10-1042-011EXISTING 8" RD. FOR OUTSIDE AIR INTAKE 20 PLP 1OCFM PLP = 200 CFM EXISTING AHU -1 UNIT TO REMAING AS IS. SEE NOTE -1 THIS SHEET. THIRD FLOOR PLAN -AC 1/4" = 1' -0" 0 1 EXISTING DUCT MAIN IN EXISTING SOFFIT TO REMAIN. SEE NOTE -2 THIS SHEET— EXISTING FANS TO INTONE QT -50 (50 CFM) 4" RD. EXHAUST TO WALLCAP W /W.M.S. EXISTING AHU -2 UNIT TO REMAING AS IS. SEE NOTE -1 THIS SHEET EXISTING 8" RD. FOR OUTSIDE AIR INTAKE 21 PLP 10CFM PLP = 210 CFM VV. STAI RWEL c ii r_a 1- A/C SYSTEMS ARE EXISTING TO REMAIN. A/C CONTRACTOR SHALL INCLUDE IN BID ALL THE NECESSARY LABOR AND MATERIALS FOR A COMPLETE INSPECTION OF THESE SYSTEMS. INCLUDING THE CLEANING OF THE AHU COILS WITH A NON ACIDIC SOLUTION. PROVIDE NEW 1" THICK FILTERS AND CHECK REFRIGERANT GAS. DELIVER AT THE END OF CONSTRUCTION A FULLY WORKING SYSTEM. BALANCE ALL AIR VOLUMES AS SHOWN, PRIOR TO FINAL C.O.; PROVIDE TEST RESULTS TO ENGINEER AND TENANT'S REP. CLEAN CONDENSATE LINES WITH PRESURISED AIR. PROVIDE A FLOAT SWITCH IN DRAIN PAN IF EXISTING UNIT DOES NOT HAVE A SECONDARY CONDENSATE DRAIN. PROVIDE A NEW DUCT SMOKE DETECTOR WITH A VISUAL /AUDIBLE SIGNAL & TEST KEY STATION AS NECESSARY. 2- DIMENSIONS OF EXISTING SUPPLY MAINS ARE THE MIN. REQUIRED. ADJUST SIZES AS NECESSARY. 1 INTERIOR CHANGE 3.7.11 USTAVO SOLAN0, P.E. �nechanical / electrical ..A• .,,.° �1� ;corisulting engineer fla. registration #: 3 4 9 2 3 `Pw 7410 -B sm. 48th. ST., miami, fl. 33155 t t e 1. ( 3 0 5) 6 6 5 - 6 1 5 1 • • s M C2 �0 f 0 92 N� i i ON z Q J Q. 0 a J LL U Q DmAmm ■Y N w�oNas DANK 10 -11 -10 is � Q LL 3: Nz`)o OQr- u Lu .�q(L OC O 03: 1z Lu mHow NO AC 1 or CHAW Na