10-349-006INSTALLATION NOTES FOR FM200 PYRO -CHEM SYSTEM THESE SPECIFICATIONS ARE TO APPLY TO ALL INSTALLATIONS OF FM200 FIRE EXTINGUISHER SYSTEMS. NOTE: PIPE SHALL CONFORM TO ASTM/NFPA 20012-2. 1. ALL THREADED PIPE TO BE BLACK STEEL OF THE FOLLOWING PIPE SIZE AND GRADE COMBINATIONS. PIPE REFERENCE PIPE TYPE & NOMINAL SIZE CONNECTION ASTM A-106 SEAMLESS, GRADE C SCH. 40 118 0-8" NPS THREADED ASTM A- 106/A -53 SEAMLESS GRADE B SCH. 40 118" -8" NPS THREADED ASTM A- 106/A -53 SEAMLESS GRADE A SCH. 40 118 0-8" NPS THREADED ASTM A-53 ERW GRADE B SCH. 40 118 7-8" NPS THREADED ASTM A-53 ERW GRADE A SCH. 40 1/8 "-8" NPS THREADED ASTM A-53 FURNACE WELD CLASS F SCH. 40 118 " -1 1/2" NPS THREADED ASTM A-53 FURNACE WELD CLASS F SCH. 80 2"- 8" NPS THREADED ASTM A-106 SEAMLESS, GRADE C SCH. 40 118 "-8" NPS WELDED ASTM A- 106/A -53 SEAMLESS GRADE B SCH. 40 118 0-8' NPS WELDED ASTM A-108/A -53 SEAMLESS GRADE A SCH. 40 118 0-8" NPS WELDED ASTM A-53 ERW GRADE B SCH. 40 118 0-S" NPS WELDED ASTM A-53 ERW. GRADE A SCH. 40 1/8" -8" NPS WELDED ASTM A-63 FURNACE WELD CLASS F SCH. 40 118" -6" NPS WELDED 2. PIPE GRADES MUST BE SUITABLE FOR THE PRESSURES CALCULATED BY PYROCHEWS FM 200 FLOW CALCULATION PROGRAM. CONSULT THE CHART IN PYROCHEM'S DESIGN MANUAL OR NFPA 2001, FOR MAXIMUM PIPE PRESSURES FOR THE DIFFERENT PIPE GRADES. 3. ALL FITTINGS TO BE 300 lb. ANSI B -16.3 BLACK MALLEABLE IRON THREADED FITTINGS THROUGH 3" SIZE. FORGED STEEL FITTINGS TO BE USED FOR LARGER SIZES. FLANGED JOINTS TO BE CLASS 600 lb. (CLASS 300 MALLEABLE IRON UNIONS OR STREET ELBOWS SHALL NOT BE USED.) FITTING DESCRIPTION PIPE SIZE CLASS 300 MALLEABLE OR DUCTILE IRON UP TO OR a 3 In. NPS 10004b RATED DUCTILE IRON OR FORGED STEEL > 3 In. NPS CLASS 300 FLANGED JOINTS ALL 4. ALL FITTINGS USED TO CONSTRUCT THE MANIFOLD, INCLUDING FITTINGS BEFORE THE ORIFICE UNION TO BE BLACK FORGED STEEL 2000 lb. OR 3000 lb. ANSI B- 16.11. 5. NOT USED 6. PIPE LENGTHS GIVEN ARE FROM CENTER TO CENTER OF FITTINGS. 7. ALL DIMENSIONS ARE TO FIELD CHECKED, ANY DEVIATIONS FROM THE ARRANGEMENT SHOWN WILL REQUIRE COMPLETE REVIEW OF THE FLOW CALCULATIONS BY THE DESIGNER. 8. REAM AND CLEAN EACH PIPE SECTION INTERNALLY AFTER PREPARATION AND BEFORE ASSEMBLY BY MEANS OF SWABBING, UTILIZING A SUITABLE NON - FLAMMABLE CLEANER. THE PIPING NETWORK SHALL BE FREE OF PARTICULATE MATTER AND OIL RESIDUE BEFORE INSTALLATION OF NOES OR DISCHARGE DEVICES. 9. ALL DISTRIBUTION PIPE AND FITTINGS MUST BE ASSEMBLIED USING PTFE PIPE TAPE DO NOT ADD TO THE FIRST TWO THREADS NEAREST THE END OF THE PIPE. 10. CYLINDERS AND PIPE TO BE SECURELY BRACKETED - ESPECIALLY AT FITTINGS AND NOZZLES. 11. NOT USED 12. SIZE REDUCTION CAN BE ACCOMPLISHED WITH THE USE OF REDUCING BUSHINGS, REDUCING COUPLINGS, REDUCING TEES, OR REDUCING ELBOWS. X HYDRAULIC NODE POINT 8', 4'-3wx 1 -1/4 "0 FM -200 PIPING ISOMETRIC C1 -1 1 SCALE. N.T.S. FILE C9400 C1 -1 B.R. •l� ADDRESS LABEL CLARIFICATION CONTAINER ('C" FOR CYLINDER /'S' FOR SPHERE) ZONE NUMBER CONTAINER NUMBER C2 -1 HARDWARE DATA CALCULATIONS HYDRAULIC gal CALCULATIONS HYDRAULIC gal BBB ■���i� �t -:• ��3�'�'' r -� f Y, .l " 20000636 FL CERT FM 16058100012009 a r W 10 Cl Mi R