONTACTS UNLESS AIR IS RECIRCULATING ONLY IN THE AREA PROTECTED BY THE PARTICULAR SYSTEM AND MAKE4JP AIR IS STOPPED. • 8. LOCATIONS SHOWN FOR THE DETECTORS ARE APPROXIMATE ONLY. DETECTORS MUST BE LOCATED WHERE SUITABLE FOR THE APPLICATION AND IN ACCORDANCE WITH NFPA-72. DETECTORS MUST NOT BE LOCATED WITHIN 3' OF A SUPPLY GRILL. S. PROTECT EQUIPMENT FROM DUST, DRILLING RESIDUE AND DAMAGE AT ALL TIMES. 10. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. 11. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS,FOR'AS BUILT' PURPOSES. 12. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO MANUFACTURER'S CUT SHEETS AND /OR INSTALLATION INSTRUCTIONS. 13. WIRING SHALL BE IN ACCORDANCE WITH WIRE TABLE WITH RESPECT TO CONDUCTOR SIZE, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY MARKED FOR FUTURE IDENTIFICATION. 14. ALL PENETRATIONS THROUGH WALLS, FLOORS OR CEILINGS SHALL BE SEALED AND COVERED WITH AN ESCUSION PLATE. IF THE PENETRATION IS THROUGH A RATED ASSEMBLY, THEN AN APPROPRIATE FIRE STOPPING MATERIAL MUST BE UTILIZED. 4T-8 5W 24''8" ,,e DEVICE LOCATION PLAN SCALE: IlV r, ADDRESS LABEL CLARIFICATION F,M- AUDIBLE DEVICE (HORN, BELL OR SPEAKER) ROOM AREA CIRCUIT NUMBER VOLUME FACTOR@ ALTITUDE DEVICE NUMBER ON CIRCUIT A2-3 VISUAL DEVICE (STROBE) ' Sq Ft. CIRCUIT NUMBER Cu. Ft .6,4 %@70F ADJ DEVICE NUMBER ON CIRCUIT 2-3 AUDIBLEIVISUAL DEVICE (HORN/STROBE) CT Trailer 462.3 T500 CIRCUIT NUMBER A 2-3 DEVICE NUMBER ON CIRCUIT 1:00 DETECTION ZONE 110 LBS DETECTION CIRCUIT DEVICE NUMBER ON CIRCUIT °1A 2 FM200 ZONES AGENT CONTAINERS 1- GANTRY 8 CONTROL ROOMS 0-1 110 LB.R - m o; • ._ ? =:a■ = ' ..• f a •' « II llpZ ® . .! YL=01 wy ll#m)= ' La1 VOLUME CALCULATIONS F,M- 200/FE: -227 iffC-227ea) NFPA 2001 TABLE A.5.5.1 (k) ROOM AREA AVG. HT.. VOLUME FACTOR@ ALTITUDE NOZZLE1. AGENT AGENT ' Sq Ft. Ft. Cu. Ft .6,4 %@70F ADJ ADJ REQ SUPPLIED CT Trailer 462.3 T500 3467.25 0.0311 1.000 1:00 108 LBS 110 LBS TOTALS 1 3,4673 108 LBS 110 LBS Y r • FL CERT EF 20000636 FL CERT FM 16058100012009 CV co T 0) �QQ L R CHANGE CALCULATIONS NFPA 72 - Q m � L0 aLo m M ' n 1 �l ' 8 � TOTAL • M ' # 4 ! , i i ` 3 •' OF } # �� • OF CROSS Z64L DETECTORS Y r • FL CERT EF 20000636 FL CERT FM 16058100012009 II -1 1 11 . 11 � n 1` n n _ � u � i v c - n • a I�Oi�ii�•i Al � r • X NQ oA'm 1007160 3 -18-10 wm Nm ecNE D9400 AS NOTED HEEr 2 oR 8 FA -2 ■ 1 CV co T 0) �QQ n T- Q m � L0 aLo m M L X ¢ W L1 T U � q t}— ��w" T ,Q m U WO W LU CI Qa � � Q II -1 1 11 . 11 � n 1` n n _ � u � i v c - n • a I�Oi�ii�•i Al � r • X NQ oA'm 1007160 3 -18-10 wm Nm ecNE D9400 AS NOTED HEEr 2 oR 8 FA -2 ■ 1