12-250-025GENERAL STRUCTURAL NOTES 1.- DESIGN CRITERIA DESIGN LIVE LOADS: A.- FLORIDA BUILDING CODE 2010 FLOOR LIVE LOAD (RESIDENTIAL) = 40 PSF B,- ASCE 7 -10 ROOF LIVE LOAD = 30 PSF BASIC WIND SPEED: 175 MPH EXPOSURE C TERRACE & BALCONIES LIVE LOAD (OVER 100 SF) = 100 PSF IMPORTANCE FACTOR : 1.0 CATEGORY II STAIRS (RESIDENTIAL) = 80 PSF C,- ACI 318 -05 D.- CONCRETE MANONRY DESIGN DEAD LOADS: ACI 530 ADDITIONAL SUPERIMPOSED FLOOR DEAD LOAD = 35 PSF ASTM C90 -70 E.- NOS 1991 REVISED EDITION ROOF DEAD LOAD = 25 PSF 2.- SOIL STATEMENT: BASED ON VISUAL OBSERVATION AT THE SITE WHERE THE RESIDENCE WILL BE CONSTRUCTED, THE SOIL CONSISTS OF A MIX OF SAND AND UMEROCK WITH AN APPROXIMATE BEARING CAPACITY OF 2,000 PSF WHICH WILL BE THE SOIL DESIGN PRESSURE FOR WHICH THE FOUNDATIONS DESIGN WILL BE BASED ON. A LETTER SHALL BE SUBMITTED BY THE ENGINEER OF RECORD AT THE TIME OF FOUNDATION EXCAVATION CONFIRMING THAT THE SOIL HAS THE CAPACITY FOR WHICH THE FOUNDATIONS WERE DESIGNED. 3.- CONCRETE: FOUNDATIONS, GROUND SLAB AND ALL STRUCTURAL ELEMENTS (BEAMS, COLUMNS, FLOOR SLABS AND STAIRS) PROVIDE SPACING AT PANEL EDGES 4' x 8' COX PLYWOOD ALL CONCRETE SHALL ATTAIN A MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF 5,000 IN 28 DAYS SHEATHING MIN. 5/8" WITH A W/C RATIO OF 0.4. AGGREGATES TO BE CLEAN AND WELL GRADED, MAXIMUM SIZE THICK MAX. SPAN 24" TO BE 1 . CONCRETE SLUMP 3 MINIMUM TO 5 MAXIMUM. VERTICAL CONCRETE DROP NOT TO EXCEED 8. TYPES 4.- CONCRETE COVER: 1 -1/2 1 1/2" TO BE AS FOLLOWS: BOTTOM TOP SIDES SP 1i EE � � „ FOOTINGS 3" 2" 2" " BEAMS 1 -1/2" 1 -1/2" 1 -1/2" PROVIDE 2x4 BLOCKING COLUMNS - -- - -- 1 -12 ®ALL PLYWOOD SEAMS SLABS 1" 3/4- 1./ ATTACH WITH (2) 16D WALLS - -- - -- 1 -1/2- NAILS TO EACH TRUSS. CANT ILEVER TOP BARS CONT. TOP BARS FASTEN PLYWOOD TO 5.- REINFORCING STEEL: BLOCKING WITH 10d NAILS TO BE NEW HIGH STRENGTH BILLET STEEL DEFORMED AS PER ASTM A -305 AND AT 4" O.C. CONFORMING TO ASTM A -615, GRADE 60. LAP CONTINUOUS BARS 30 -BAR 1� DIAMETERS, UNLESS OTHERWISE NOTED IN PLANS. HOOK DISCONTINUOUS ENDS 2x WOOD FASCIA SEE TYPICAL WALL OF ALL TOP BARS. REINFORCING STEEL TO BE DETAILED AND FABRICATED IN "MANUAL SECTION NAILED W/ 2 -16d NAILS ACCORDANCE WITH OF STANDARDS PRACTICE OF DETAILING REINFORCING CONCRETE STRUCTURES -, AND THE ACI BUILDING CODE 318, LATEST EDITION. 0 EACH TRUSS 6 MASONRY BLOCK it" SPACE AT PANEL ENDS CONCRETE BLOCK COLUMNS TO BE ERECTED PRIOR TO PLACING CONCRETE IN ADJACENT BEAMS. ALL CONCRETE BLOCK TO BE GRADE N -1, CONFORMING TO ASTM C -90 WITH A fc = 1,900 PSI (MINIMUM). PROVIDE No. 9 GAGE GALVANIZED. STEEL LADDER TYPE JOINT REINFORCING AT EVERY OTHER COURSE FOR ALL MASONRY BLOCK WALLS. PROVIDE ■ FOOTING TYPES TYPICAL BAR DIAGRAM 1 -1/2 1 1/2" TYP. BAR SP 1i EE � � „ WF TSE TS CF OR — R CANTILEVER 'L" COLUMN - o "GREA > o —) WHI EVER R GIRDER TRUSS CONNECTION DETAIL _ Ty CONC, CONC. COLUMN THREE PLY iTRUSS MF MONOLITHIC FOOTING 3/4" NON- SHRINKING I ( GROUNG L - L —_ CANT ILEVER TOP BARS CONT. TOP BARS S 'E' BAR OVER TERIOR PORT LEFT OR RIGHT STD. 90 DEG. HOOKS BAR SIZE - MIN. LAS „SFLICE w AT BOTTOM TO ENSURE PROPER (USE 4 0 3/4- DIA,) 1� GIRDER TRUSS a (2) 5/8" DIA. x 4 -1/2" EMBEDMENT FOR TWO PLY G.T. (4) 3/4" DIA, x 5" EMBEDMENT FOR THREE PLY G.T. 2� 3/4" STEEL PLATE `J (1) 5/8" DIA. THRU BOLT Q TOP PLATE 1/4" FOR TWO PLY G.T., 3/8" FOR THREE PLY G.T. (, CONCRETE TIE BEAM MIN. 3,000 PSI Y `0 O ru Q o _ 0 0 Q BOTTOM BARS CONT. BARS 5 6 26 31” 0 8" x 8" x 16" CONCRETE EMBED 12 BAR DIAM, EMBED 12 BAR DIAM. 17 39" MASONRY BLOCK 11 -x-11 C 8 51" 9 65" WALL FOOTING THICK. SLAB EDGE THICKENED SLAB COLUMN FOOTING TYP. CONC. COVER NOTE: WHERE NECESSARY CONTINOUS TOP BARS SHALL BE LAPPED 24 BAR DIAMETERS IN MIDDLE 1/3 OF SPAN WELDED WIRE MESH ON CLEAN 110 82" of Sm so %� LI �Ij I.� - ��►�'►�I FP? :. 1 - # 5 T & B CORNER BARS AT ALL BEAM INTERSECTIONS, EXTEND 30 INTO BEAMS EACH SIDE. 2•x4' #2 SOUTHERN YELLOW PINE CROSS BRACING MEMBERS FASTENED TO TRUSSES W /2 -16d NAILS EACH END (REFER TO TRUSS NOTES, TRUSS LAYOUT 7.- REINFORCED MASONRY AND NOTE BELOW FOR LOCATION)OR O 20' -0. O.0 MAX ALL CONCRETE BLOCK TO BE GRADE N -1, CONFORMING TO ASTM C -90 WITH A MINIMUM PRISM STRENGTH (fm) = 1,500 psi. ALL UNITS SHALL BE BUILT TO PRESERVE THE VERTICAL CONTINUITY OF THE CELLS TO BE FILLED, AND MUST MAINTAIN A CLEAR, UNOBSTRUCTED CONTINUOUS VERTICAL CELL MEASURING 2 INCHES BY 3 INCHES MINIMUM. CLEANOUT OPENINGS MUST BE PROVIDED AT ALL CELLS TO BE FILLED. MAXIMUM HEIGHT OF GROUTING LIFTS IS 4' -0 ". THE VERTICAL REINFORCEMENT MUST HAVE A MINIMUM 60 INCH LAP SPLICE VISIBLE ABOVE THE UPPERMOST CELL WHERE STRUCTURE IS TO CONTINUE VERTICALLY, INTERMEDIATE LAPS IN CONCEALED WALL AREAS ARE NOT PERMITTED. ALL CONCRETE USED FOR GROUTING SHALL BE PEAROCK WITH A COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS. SUBMIT MIX DESIGN FOR APPROVAL MORTAR SHALL BE TYPE M, WITH A MINIMUM STRENGTH OF 2,500 PSI. \ \\ I I SLUMP TO BE 7" TO 9 -. BLOCK UNITS SHALL HAVE A MINIMUM COMPRESION STRENGTH Pc= 1,900 psi. 8.- SLAB ON FILL: I FILL AND BACKFILL TO BE COMPACTED TO 95% OF THE MODIFY PROCTOR DENSITY TEST (ASTM D- 1557). COMPACTION LAYERS NOT TO EXCEED 12 -. BACKFILL MATERIAL TO BE NOTE, APPROVED BY SOIL ENGINEER. GENERAL CONTRACTOR TO FOLLOW CLOSELY THE SOIL PREPARATION INSTRUCTIONS CONTAINED IN THESE PLANS, SEE "SOIL PREPARATION INSTRUCTIONS ". 1 "x4' CONT. LATERAL WOOD BRACING NAILED TO BOTTOM CHORD MAXIMUM 8' -0' SLABS ON FILL TO BE PLACED ON A CHECKERBOARD PATTERN, WITH POURS LIMITED TO SPACING AND AS REQUIRED BY TRUSS MANUFACTURER (REFER TO TRUSS NOTES 600 S.F. AND 30 FEET IN ANY DIRECTION. WAIT 24 HOURS BETWEEN POURS, AS AN ALTERNATIVE AND TRUSS LAYOUT FOR LOCATION) SLABS MAY BE POURED CONTINUOSLY, HOWEVER, MUST BE SAW CUT SAME DAY IT IS PLACED. PROVIDE VAPOR BARRIER BELOW ALL SLABS ON FILL (10 MIL), 9.- PRE - FABRICATED WOOD TRUSSES: SHALL BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE TRUSS PLATE INSTITUE (T.P.I.), LATEST EDITION, TRUSSES TO BE ERECTED FOLLOWING THE GUIDELINES OF THE T.P.I. PUBLICATION BWT -76, SUBMIT LAYOUT PLAN AND INDIVIDUAL TRUSS DRAWINGS FOR EACH DIFFERENT TRUSS, SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR APPROVAL BY STRUCTURAL ENGINEER PRIOR TO FABRICATION. DESIGN THE WOOD TRUSSES AND PROVIDE CALCULATIONS FOR THE FOLLOWING LOAD CASES: 1. ROOF GRAVITY: TOP CHORD LIVE LOAD = 30 PSF. 4" CONC. SLAB ON FILL W 6x6 TOP CHORD DEAD LOAD = 20 PSF. W1.4xW1, 4 W. W.F. BOTTOM CHORD DEAD LOAD = 10 PSF. TOP OF FIN. FL ADDITIONAL BOTTOM CHORD PANEL POINT LOAD = 200 PSF. LEV. 0'-0" NOTE: ZERO (0) PER CENT (%) STRESS INCREASE FOR LUMBER AND PLATES. 2. ROOF NET UPLIFT: SEE ROOF FRAMING PLAN COMPACTED NOTE: 33 PER CENT (7.) STRESS INCREASE FOR LUMBER FILL OVERSTRESSING OF WOOD FOR WIND DESIGN IS ALLOWED BUT IS NOT ALLOWED TO 8" CONCRETE REINF MASONRY BLOCK WALL W / #9 HORIZ JOINT REINF @ 16" O.C. w GRADE a V) Z a 00 o 5 1'x4- CONT. LATERAL WOOD BRACING NAILED TO BOTTOM CHORD MAXIMUM 8' -0- SPACING AND M REQUIRED BY TRUSS MANUFACTURER (REFER TO (2) 16d NAILS TRUSS NOTES AND TRUSS LAYOUT FOR LOCATION EACH MEMBER 24 "o.c. (OVERLAP O SPLICES) \"-PRE-ENC4NEERED WOOD OVERSTRESS TRUSS METAL PLATES AS PER ASCE 7 -05, 3„ GENERAL CONTRACTOR TO PROVIDE PERMANENT LATERAL BRACING OF THE BOTTOM CHORD CONCRETE FOOTING (See AND THE WEB MEMEBERS IN ACCORDANCE WITH RECOMMENDATIONS OF T.P.I. BWT -76 AND THE Schedule for Size & Reinf.) REQUIREMENTS OF THE INDIVIDUAL TRUSS DESIGNS. SUBMIT PERMANENT BRACING PLAN FOR REINFORCED BLOCK WALL TO FOOTING D E TA I L APPROVAL BY ENGINEER PRIOR TO ERECTION. GENERAL CONTRACTOR TO SUBMIT SIGNED AND SEALED SHOP DRAWINGS BY A FLORIDA REGISTERED PROFESSONAL ENGINEER FOR ALL TRUSS TO TRUSS CONNECTIONS. SCALE: N.T.S. 10.- SHOP DRAWINGS: NO SHOP DRAWING SHALL BE SUBMITTED FOR ARCHITECT /ENGINEER'S REVIEW UNTIL AFTER THEY HAVE BEEN REVIEWED AND NOTED FOR CONSTRUCTION METHOD, DIMENSIONING, AND OTHER TRADE REQUIREMENTS BY THE CONTRACTOR, AND STAMPED WITH THE CONTACTOR'S APPROVAL SEAL. ENGINEER ASSUMES NO RESPONSABILITY FOR DIMENSIONS, QUANTITIES, ERRORS OR OMOSSIONS, AS A RESULT OF CHECKING AND REVIEWING ANY SHOP DRAWINGS. ANY ERRORS OR OMISSIONS MUST BE MADE GOOD BY CONTRACTOR, IRRESPECTIVE OF RECEIPT, CHECKING OR REVIEW OF DRAWINGS BY ENGINEER, AND EVEN THOUGH WORK IS DONE IN ACCORDANCE WITH SUCH SHOP DRAWINGS. 11.- WOOD MEMBERS: ALL STRUCTURAL WOOD MEMBERS TO BE SAWN LUMBER. 'DIMENSIONS LUMBER TO BE 'SOUTHERN PINE ' WITH A MINIMUM COMMERCIAL GRADE OF 'NO. 2'. DESIGN BENDING STRESS OF Fb= 1200 PSI ALL WOOD MEMBERS TO BE FREE OF ALL IMPERFECTIONS AS, SPLITS, CHECKS, OR EXCESSIVE KNOTS. UNSATISFACTORY MATERIALS TO BE REPLACE AT NO COST TO THE OWNER. ALL MEMBERS IN CONTACT WITH CONCRETE OR EXPOSED TO THE ELEMENTS, TO BE PRESSURE TREATED. COLUMN REINFORCING -� 1/2" EXPANSION JOINT 2 "CL 4" CONC. SLAB ON FILL W 6x6- W1.4xW1.4 W.W.F. Q TOP OF FIN. FL. 0° ELEV. 0'-0" TIES CONC. COLUMN See Schedule DOWELS -SAME SIZE & NUMBER AS COL. REINF. •.x COLUMN DOWELS -SAME SIZE & NUMBER AS COL. REINFORCEMENT -SET DOWELS WITH HIGH STRENGTH EPDXY IN 4" DEEP DRILLED HOLES IN EXIST. CONCRETE BEAM COLUMN REINFORCING TIES 2 "CL CONC. COLUMN See Schedule 0 COLUMN DOWELS -SAME Q SIZE & NUMBER AS COL. TOP OF FIN. FL. m REINFORCEMENT -SET ELEV. 0--0 to - • : x X: DOWELS WITH HIGH x I ,�, STRENGTH EPDXY IN 6" ..,v DEEP DRILLED HOLES IN �, -- -s EXIST. FOOTING EXISTING CONCRETE �� -- COMPACTED FOOTING I ` ONCRETE FOOTING FILL See Schedule for iize & Reinf.) NEW CONCRETE COLUMN TO EXISTING FOOTING NEW CONCRETE COLUMN TO FOOTING DETAIL AND TIE BEAM DETAIL SCALE: N.T.S. SCALE: N.T.S. PRE - ENGINEER[ ROOF TRUSSES @24" O.C. HURRICANE STRAP SEE SCHEDULE 3 12 I.f..yl :r is STEEL COLUMN BOTT PLATE DETAIL NTS 4- 5/8" DIAM, x6" LG HEAD STUDS WELDED TO PLATE HSS 3.5 "x3.5 "x1/4" 3" x 12" x 5/8" SM- PLATE )OD BEAM NAM THRU BOLT EACH BEAM TEAMS OVER SUPPORT) STEEL PLATE BOTH SIDES HIGH X 8" LONG X 6" X 8" TOP STL PLATE 3.5%3.5%1 /4" "OM STL PLATE SEE DETAIL 5/4- DIAM. HEAD STUDS EMB,: 6" STEEL COLUMN CONNECTION DETAIL SCALE: 1" = 1' -0" TOP OF BEAM SEE BEAM SCHEDULE 11 V .TYP -+ 3 R '<R. w (Typ) TOP OF CONC. (TYP) ,K BEAM a 2 ; a 2 T1 -2 -1/8" 4 FI LE:knoepffier- Hemert DRAWN: G.A.R. 1 -1/2 1 1/2" DATE: 01 -20 -12 SECTION TWO PLY TRUSS (MAX. UPLIFT= 5,480 #) ° A a OF (USE 2 0 5/8" DIA.) EDGE _....EDGE OF GIRDER TRUSS CONNECTION DETAIL o CONC, CONC. COLUMN THREE PLY iTRUSS SCALE: 1" = 1' -0" N N COLUMN (MAX. UPLIFT= 14,400 #) Li Q w AT BOTTOM TO ENSURE PROPER (USE 4 0 3/4- DIA,) 1� GIRDER TRUSS a (2) 5/8" DIA. x 4 -1/2" EMBEDMENT FOR TWO PLY G.T. 1'x4- CONT. LATERAL WOOD BRACING NAILED TO BOTTOM CHORD MAXIMUM 8' -0- SPACING AND M REQUIRED BY TRUSS MANUFACTURER (REFER TO (2) 16d NAILS TRUSS NOTES AND TRUSS LAYOUT FOR LOCATION EACH MEMBER 24 "o.c. (OVERLAP O SPLICES) \"-PRE-ENC4NEERED WOOD OVERSTRESS TRUSS METAL PLATES AS PER ASCE 7 -05, 3„ GENERAL CONTRACTOR TO PROVIDE PERMANENT LATERAL BRACING OF THE BOTTOM CHORD CONCRETE FOOTING (See AND THE WEB MEMEBERS IN ACCORDANCE WITH RECOMMENDATIONS OF T.P.I. BWT -76 AND THE Schedule for Size & Reinf.) REQUIREMENTS OF THE INDIVIDUAL TRUSS DESIGNS. SUBMIT PERMANENT BRACING PLAN FOR REINFORCED BLOCK WALL TO FOOTING D E TA I L APPROVAL BY ENGINEER PRIOR TO ERECTION. GENERAL CONTRACTOR TO SUBMIT SIGNED AND SEALED SHOP DRAWINGS BY A FLORIDA REGISTERED PROFESSONAL ENGINEER FOR ALL TRUSS TO TRUSS CONNECTIONS. SCALE: N.T.S. 10.- SHOP DRAWINGS: NO SHOP DRAWING SHALL BE SUBMITTED FOR ARCHITECT /ENGINEER'S REVIEW UNTIL AFTER THEY HAVE BEEN REVIEWED AND NOTED FOR CONSTRUCTION METHOD, DIMENSIONING, AND OTHER TRADE REQUIREMENTS BY THE CONTRACTOR, AND STAMPED WITH THE CONTACTOR'S APPROVAL SEAL. ENGINEER ASSUMES NO RESPONSABILITY FOR DIMENSIONS, QUANTITIES, ERRORS OR OMOSSIONS, AS A RESULT OF CHECKING AND REVIEWING ANY SHOP DRAWINGS. ANY ERRORS OR OMISSIONS MUST BE MADE GOOD BY CONTRACTOR, IRRESPECTIVE OF RECEIPT, CHECKING OR REVIEW OF DRAWINGS BY ENGINEER, AND EVEN THOUGH WORK IS DONE IN ACCORDANCE WITH SUCH SHOP DRAWINGS. 11.- WOOD MEMBERS: ALL STRUCTURAL WOOD MEMBERS TO BE SAWN LUMBER. 'DIMENSIONS LUMBER TO BE 'SOUTHERN PINE ' WITH A MINIMUM COMMERCIAL GRADE OF 'NO. 2'. DESIGN BENDING STRESS OF Fb= 1200 PSI ALL WOOD MEMBERS TO BE FREE OF ALL IMPERFECTIONS AS, SPLITS, CHECKS, OR EXCESSIVE KNOTS. UNSATISFACTORY MATERIALS TO BE REPLACE AT NO COST TO THE OWNER. ALL MEMBERS IN CONTACT WITH CONCRETE OR EXPOSED TO THE ELEMENTS, TO BE PRESSURE TREATED. COLUMN REINFORCING -� 1/2" EXPANSION JOINT 2 "CL 4" CONC. SLAB ON FILL W 6x6- W1.4xW1.4 W.W.F. Q TOP OF FIN. FL. 0° ELEV. 0'-0" TIES CONC. COLUMN See Schedule DOWELS -SAME SIZE & NUMBER AS COL. REINF. •.x COLUMN DOWELS -SAME SIZE & NUMBER AS COL. REINFORCEMENT -SET DOWELS WITH HIGH STRENGTH EPDXY IN 4" DEEP DRILLED HOLES IN EXIST. CONCRETE BEAM COLUMN REINFORCING TIES 2 "CL CONC. COLUMN See Schedule 0 COLUMN DOWELS -SAME Q SIZE & NUMBER AS COL. TOP OF FIN. FL. m REINFORCEMENT -SET ELEV. 0--0 to - • : x X: DOWELS WITH HIGH x I ,�, STRENGTH EPDXY IN 6" ..,v DEEP DRILLED HOLES IN �, -- -s EXIST. FOOTING EXISTING CONCRETE �� -- COMPACTED FOOTING I ` ONCRETE FOOTING FILL See Schedule for iize & Reinf.) NEW CONCRETE COLUMN TO EXISTING FOOTING NEW CONCRETE COLUMN TO FOOTING DETAIL AND TIE BEAM DETAIL SCALE: N.T.S. SCALE: N.T.S. PRE - ENGINEER[ ROOF TRUSSES @24" O.C. HURRICANE STRAP SEE SCHEDULE 3 12 I.f..yl :r is STEEL COLUMN BOTT PLATE DETAIL NTS 4- 5/8" DIAM, x6" LG HEAD STUDS WELDED TO PLATE HSS 3.5 "x3.5 "x1/4" 3" x 12" x 5/8" SM- PLATE )OD BEAM NAM THRU BOLT EACH BEAM TEAMS OVER SUPPORT) STEEL PLATE BOTH SIDES HIGH X 8" LONG X 6" X 8" TOP STL PLATE 3.5%3.5%1 /4" "OM STL PLATE SEE DETAIL 5/4- DIAM. HEAD STUDS EMB,: 6" STEEL COLUMN CONNECTION DETAIL SCALE: 1" = 1' -0" TOP OF BEAM SEE BEAM SCHEDULE 11 V .TYP -+ 3 R '<R. w (Typ) TOP OF CONC. (TYP) ,K BEAM a 2 ; a 2 T1 -2 -1/8" 4 SHINGLE ROOFING SYSTEM (BATCH EXISTING) OVER 151 AND 301 ROOFING FELT, 1/2" C.D.X. PLYWOOD SHEATHING (4 PLY MIN.) AND PRE - ENGINEER WOOD TRUSSES AT 24" .C. (TYPICAL) 12 TRUSS BEARING 3 MATCH EXISTING POINT -� [ FIELD VERIFY EXISTING OVERI TO BE REMOVE \8" x 12" CONC. BM. W/ 4 #5'S CONT. (LAP STEEL 18" MIN. AT SPLICES) PROVIDE HOR. JOINT REINFORCING EVERY SECOND COURSE (16" VERT.). No. 9 GA LADDER TYPE EXTEND 4" INTO TIE COLUMNS #6 INFILLED CELL ® 32" O.C. MAX. \\ TYP. WALL SECTION `r FOR LEGEND SEE TYPICAL WALL SECTION -THIS SHEET 1/2t' = 1' -0" NEW CONC.- = TIE BEAM NEW BLOCK - WALL LO_- 00 2 -20 TOP PLATE 2 -2x4 CONT. NAILER OVER EX. PLYWD & TRUSSES_ SECTION - EXISTING CEILING BOAR (N.I.C.) CRICKET 4' -8" -EXISTING TIE BEAM (N.I.C.) FOR LEGEND SEE TYPICAL WALL SECTION -THIS SHEET 1/21# = V -0" #3 STIRRUPS PER SCHEDULE (SPACE AT 6" WHEN GIRDER TRUSS BEARS ON , 4- #5 CONT yOPENING ABOVE DOOR OR WINDOWS) 17, t ADD 2- #5; OVER WIN OW OR DOOR OPENINGS 1 8_" 1110 001 i CONC. TIE BEAM -- OPENING t ;I gpi Ig� 98 We- t;x FI LE:knoepffier- Hemert DRAWN: G.A.R. 1 -1/2 1 1/2" DATE: 01 -20 -12 SECTION TWO PLY TRUSS (MAX. UPLIFT= 5,480 #) ° ►�i OF (USE 2 0 5/8" DIA.) EDGE _....EDGE OF GIRDER TRUSS CONNECTION DETAIL o CONC, CONC. COLUMN THREE PLY iTRUSS SCALE: 1" = 1' -0" (/ COLUMN (MAX. UPLIFT= 14,400 #) Li Q w AT BOTTOM TO ENSURE PROPER (USE 4 0 3/4- DIA,) 1� GIRDER TRUSS a (2) 5/8" DIA. x 4 -1/2" EMBEDMENT FOR TWO PLY G.T. (4) 3/4" DIA, x 5" EMBEDMENT FOR THREE PLY G.T. 2� 3/4" STEEL PLATE `J (1) 5/8" DIA. THRU BOLT Q TOP PLATE 1/4" FOR TWO PLY G.T., 3/8" FOR THREE PLY G.T. (, CONCRETE TIE BEAM MIN. 3,000 PSI SHINGLE ROOFING SYSTEM (BATCH EXISTING) OVER 151 AND 301 ROOFING FELT, 1/2" C.D.X. PLYWOOD SHEATHING (4 PLY MIN.) AND PRE - ENGINEER WOOD TRUSSES AT 24" .C. (TYPICAL) 12 TRUSS BEARING 3 MATCH EXISTING POINT -� [ FIELD VERIFY EXISTING OVERI TO BE REMOVE \8" x 12" CONC. BM. W/ 4 #5'S CONT. (LAP STEEL 18" MIN. AT SPLICES) PROVIDE HOR. JOINT REINFORCING EVERY SECOND COURSE (16" VERT.). No. 9 GA LADDER TYPE EXTEND 4" INTO TIE COLUMNS #6 INFILLED CELL ® 32" O.C. MAX. \\ TYP. WALL SECTION `r FOR LEGEND SEE TYPICAL WALL SECTION -THIS SHEET 1/2t' = 1' -0" NEW CONC.- = TIE BEAM NEW BLOCK - WALL LO_- 00 2 -20 TOP PLATE 2 -2x4 CONT. NAILER OVER EX. PLYWD & TRUSSES_ SECTION - EXISTING CEILING BOAR (N.I.C.) CRICKET 4' -8" -EXISTING TIE BEAM (N.I.C.) FOR LEGEND SEE TYPICAL WALL SECTION -THIS SHEET 1/21# = V -0" #3 STIRRUPS PER SCHEDULE (SPACE AT 6" WHEN GIRDER TRUSS BEARS ON , 4- #5 CONT yOPENING ABOVE DOOR OR WINDOWS) 17, t ADD 2- #5; OVER WIN OW OR DOOR OPENINGS 1 8_" 1110 001 i CONC. TIE BEAM -- OPENING t ;I gpi Ig� 98 We- t;x ROBERT A. GUZMAN, P.E. 15966 S.W. 98TH STREET, MIAMI, FLORIDA 33196 TEL 305 - 519 -4357, FAX. 305 -408 -1095 FL REG. No. 52647 TYP. GROUT FILLED MASONRY CELL DETAIL N.T.S. ADDRESS 7011 SW 68 CT. S. MIAMI FLORIDA LEGAL DESCRIPTION LOT 2 OF SUNSET CIRCLE ACCORDING TO THE PLAT BOOK 48 PAGE 5 MIAMI -DADE COUNTY, FLORIDA PROD No:10 -13 -11 FI LE:knoepffier- Hemert DRAWN: G.A.R. 3" X 3" CLEAR UNOBSTRUCTED OPENING DATE: 01 -20 -12 M ►�i (1)# 5 IN 3000 PSI GROUT o LL FILLED CELL. PROVIDE CLEANOUT (/ Li Q w AT BOTTOM TO ENSURE PROPER 4 CAID O FILL ADD WEEP HOLES AT 1/3 F�R AND 2/3 OF SPAN HOOK REINF. t� W BAR 12" AT TOP AND BOTTOM 4 Y `0 O ru Q o _ 0 0 Q to cc5 0 8" x 8" x 16" CONCRETE r f� 4- MASONRY BLOCK m C Co 4" CONCRETE SLAB W/ 6x6 #10/10 0 W WELDED WIRE MESH ON CLEAN • COMPACTED FILL o: q o a R-'--1 t •' •' - VAPOR BARRIER LJ., CN \>. \�\ \ , \�\ \� MONOLITHIC CONCRETE FOOTING �I (REFER TO FOOTING SCHEDULE) ROBERT A. GUZMAN, P.E. 15966 S.W. 98TH STREET, MIAMI, FLORIDA 33196 TEL 305 - 519 -4357, FAX. 305 -408 -1095 FL REG. No. 52647 TYP. GROUT FILLED MASONRY CELL DETAIL N.T.S. ADDRESS 7011 SW 68 CT. S. MIAMI FLORIDA LEGAL DESCRIPTION LOT 2 OF SUNSET CIRCLE ACCORDING TO THE PLAT BOOK 48 PAGE 5 MIAMI -DADE COUNTY, FLORIDA PROD No:10 -13 -11 FI LE:knoepffier- Hemert DRAWN: G.A.R. CHECKED: A.K. DATE: 01 -20 -12 M ►�i Ln o LL a (/ Li Q w 4 CAID O F�R t� w L� 4 Y `0 O Q o _ 0 0 o0 to cc5 0 f� 4- Z m C 3 0 W o: q o a R-'--1 J W V) Li t WLO M ►�i Ln o LL (/ Li Q w 4 CAID O w� t� w L� 4 Y `0 O Q o _ 0 o0 to J W V) Li oepffler -rtAN HF- 1,AERI SHEE r k t c=> CAID t� cc5 f� 4- o C 3 CA a R-'--1 oepffler -rtAN HF- 1,AERI SHEE r k t