Loading...
12-72-001FIRE ALARM INSTALLATION & OPERATION NOTES: FIRE ALARM SEQUENCE OF OPERATION: ACTUATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT DETECTOR OR WATER FLOW SWITCH SHALL CAUSE THE FOLLOWING OPERATIONS TO OCCUR; 1. GENERAL ALARM ACTIVATION OF ALL PROGRAMMED SIGNAL CIRCUITS, ON FLOOR OF INCIDENCE AND FLOOR ABOVE AND BELOW. (IF MULTIPLE FLOORS) 2. LIGHT THE ASSOCIATED INDICATORS CORRESPONDING TO ACTIVE SIGNAL CIRCUITS. 3. A GENERAL ALARM SHALL BE ANNUNICATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH & DETECTION DEVICE. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF A DETECTION OR MANUAL DEVICE. A SUPERVISORY SIGNAL SHALL ANNUNCIATE ANY TAMPER, HVAC, OR DUCT DETECTOR ACTIVATION. 4. IF MULTIPLE FLOORS, EACH ELEVATOR LOBBY, HOIST, AND MACHINE ROOM SMOKE DETECTOR SHALL INITIATE AN ALARM CONDITION IN THE BUILDING AND RETURN ALL ELEVATORS TO THE PRIMARY OR ALTERNATE FLOOR OF EGRESS IN COMPLIANCE WITH ANSI ASME Al 7.1. 5. WATERFLOW SWITCH SHALL ACTIVATE GENERAL ALARM. A VALVE TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY ALARM INDICATION. 6. ANNUNCIATION OF THE ACTIVE DEVICE AT THE FIRE ALARM CONTROL PANEL AND ANY ANNUCIATORS, IN MONITORED BUILDING, SEND A SIGNAL TO THE U.L. LISTED CENTRAL STATION FOR ALARM, TROUBLE, WATERFLOW AND SUPERVISORY CONDITIONS. FIRE ALARM SPECIFICATIONS: ALL EQUIPMENT TO BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE COMPATIBLE WITH THE SYSTEM BEING USED. SYSTEM IS TO BE POWER LIMITED. SYSTEM TO BE CERTIFICATED STATION SERVICE AS PER NFPA -72. FIRE ALARM PANEL SHALL BE LISTED FOR CENTRAL STATION SERVICE PER NFPA 72, 2002, SECTION 8.3, UNLESS OTHERWISE SPECIFIED. THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM MANUFACTURER AND ARTICLE 760 OF THE NATIONAL ELECTRICAL CODE. MINIMUM WIRE SIZE IS 12 AWG FOR GROUND CONNECTION. (NOTE: PANEL NEUTRAL OR CONDUIT GROUND IS NOT ACCEPTABLE). ALL STROBE LIGHTS SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM AND SHALL BE SYNCHRONIZED IN OPEN AREAS. ALL AUDIBLE SIGNALS SHALL HAVE THREE PULSE TEMPORAL PATTERN AND SOUND LEVEL SHALL BE AT LEAST 15 DBA ABOVE AMBIENT SOUND LEVEL AND HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FT ABOVE THE FLOOR IN OCCUPIED AREAS. FIRE ALARM CIRCUITS AND DEVICES SHALL BE CLASS "B ". ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. AND N.E.C. 760. CONNECTIONS TO LIGHTS AND POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT. THE CIRCUIT AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING AND BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND BE PER N.F.P.A. 72 2002 EDITION THE FIRE ALARM PANEL IS PROVIDED WITH STANDBY BATTERY PER N.F.P.A. 72 WITH 24 HOURS OF STANDBY AND 15 MINUTES OF ALARM (AS REQUIRED). SHOULD LOSS OF NORMAL 120VAC POWER OCCUR, FIRE ALARM PANEL WILL AUTOMATICALLY TRANSFER TO BATTERY. A CERTIFICATE OF COMPLETION WILL BE PREPARED AND A COPY PROVIDED TO THE OWNER AND THE CITY FIRE RESCUE DEPARTMENT. OWNER MANUALS, INSTALLATION INSTRUCTIONS, OPERATION INSTRUCTIONS AND RECORD DRAWINGS SHALL BE AT THE SITE ON COMPLETION OF JOB AND FINAL ACCEPTANCE. INSTALLATION NOTES: ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED N.E.C. ELECTRICAL TUBING AND SHALL BE SEALED WITH U.L. APPROVE FIRE STOP MATERIAL. COLOR CODING MAY NOT APPLY TO EXISTING WIRE. (WIRE TO BE LABELED ACCORDINGLY.) CONDUIT SHALL BE A MINIMUM OF 1 /2" AND 407o FILL MAXIMUM. TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE CONTROL COMMUNICATOR. ALL FLOW, TAMPER, PIV AND BACKFLOW WILL HAVE MONITOR MODULES; FIRE PROTECTION SPRINKLER PUMP MONITORING. (3 POINTS) (A).FIRE PUMP RUN (B).FIRE PUMP FAIL (C).FIRE PUMP PHASE REVERSAL. ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC. VERIFY EXACT LOCATIONS OF DEVICES AND WIRE ROUTING PRIOR TO STARTING WORK. MOUNTING REQUIREMENTS: MANUAL PULL STATIONS TO BE INSTALLED AT 48" A.F.F. MOUNT FIRE ALARM SYSTEM STROBES, SPEAKER /STROBES AT 80" A.F.F. FROM BOTTOM OF DEVICE OR 6' BELOW CEILING. (WHICH EVER IS LOWER) SMOKE DETECTOR SHALL NOT BE LOCATED WITHIN S OF SUPPLY AIR OUTLETS. SMOKE DETECTORS TO BE INSTALLED AS PER N.F.P.A. 72. WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4' MINIMUM FROM CEILING WITH 12" MAXIMUM FROM CEILING. WIRE LEGEND SYMBOL WIRE TYPE AND DESCRIPTION A 2 # 16 FPLR ISOTEC P44R I 42SFPLI -02 WIRE FOR DATA COMMUNICATION B 2 # 14 FPLR ISOTEC P #- IR142SFPLI -02 WIRE FOR STROBES C 2 #16 FPLR ISOTEC P #- IR142SFPL1 -02 WIRE FOR SPEAKERS SCOPE OF WORK 1. INSTALLATION OF NEW POWER SUPPLY, NOTIFICATION & INITIATING DEVICES FOR THE SCOPE OF WORK SHOWN ON THE ATTACHED PLANS. SCOPE OF WORK HAS A TOTAL AREA OF: 3,876 SQ. FT. THE EXISTING FIRE ALARM SYSTEM IS AN ADDRESSABLE INTELLIGENT SYSTEM. THE SYSTEM HAS A SLC DEVICE CAPACITY OF 96 DETECTORS, AND 94 MODULES, X2 SLC LOOPS, FOR A TOTAL OF 380 POINTS. 2. THE MAXIMUM HEIGHT OF CEILING 9'-8". 3. SEE BATTERY CALCULATIONS FOR MAXIMUM LENGTH PER INDICATING CIRCUIT. 4. BUILDING IS FULLY SPRINKLERED. FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS U�LABORATORIES, INC.O FOR USE IN THROUGH - PENETRATION US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE ® RESISTANCE DIRECTORY 50L6,90G9 SECTION A -A System No. C -AJ -1044 June 15, 2005 F Ratings - 2, 3, and 4 Hr. (See 'Items 2A and 4) T Rating - 0 Hr. L Rating at Ambient - 2 CFM /sq. ft. L Rating at 400 F - less than 1 CFM /sq. ft. W Rating - Class I (See item 4) 1. Floor or Wall Assembly Lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3) concrete. Except as noted in table under Item 4, min thickness of solid concrete floor or wag assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units *. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both Sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow -core precast concrete units is 7 in. ( 178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 1 A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wag assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID for smaller) min 0.028 (0.71 mm) wag thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wag assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wag. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor orwall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. (762 mm) diam (or smager) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit. D. Conduit -Nom 4 in. (102 mm) diam for smaller) steel electrical metallic tubing. E. Copper- Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nom 6 in. (152 mm) diam for smaller) Regular (or heavier) copper pipe. 3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly- packed mineral wool batt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fig material (Item 4). 4. Fig,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assembles, required caulk thickness to be installed symmetrically on both sides of wag, flush with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wag. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table: Min. Floor or Wag Thkns In. (mm) Nom. Pipe Tube or Conduit Diam in. (mm) Max Annular Space in. (mm) Min. Caulk Thkns in. (mm) F Rating Hour 2-1/2(64) 1/2 -12 (13 -305) 1-3/8(35) 1/2(13) 2 2-1/2(64) 1/2-12 (13-005) 3-1/4(83) 1 (25) 2 4-1/2(114) 1/2 -6 (13 -152) 1-3/8(35) 1/4(6)(a) 2 4-1/2(114) 1/2 -12 (13 -305) 1-1/4(32) 1/2(13) 2 4- 1/2(114) 1/2 -20(13 -508) 2(51) 1(25) 2 4-1/2(114) 1/2-20 (13 -508) 2 (51) 1 (25) 2 4-1/2(114) 1/2 -12 (13-305) 3-1/4(83) 1 1 (25) 1 2 4-1/2(114) 22 -30 {558 -762) 2 (51) 1/2(51) 2 5 -1/2 (140) 1/2 -6 {13 )52) 1 -3/8 (35) 1 (25) (b) 2 (a) Min 2 in. (51 mm) thickness of mineral wool ball insulation required in annular space. (b) Min 1 in. (25 mm) thickness of mineral wool ball insulation required in annular space on both sides of floor or wag assembly. Min I in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wag assembly. 3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant. (Note: W Rating applies only when FB -3000 WT sealant is used.) *Bearing the UL Classification Marking *NOTE This material was extracted by 3M f ire protection products from 2004 edition of the UL fire resistance directory. COUNT FIRE ALARM LEGEND N E SYMBOL DEVXE TYPE MODEL MANUFACTURE 12 AWG 1.93 10 AWG FIRE ALARM CONTROL PANEL STANDBY EXISTING . STANDBY 2 ( WITH 12 LCX) SLC EXPANDER EST -2 EST CURRENT 1 PL'- ALARM & (AA -50) AMPLIFIERS 0.000 CURRENT 1 41 /® FIRE ALARM POWER SUPPLY BPSIQA EST BATTERY 1 ® REMOTE CABINET RACCR EST QTY (AMP -HR) CURRENT PER WITH SIGH -APS & SIGA -AA50 DRAW QTY (AMP4" CURRENT X PER UNIT = 1.680 5 190 PER UNIT SPEAKER / STROBE G4RF -S7VM EST OHMS AWG o w Z SIGA -HRS ITEM (AMPS) 2 ER SPEAKER / STROBE G4RF -S7VM EST 3.07 (AMPS) 1.498 1.131 20.4 19.27 (AMPS) YES CIRCUT#2 SPEAKER / STROBE (75cd) 3.07 BPS10A 0.070 6 S WEATHERPROOF 757-4A-RS EST x 1 = SPEAKER / STROBE (1100 CIRCUIT #1 1.636 1.498 37 S WEATHERPROOF 757 BARS EST 1.753 1 ® STROBE ONLY GC -VM EST 1.514 x 1 CEILING MOUNT 1.514 SPARE 14 313 ® STROBE ONLY GIRF -VM EST 32 F❑ PULL STATION SIGA -278 EST 5' 8 © CONTROLMODULE SIGA -CCIS EST 184 O SMOKE DETECTOR SIGA -PS EST 1 2 O HEAT DETECTOR SIGA+IRS EST 4 DUCT DETECTOR SIGA -SD EST 4 14 1 REMOTE TEST STATION SIGA TRM EST 3 ® CONTROL RELAY MODULE SIGA-CR EST 6 M❑ MONITOR MODULE SIGA -Cn EST (N) = NEW DEVICE (E) = EXISTING DEVICE 21 818 TOTAL DEVICES (ER) = EXISTING RELOCATE FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS `* U LABORATORIES, INC. ® FOR USE IN THROUGH - PENETRATION u US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE ® RESISTANCE DIRECTORY 50L6,90G9 SECTION A -A System No. W -L-Ml September 07, 2004 F Ratings - 1 and 2 Hr. (See items 1) T Rating - 3/4, 1, 1 -1/2 and 2 Hr. (See item 2) L Rating at ambient - 15 CFM /sq. ff. (See item 3) L Rating at 400 F - less than 1 CFM /sq. ff. (See item 3) 1. Wag Assembly - The 1 or 2 hr fire -rated gypsum wallboard /stud wal assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wag or Partition Designs in the UL Fire Resistance Directory and shag include the following construction features: A. Studs - Wag framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3 -5/8 in. wide by 1 -3/8 in. deep channels spaced max 24 in OC. B. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 ff wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be as specified in the individual Wall or Partition Design. Diam of circular through opening to be 3/8 in. to 5/8 in. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached to studs with cement coated nails as specified in the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self- tapping bugle -head steel screws as specified in the individual Wall or Partition Design. The hourly F Rating of the firestop system is equal to the hourly Fre rating of the wall assembly in which it is installed. 2. Cables - Individual cable or max 1 in. diam cable bundle installed in through opening with an annular space of min 0 in. (point contact) to max 3/4 in. Cable to be rigidly supported on both sides of wag assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride PVC insulation and jacket materials. When max 25 pair telephone cable is used, T Rating is 2 hr.When 50 to 150 pair telephone cable is used in 1 hr fire rated wag, T Rating is 3/4 hr.When 50 to 150 pair telephone cable is used in 2 hr fire rated wall, T Rating is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ( "Romex") nonmetallic sheathed cable with PVC insulation and jacket materials. When Type NM cable is used, max T Rating is 1 -1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of 5/8 in. When fiber optic cable is used, max T Rating is 2 hr. D. Max 12 AWG multi conductor (max seven conductors) power /control cable with cross -inked polyethylene (XLPE) insulation and XLPE or PVC jacket materials. When multi conductor power /control cable is used, max T Rating is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl chloride insulation and jacket materials. 3. Fill,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material installed to completely fig annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 in. diam bead of caulk or putty applied to perimeter of cables) at its egress from each side of the wag. 3M COMPANY - MP+ Stix putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -,NM WT sealant is used.) *Bearing the UL Classification Mark FROM INTFC BOARD AT FACP - NOTE. 1- EXISTING `J W CMrLV TCC LVUIYL2Z EXAM ROOM 306 EXI5TING 319 EXISTING EXISTING OFFICE OFFICE OFFICE 03.40 O O 318 23.2.6 320 321 23.2.3 v B 7i /� s� 1 B i� /�7r� 11 23.2.7 �\ 75cd EXISTING EOL- EXAM ROOM 317 EXISTING EXAM ROOM 31G EOL 23.3.6 75cd L -rl 75cd 23.3.5 EXISTING EXAM ROOM 3 CABLE U�30(aTY'j Ei \30 l 00 13 j LOOa LOQP LOOP ADDRESS WIRING FOR ADB-FL BASE (STYLE 41 3' HIGH COUNTER ( ^1 I I I I EXISTING I I NURSE STATION 1 1 322 I 1 I I I 1 (-- -_123.3.3 75cd 1B 71 23.3.4 23.3.2 EXAM 7 ROOM F 302 • NOTE: 3 TO NEXT DEVICE - (WHERE APPLICABLE) NOTE 1. DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE NOTE 2 DO NOT LOOP WIRE UNDER TERMINALS 1& 2. BREAK WIRE RUN TO PROVIDE SUPERVISION NOTE 3. OBSERVE POLARITY. DO NOT GROUND CONTROL WIRES OR SHIELDS. TIE SHIELDS TOGETHER AT EACH DETECTOR. NOTE 4- SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE NOTE 5. RECORD THE LOOP ADDRESS & DEVICE TYPE IN THE SPACES PROVIDED ON VD = 2 X L X R X I OPERATING RANGE FOR DEVICES 1000 ARE BETWEEN 16VDC AND 33VDC VD= VOLTAGE DROP L = ONE -WAY LENGTH OF CIRCUIT R = CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET 1= LOAD CURRENT IB 75cd 23.3.1 EXAM ROOM 301 OFFICE OFFICE 308 309 305 1 1 COUNTER 23.2.2 ;, _----- - - - - ^ 1 B ( 1 _ - ( - - -- 1 oC 23.1.6 �1 1 o a r S 75cd i i i_ QZ RECEPTION EOL -1 1 I 1 O AREA r RECEPTION 304 AREA 314 I I B 1 i 16 ❑ i `►`1 WAITING AREA 300 23.2.1 75cd WAITING AREA 313 23.1.2 75cd L TO NEW POWER L TO NEW POWER SUPPLY #23 CIRCUIT #3 SUPPLY #23 CIRCUIT #2 E 3RD FLOOR - FIRE ALARM PLAN N �a SCALE: 1/8* = V-17 _ w 4" SQUARE (2 -1/8" DEEP) BOX (OR 4" BOX). PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING FLEX \�J 4" SQUARE BOX TO 1 1 3-0 ADAPTER RING (OR NO RING IF 4-0 BOX IS USED) j j PLUG - IN DETECTOR BASE NOTE: MIN PIPE FLEX 1/7' FREE WIRE IN CEILING DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. OHMS PER THOUSAND 18 AWG 75cdI ) g 16 AWG 4.89 -- - - - - -1 3.07 12 AWG 1.93 10 AWG 1.21 STANDBY EXISTING . STANDBY 1 1 X -RAY ROOM 0.000 COUNTER 315 CURRENT 1 PL'- ALARM TOTAL ALARM 0.000 75cd 23.3.1 EXAM ROOM 301 OFFICE OFFICE 308 309 305 1 1 COUNTER 23.2.2 ;, _----- - - - - ^ 1 B ( 1 _ - ( - - -- 1 oC 23.1.6 �1 1 o a r S 75cd i i i_ QZ RECEPTION EOL -1 1 I 1 O AREA r RECEPTION 304 AREA 314 I I B 1 i 16 ❑ i `►`1 WAITING AREA 300 23.2.1 75cd WAITING AREA 313 23.1.2 75cd L TO NEW POWER L TO NEW POWER SUPPLY #23 CIRCUIT #3 SUPPLY #23 CIRCUIT #2 E 3RD FLOOR - FIRE ALARM PLAN N �a SCALE: 1/8* = V-17 _ w 4" SQUARE (2 -1/8" DEEP) BOX (OR 4" BOX). PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING FLEX \�J 4" SQUARE BOX TO 1 1 3-0 ADAPTER RING (OR NO RING IF 4-0 BOX IS USED) j j PLUG - IN DETECTOR BASE NOTE: MIN PIPE FLEX 1/7' FREE WIRE IN CEILING DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. OHMS PER THOUSAND 18 AWG 7.77 16 AWG 4.89 14 AWG 3.07 12 AWG 1.93 10 AWG 1.21 POWER SUPPLY #23 QTY STANDBY AMPS REQUIRED 2 REQUIRED 0.239 TOTAL ALARM 4 REQUIRED STANDBY 1.020 STANDBY - STANDBY 0.000 TOTAL STANDBY STANDBY CURRENT ALARM ALARM TOTAL ALARM 0.000 CURRENT 0 CAPACITY CAPAC2TY (HOURS) CANT (AMPS) BATTERY CAPACITY FACTOR 1.2 DESCRIPTION (AMPS) (AMP -HR) QTY (AMP -HR) CURRENT PER = DRAW QTY (AMP4" CURRENT X PER UNIT = 1.680 2.939 0.25 PER UNIT 5.035 3.527 1.259 OHMS AWG o w Z SIGA -HRS ITEM (AMPS) X 0.00045 = CIRCUIT #1 (AMPS) 3.07 (AMPS) 1.498 1.131 20.4 19.27 (AMPS) YES CIRCUT#2 169 3.07 BPS10A 0.070 x 1 = 0.070 0.270 x 1 = 0.270 CIRCUIT #1 1.636 1.498 XI 1 =1 1.498 CIRCUT#2 1.753 x 1 = 1.753 CIRCXIIT93 1.514 x 1 = 1.514 SPARE 0.000 X1 0 = 0.000 TOTAL SYSTEM TOTAL SYSTEM 0.070 SIGA -CC1S 5' STANDBY PS 0.00022 ALARM PS 0.00178 KMVL rr¢U LR r-KA rrvn IMC I-KWM Wl"A /Z 6 4.4A.D.a.-I STANDBY: 24 HOURS ALARM- 15 M[MnFS X 11R f - n 251- InIIRS REQUIRED QTY TOTAL AMPS REQUIRED 2 REQUIRED 0.239 TOTAL ALARM 4 REQUIRED STANDBY 1.020 STANDBY - STANDBY 0.000 ALARM TIME STANDBY CURRENT ALARM ALARM TIME HOURS) 0.000 CURRENT 0 CAPACITY CAPAC2TY (HOURS) CAPACITY (AMPS) BATTERY CAPACITY FACTOR 1.2 - (AMPS) (AMP -HR) (AMP -HR) (AMP -HR) 1.498 = DRAW DROP (AMP4" 24 X 0.070 = 1.680 2.939 0.25 X 5.035 3.527 1.259 PS23 REQUIRED QTY REQUIRED AMPS TOTAL 2 G4RFS7VM 0.239 MINIMUM 4 GIRF VM 0.255 1.020 REQUIRED - 0.000 0.000 o STANDBY 0.000 ALARM 0 AMPIHOUR 0.000 DERATING 0 AMPMOUR CAPAC2TY 0.000 CAPACITY - BATTERY 0.000 FACTOR 1.2 - BATTERY (AMP -HR) 6 (AMP -HR) 1.498 = DRAW DROP VOLTAGE REQUIRED 1.680 + 1.259 = 2.939 X 1.2 = 3.527 TOTALS FOR CIRCUIT #1 QTY NOTIFICATION TYPE AMPS TOTAL 2 G4RFS7VM 0.239 0.478 4 GIRF VM 0.255 1.020 0 - 0.000 0.000 o - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - 1 0.000 0.000 6 TOTAL AMPS: 1.498 TOTALS FOR CIRCUIT #2 QTY NOTIFICATION TYPE AMPS TOTAL 2 G4RFS7VM 0.239 0.478 5 G1RF -VM 0.255 1.275 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 7 TOTAL AMPS: 1.753 MINIMUM AMPMOUR BATTERY REQUIRED 7 TOTALS FOR CIRCUIT #3 QTY NOTIFICATION TYPE AMPS TOTAL 1 G4RFS7VM 0.239 0.239 5 GIRF -VM 0.255 1.275 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.000 0.000 0 - O.ODD 0.000 o - OMO 0.000 6 1 TOTAL AMPS: 1.514 TOTALS FOR CIRCUT94 QTY NOTIFICATION TYPE AMPS TOTAL 0 - 0.000 0.000 0 - 0.000 0.000 0 - 0.0w 0.000 0 - 0.000 0.000 0 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.000 0.000 o - 0.000 0.000 0 - 0.000 0.000 0 - o.ODO 0.000 0 TOTAL AMPS: 0.000 VOLTAGE DROP CALCULATIONS REQUIRED STANDBY TIME IN HOURS CURRENT MPS TOTAL CURRENT MPS 0.269 X VOLTAGE ALARM LOAD REQUIRED ALARM TIME IN HOURS WIRE RUN OHMS PER TOTAL 0.1500 POWER 0.15 VOLTAGE 4u-roL' D-w CIRCUIT 7.70 MULTIPLY BY THE DERATING FACTOR OF 1.2 SPAR VOLTAGE 1 READING 0.02000 ACCEPTABLE 0.02000 ONE WAY WIRE SIZE CIRCUIT WM SUPPLY Z DROP AT 32 NUMBER (FEET) = DRAW DROP VOLTAGE ATILAST END VOLTAGE DROP SIGA -PS 184 X 0.00045 DEVICE 0.08280 OHMS AWG o w Z SIGA -HRS 3 X 0.00045 = CIRCUIT #1 123 3.07 14 1.498 1.131 20.4 19.27 6% YES CIRCUT#2 169 3.07 14 1.753 1.819 20.4 18.58 9% YES CIRCXIIT#3 176 3.07 14 1.514 1.636 20.4 18.76 8% YES SPARE 0 3.07 14 1 0.000 I 0.000 20.4 20.40 0% NOT USED BATTERY CALCULATION - STANDBY i 23.1.3 75cd EXAM ROOM 310 23.1.5 75cd no ALA" SYSTEM TO BE G INSTALLED IN ACCORDANCE WIT) 75cd NFPA 7% 70;101• 23.1.4 WAITING AREA 311 23.1.1 1 B 7�d TO NEW POWER SUPPLY #23 CIRCUIT #1 7' APPROV NIIAM -DARE COUNTY FIRE BLDG. PERMIT FIRE FIRE SUPPRESSION WATER M DATE: l� / SY. FIRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER NFPA 72 AREA OF AREA LOCATION OF NEW POWER SUPPLY IN EXISTING ELECTRICAL ROOM S 3RD FLOOR - SITE PLAN N 6 SCALE: N.T.S. - w DEVICE TYPE NUMBER OF DEVICES REQUIRED STANDBY TIME IN HOURS CURRENT MPS TOTAL CURRENT MPS 0.269 X 24 = 6.44 ALARM LOAD REQUIRED ALARM TIME IN HOURS MAIN CIRCUIT BOARD 2-MCM 1 X 0.1500 = 0.15 ADD STANDBY AND ALARM LOAD FOR REQUIRED 4u-roL' D-w AMPERE HOUR BATTERY 7.70 MULTIPLY BY THE DERATING FACTOR OF 1.2 SPAR 2 -LCX 1 X 0.02000 = 0.02000 0 o WM Z SIGA -278 32 X 0.00025 = 0.00800 Nftft c� C O SIGA -PS 184 X 0.00045 = 0.08280 oQ WSJ o w Z SIGA -HRS 3 X 0.00045 = 0.00135 REVISIONS: LICENSED ENGINEER: SHANTILAL C. PATEL (954) 327 -9475 P.E. 002855 FIRE PqC i is SIGA -SD 4 X 0.00045 = 0.00180 DATE: SCALE: 12/28/11 1/8 DRAWN BY: CHECKED BY: SIGA -CR 3 X 0.00010 = 0.00030 SIGA -CT1 6 X 0.00025 = 0.00150 SIGA -AA50 1 X 0.00100 = 0.00100 SIGA -CC1S 8 X 0.00022 = 0.00178 SUM COLUMN FOR STANDBY LOAD 2 X 0.23900 = 0.269 DEVICE TYPE NUMBER OF DEVICES REQUIRED STANDBY TIME IN HOURS CURRENT AMPS TOTAL CURRENT MPS 0.269 X 24 = 6.44 ALARM LOAD REQUIRED ALARM TIME IN HOURS MAIN CIRCUIT BOARD 2-MCM 1 X 0.2750 = 027500 ADD STANDBY AND ALARM LOAD FOR REQUIRED 4u-roL' D-w AMPERE HOUR BATTERY 7.70 MULTIPLY BY THE DERATING FACTOR OF 1.2 SPAR 2 -LCX 1 X 0.13000 = 0.13000 0 o WM Z SIGA -278 32 X 0.00040 = 0.01280 Nftft c� C O SIGA -PS 184 X 0.00045 = 0.08280 oQ WSJ o w Z SIGA -HRS 3 X 0.00045 = 0.00135 REVISIONS: LICENSED ENGINEER: SHANTILAL C. PATEL (954) 327 -9475 P.E. 002855 FIRE PqC i is SIGASD 4 X 0.00045 = 0.00180 DATE: SCALE: 12/28/11 1/8 DRAWN BY: CHECKED BY: SIGA -CR 3 X 0.00010 = 0.00030 SIGA -CT1 6 X 0.00040 = 0.00240 SIGA -AA50 1 X 3.00000 = 3.00000 SIGA -CC1 S 8 x 0.00001 = 0.00008 G4RFS7VM 2 X 0.23900 = 0.47800 G1 RF -VM 4 X 0.25500 = 1.02000 SUM COLUMN FOR LOAD IN ALARM I ice] 10 P STANDBY LOAD o° REQUIRED STANDBY TIME IN HOURS CURRENT (AMPS) (24 OR 60 Him) 0.269 X 24 = 6.44 ALARM LOAD REQUIRED ALARM TIME IN HOURS CURRENT (AMPS) Z t Li Q�p (15 MINUTES = 0.250) 5.005 X 0.250 = 1.25 ADD STANDBY AND ALARM LOAD FOR REQUIRED 4u-roL' D-w AMPERE HOUR BATTERY 7.70 MULTIPLY BY THE DERATING FACTOR OF 1.2 SPAR TOTAL AMPERE HOUR REQUIRED = 9.24 24 AM BATTERIES PROVIDED ADA HEIGHT REQUIRMENTS WITH DEEP 19M BOX STROBE OR SPEAKER /STROBE 001 80" A.F.F. OR 0 0 6" BELOW CEILING -110101 (WHICHEVER IS LOWER) PULL STATION 48" A.F.F. O }O O NOT TO SCALE BOX MOUNTING REQUIRMENTS 1900 BOX PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING I 1 DETECTOR BASE DETECTOR HEAD BIG MOUNTING IN SHEET ROCK OR PLASTER TYPE CEILINGS (MUST BE INSTALLED WITH CONDUIT) THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. NOT TO SCALE o° - -0, y V) J Z O U z - (J H N WN W I-JWM Oa�M aW�J IO U) < d - Z t Li Q�p �� � 0 li.l , W 4", i W 4u-roL' D-w 1 SPAR NT IARM // N EXT, 0 o WM Z Q , M at Q Q Q Nftft c� C O co � o oQ WSJ o w Z H U LLI O a REVISIONS: LICENSED ENGINEER: SHANTILAL C. PATEL (954) 327 -9475 P.E. 002855 FIRE PqC i is *; No 285 * PROJECT NUMBER: 000000 DATE: SCALE: 12/28/11 1/8 DRAWN BY: CHECKED BY: D.L. D.N. 1 of 3