Loading...
12-250-032AIR CONDITIONING NOTES- 1,— ALL CONDITIONING SUPPLY DUCTSAND FRESH AIR INTAKE DUCTS SHALL HAVE A MANUAL VOLUME BALANCING DAMPER INSTALLED, 2,— ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST LOCAL CODES, FLORIDA BUILDING CODE AND SECTI ❑N 503 OF FLORIDA ENERGY EFICIENCY CODE, 3,— DUCTWORK: RETURN AND SUPPLY PLEUMS TO BE ( +) 1 1/2' FIBERGLASS DUCTBOARD ALL SEAMS AND JOINTS SEALED AND STAPLED WITH SILVER TAPE UL181A,T❑ BE R -6 FLEX DUCT USING SILVER TAPE UL181A AND NYLON PANDUIT STRAPS AT COLLAR CONNECTIONS, ROUND DUCT WORK 4,— AIR CONDITIONING CONTRACTOR SHALL PROVIDE ONE YEAR GUARANTEE ON ALL MATERIAL AND LABOR FURNISHED AND FIVE YEARS ON ALL COMPRESSORS, 5,— ALL FLEX DUCT TO BE HUNG WITH 2' U CHANNEL CONTINUOUS PROVIDE AIR CHAMBERS ON ALL SUPPLIES, 6.— FANS TO BE CONNECTED FOR PROPER SHUT DOWN, 71— RETURN AIR GRILLES ARE FILTERED, 8,— RECTANGULAR DUCTWORK TO BE HUNG WITH 2' U CHANNEL AND METAL STRAP @ 4' ❑ICI 9,— ELECTRICAL CONTROLS AND POWER WIRING UNDER ELECTRICAL CONTRACT. 10,—TEST AND BALANCE, CONRACTOR SHALL TEST AND BALANCE VENTILATI ❑N AND A/C SYSTEMS. DUCT CALCULATI ❑NS SYSTEM 1 EQUAL FRICTION DUCT SIZING= (011 IWG /LENGHT) X 100 L -1 EFDS= (011 IWG/ 24') X 100 = 0,416 IWG CEILINGS R -19 EQUAL FRICTION DUCT SIZING= (011 IWG /LENGHT) X 100 L -2 EFDS= (0.1 IWG/ 30') X 100 = 0.33 IWG CONMENSATE PRAM DUCT CALCULATIONS SYSTEM 2 RETURN DUCT Ceiling EQUAL FRICTI ❑N DUCT SIZING= (011 IWG /LENGHT) X 100 L -1 EFDS= (011 IWG/ 19,5') X 100 = 015128 IWG VrTH FLOAT EI EQUAL FRICTION DUCT SIZING= (011 IWG /LENGHT) X 100 L -2 EFDS= (011 IWG/ 30) X 100 = 0133 IWG 15/15 CONDENSER REFRIGERANT PIPING TO RESPECTIVE AHU 4' CONC. SLAB 3/4' VIBRA PADS / UNIT TO BE SECURE TO CONC. PAD USING 5/16' TAPCON & STRAP TYP OF 4 CONDENSER ATT. DETAIL SCALE: NTS IF APPLICABLE SCREEN NOTES CONTRACTOR WILL DETERMINE ROOF L❑CATI ❑N, CMU WALL CREAREANCESi SIDESi 12' SERV. PANED 36' TOP, 60' 4' PVC PIPE SLEEVE WATERTIGHT SELF FLASHING BASE CAP TO BE COATED WITH TAR IN BOTH SIDES OF THE FLANGE, FLANGE TO LINE FLUSH WITH ROOFTOP AND TO BE SEALED WATERTIGHT WITH TAR. ATTACH DUCT WORK TO CAP AND SEAL AM EMUST, ROOF PENETRATION DETAIIS HVAC LEGEND SUPPLY AIR VjCT DESIGNATION CBS INS. INT. R -4.0. MANUAL DAMPER RIGID POLYSTYRENE THERMOSTAT 3 Y2" ' SUPPLY CEILINGS R -19 RETURN AIR BATTS FIBERGLAS EQUIPMENT DESIGNATION 9 "" SENSOR SMOKE FIRESTAT ■�' EXHAUST FAN i EXISTING FRESH AIR INTAKE CONMENSATE PRAM SUPPLY Broan RETURN DUCT Ceiling SCOOP DAMPER INSULATION TYPES SUPPLY AIR VjCT MFG, CBS INS. INT. R -4.0. 4" RIGID POLYSTYRENE FRAME WOOD ADJACENT R -13, 3 Y2" BATTS FIBERGLAS CEILINGS R -19 6Y4" BATTS FIBERGLAS ATTIC R -30 9 "" BATTS FIBERGLAS TYPICAL HANGING STIR AND SADDLE HANGIN( DETAIL TYPICAL 2 BAR AND WIRE DUCT HANGING DETAIL will i I 1 11 VERTICAL AIR HANDLER NEW SPLIT UNIT SCHEDULE CU -1 & 2 SUPPLY AIR VjCT MFG, LOCATI ❑N MODEL SEER # VOLTAGE OVERCURRENT DEVICE MAX.(2) ] ' 1' 1 , ar C a .Y ] I 1 WALL STRUCTURE C❑ ❑LING CAPCITY (BTU) COIL AM HANDLER FAN BLADE UMT CU -1 EXISTING EXISTING CONMENSATE PRAM ' ] Broan STEEL MY ' Ceiling SECONDARY AuxnIARY PAN 0110 120/1 108 F 3 CU -2 GALVAMED 1 PAN OUTSIDE GRD, ELEV VrTH FLOAT EI - i 1 WIRED LOW YI 11] . 1 AT 2 -18 3/8' 0 PER FT. TO EXTERIOR VERTICAL AIR HANDLER NEW SPLIT UNIT SCHEDULE CU -1 & 2 PLAN MARK MFG, LOCATI ❑N MODEL SEER # VOLTAGE OVERCURRENT DEVICE MAX.(2) MINI CIRCUIT AMPACITY COMPONENTS DATA SCFM C❑ ❑LING CAPCITY (BTU) COIL FAN M ❑TOR FAN BLADE COMPRES ❑R CU -1 EXISTING EXISTING EXISTING Restroom Exhaust Broan QTR110 Ceiling 110 0110 120/1 108 F 3 CU -2 RHEEM OUTSIDE GRD, ELEV RAPM030JEZ 16 208 -230 1PH -60HZ 25/25 17/17 2 -18 3/8' 0 PSC, 018 AMP 1/6 HP 24'0- 3 SCFM -4000 16 LRA - 79 3300 1557 30,000 NEW FAN SCHEDULE MARK SERVICE MFG, Model MTG. CFM ESP In H2O Volt Phase/ Watts F 1 Restroom Exhaust Broan QTR110 Ceiling 110 0110 120/1 108 F 2 Restroom Exhaust Broan QTR110 Ceiling 110 0110 120/1 108 F 3 Restroom Exhaust Broan QTR110 Ceiling 110 0110 120/1 108 z 0 I= I— (n p W ( <L EFL F r''{ C•F F'' ! /f J r� FF { r EXISTING (N.I.C.) f' 3 ---V` R 1 o i } 4 .+n } } 12X12 i 70 CFM € } 10 "0 "e 6 "0 6x12 6 °0 120 CFM / ................ .................... .... F .... .... .......... . ..............................I F< 1 / i ME ,,,'PF F.t \x.,.va.:,ro, ., .............�o,voNw�€ T`` i A inle " A/j F EXIS�NG (R..C.) A. 8� r 1'C.0 . ............................. .... ... € .............. ........ . r , z € 3F VOLTAGE MINI CIRC MAXI BKR, BLOWER 70 CFM i € 8X4 i -' 4 SERVICE VALVE ?mm ,uu ............ .... .... 6 "0 i r m 14c 2 12x10 F .... .... .......... . ..............................I F< 1 / i ME ,,,'PF F.t \x.,.va.:,ro, ., .............�o,voNw�€ T`` i A inle " A/j F EXIS�NG (R..C.) A. 8� r 1'C.0 . ............................. .... ... € .............. ........ . r , z € ` 3 i_ VOLTAGE MINI CIRC MAXI BKR, BLOWER 70 CFM i o 8X4 i -' 4 SERVICE VALVE ?mm ,uu ............ .... .... 6 "0 i r m 14c 2 12x10 v nF 106 S' L LOUVERED DOOR .. 75 CFM t a 1010: ell L n F 70 CFM , 80 6 0 i } i : •?'' 1 iF �F` 1j �':� \••v =w�: y}y � 6x12 120 CFM IK ,fit J" ,t rf Y F`•F /' f \ \:QuS' k 2 r p} {{ EXIST] -6 (N.I.c HATCHED ..AREA /INDICATES Fr EXISTING G (N:F.FC.) } ? rN.\ 'w`.,,vx.,,vauW:.,,,,��5• 'w`"i,,, ..... �. :$V.VT� 1 \„se,'"`...��.v. \ \,WT` �� \,.,�,v.�„v. vtu,1u; �: z (n X MECHANICAL PLAN SEE SHEET A -1 SITE PLAN FOR OVERALL FLOOR PLAN 10 °0 6 "0 } 70 CFM 6'0 m € 8X4 ROOF Cup i vI F F2 € r 6 00 0 CFM r X4 { € INQ A!H 10.0 12X12 70 CFM A J v €E 6' A.G. MIN. z 0 0 <r 1/411 = 1' -0" NEW AC AHU UNIT -1 & 2 PLAN MFG, LOCATION MODEL VOLTAGE MINI CIRC MAXI BKR, BLOWER COMPONENTS CONNECTORS DATA NOMINAL RATINGS BLOWER SERVICE VALVE COOLING (BTH /H) CFM MARK m SEER # s AMPACITY SIZE MOTOR AHU -1 W � o° W Y Y � O AHU -2 RHEEM FLOOR 400 Z O 208 -230 217/410 15/15 FLA 2,5 10 5/8'0 LIQUID 3/8' 30,000- 36,000 H -1,151 MOUNT RHLLHM3617IA HP 1/3 DRAIN FTP 3/4' SUCTION 7/8' 215 T❑ 3 TON M- 1012 '/ . Ld 1PH -60HZ ea, • .-� O a L- 900 WALL❑WABLE RANGE PER FMC: 100 -115% OF DESIGN CAPACITY ADDRESS 7011 SW 68 CT. S. MIAMI FLORIDA LEGAL DESCRIPTION LOT 2 OF SUNSET CIRCLE ACCORDING TO THE PLAT BOOK 48 PAGE 5 MIAMI —DADE COUNTY, FLORIDA DO NOT SCALE DRAWINGS, USE GIVEN DIMENSION REPORT. ANY DISCREPANCIES ON DIMENSION REPORT TO THE ARCHITECT OR CONSTRUCTION SUPERINTENDENT BEFORE PROCEEDING WITH WORK. THESE PLANS ARE IN COMPLIANCE WITH THE 2007 FLORIDA BUILDING CODE AND 2009 SUPPLEMENT INCLUDING SECTION 1609 FOR 140 MPH BASIC WIND SPEED 3— SECOND GUST AND EXPOSURE "B" WIND ZONE lilt. I�i=� oepffler —VAN HEMERT SHEET i M -1 Fr XX 13 _m M M ° CL? (ri V b m s J r W � o° W Y Y � O w 400 Z O Min O v 1O oepffler —VAN HEMERT SHEET i M -1 Fr XX 13 _m CL? V b s r cry '/ . Ld ea, • oepffler —VAN HEMERT SHEET i M -1 Fr XX 13 _m CL? V b cry Ld o • .-� O a oepffler —VAN HEMERT SHEET i M -1 Fr XX 13 _m