DESCRIPTION
FA0.1
FIRE ALARM NOTES, LEGEND & INDEX
FA2.1
FIRE ALARM PLAN
F EMOTE
1
POWER
SUPPLY
L _(RPSL J I
r -1 f -- LJP_ LJP -- 2p— �2F— 2F
INTERCEPT EXISTING FIRE ALARM INITIATING
CIRCUIT, EXTEND TO NEW LOCATION OF
DEVICE AND CONNECT FOR OPERATION.
I
I
I I
I
I
rrr r
III I
III I
IIIII�
illlll
Iillll
I I I I (.IL— --`2L— M_ r�
I I I I T �P LJ
�� P P
IIIIIII �P
IIIIIII
IIIIIII
IIIIIII �
IIIIIII
.L � - --
LIJ
r —n—RE- 1 1 r
1 � � MAIN � r , 1 1
FIRE ALARM REMOTE
I CONTROLLER I I ALARM ( I COMMUNICATOR I I ANNUNCIATOR
I I I CONTROL ( ( TRANSMITTER
N
PANEL I I PANEL I
L_.r_J i (FACP) i L__T__J L__T__J
III I I
L----- - - - -- J I L-- - - - --� I
L-------------- - - - - --
SEVENTH FLOOR
SECOND FLOOR
FIRST FLOOR
FIRE ALARM SYSTEM WIRE SCHEDULE:
FIRE ALARM SYSTEM SHALL BE POWER LIMITED
• INITIATING CIRCUITS: 4 CONDUCTOR, #18 AWG
SOLID, SHIELDED TWISTED PAIR
• INDICATING CIRCUITS: 2 CONDUCTOR, #14 AWG
SOLID, SHIELDED CABLE
• ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL
TUBING (EMT) UNLESS OTHERWISE NOTED.
• PLENUM RATED FIRE ALARM CABLE IS ACCEPTABLE
FOR USE WHERE APPROVED BY THE AUTHORITY HAVING
JURISDICTION.
FIRE ALARM RISER DIAGRAM
NOT TO SCALE
P
P
FIRE ALARM SHEET INDEX
3HEETf
DESCRIPTION
FA0.1
FIRE ALARM NOTES, LEGEND & INDEX
FA2.1
FIRE ALARM PLAN
FIRE ALARM NOTES
1. ALL NEW EQUIPMENT AND DEVICES SHALL BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE
COMPATIBLE WITH THE EXISTING SYSTEM IN USE
2. ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. 72 AND N.E.C. ARTICLE 760. WIRING SHALL BE
SOLID COPPER OR STRANDED COPPER WITH A MAX. OF 7 STRANDS FOR 16 GA AND 18 GA, STRANDED
COPPER WITH A MAX.OF 19 STRANDS FOR SIZES 14 AND LARGER PER N.E.C. 760 AND N.F.P.A. 70.
3. ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED (NEC) METALLIC CONDUIT AND SHALL
BE SEALED WITH A U.L. APPROVED FIRE STOP MATERIAL. (SEE FIRE STOP DETAIL)
4. COLOR CODING MAY NOT APPLY TO EXISTING SYSTEMS. LABEL EXISTING WIRING ACCORDINGLY.
5. ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC ONLY, VERIFY EXACT LOCATIONS
PRIOR TO STARTING WORK.
6. ALL FIRE ALARM NOTIFICATION APPLIANCES SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM.
7. ALL FIRE ALARM AUDIBLE SIGNALS IN OPEN AREA SHALL HAVE A THREE PLUS TEMPORAL PATTERN.
8. ALL FIRE ALARM AUDIBLE SIGNALS SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dba ABOVE THE
AVERAGE ABMBIENT SOUND LEVEL.
9. MANUAL STATIONS TO BE INSTALLED AT 48" INCHES A.F.F.
10. MOUNT FIRE ALARM SYSTEM AUDIBLE /VISUAL SIGNALS (COMBINATION DEVICES) SUCH THAT THE ENTIRE
STROBE LENS IS 80" A.F.F. OR 6" BELOW CEILING, WHICHEVER IS LOWER.
11. MOUNT FIRE ALARM SYSTEM STROBES SUCH THAT THE ENTIRE STROBE LENS IS 80" A.F.F. OR 6"
BELOW CEILING, WHICH EVER IS LOWER.
12. SMOKE DETECTORS TO BE INSTALLED AS REQUIRED BY N.F.P.A. 72.
13. THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM
MANUFACTURER, AND N.E.C. ARTICLE 760. MINIMUM WIRE SIZE IS AWG FOR GROUND CONNECTION.
(NOTE PANEL NEUTRAL OR CONDUIT GROUND IS NOT ACCEPTABLE
14. A GENERAL ALARM SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH
OR DETECTION DEVICE.
15. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF ANY DETECTION OR
MANUAL DEVICE.
16. A SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY FIRE SPRINKLER
SYSTEM TAMPER SWITCH.
17. HVAC DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM CONTROL PANEL AND
SHALL INITIATE A SUPERVISORY SIGNAL ONLY.
18. ALL FIRE ALARM SYSTEM DEVICES INSTALLED FOR THIS SPECIFIC PROJECT SHALL BE U.L. CERTIFIED.
19. ALL FIRE ALARM INITIATING DEVICES SHALL BE ADDRESSABLE AND ALL FIRE ALARM CIRCUITS SHALL
BE CLASS "B ", STYLE "C ".
20. SECURITY LOCK SYSTEM (BY OTHERS) SHALL BE TIED INTO FIRE ALARM SYSTEM. EMERGENCY EXITS
SHALL UNLOCK UPON RECEIPT OF ANY FIRE SIGNAL OR LOSS OF PRIMARY POWER.
21. PROVIDE CERTIFICATE OF COMPLETION AT THE FINAL INSPECTION OF THE FIRE ALARM SYSTEM.
22. FIRE ALARM CONTRACTOR SHALL PROVIDE A DETAILED SET OF SHOP DRAWINGS (INCLUDING DEVICE
CUT SHEETS), A COMPLETE POINT TO POINT WIRING DIAGRAM, FLOOR PLAN DRAWINGS INDICATING
ALL DEVICE LOCATIONS AND NUMBERS, COMPLETE BATTERY CALCULATIONS AND COMPLETE
NOTIFICATION APPLIANCE CIRCUIT CALCULATIONS (FOR THE SYSTEM TO BE INSTALLED) TO THE
BUILDING DEPARTMENT (AUTHORITY HAVING JURISDICTION) AT THE TIME OF APPLICATION FOR
BUILDING PERMIT.
23. PROVIDE THE OWNER WITH A COMPLETE FIRE ALARM SYSTEM AND INSTALLATION MANUAL COVERING
MANUAL COVERING ALL SYSTEM EQUIPMENT INSTALLED FOR THIS PROJECT. KEEP AT THE MAIN FIRE
ALARM CONTROL PANEL.
FIRE ALARM SYMBOLS
ElP FIRE ALARM MANUAL PULL STATION.
(EXISTING TO REMAIN)
OP PHOTOELECTRIC SMOKE DETECTOR.
(EXISTING TO REMAIN)
FF-A-FF9 FIRE ALARM CONTROL PANEL — ADDRESSABLE.
(EXISTING TO REMAIN)
F—RPS--j REMOTE POWER SUPPLY.
(EXISTING TO REMAIN)
75 cd FIRE ALARM SPEAKER / STROBE COMBINATION. NUMERAL
® ADJACENT TO DEVICE INDICATES CANDELA RATING.
(MATCH EXISTING SYSTEM)
D0 N0T INSTALLL,ARM
tractor's tvor - nr plans shall
Fire Alarm �err,.it appro "al to N"'aml-
be submitted for T✓ Ir.
Department,
Dkde County .... �yt
AP e for B i' 'ing Pe
Date
>3v
75 cd FIRE ALARM STROBE. NUMERAL ADJACENT TO DEVICE
%QJ INDICATES CANDELA RATING.
(MATCH EXISTING SYSTEM)
ISSUED FOR PERMIT IN1111l�[Ip�
ISSUED FOR CONSTRUCTION
KAMM CONSULTING PROJECT #: 20:
PROJECT MANAGER GREG KEMP
A"m M 1407
Deerf
Phone
:�t Newport Center rDK e
; B*aifi. Florida 344442
of Authorization t 1$�
a�SN3"?s -12
•
PJESCO
ARCHITECT3
1750 PONCE DE LEON BLVD
CORAL GABLES, FL 33134
305.448.4288 305.44 AN6
AA0002678
SEAL
KAMM CONSULTING
1407 W. Fe 1VPOFfT CB�lTt�i ORVE
DAD BEACH, FL 33442
(g64) M-2MO FAX (964) 949'M
<
LL a. I— �
o Lz F- =) 8
WU��
J w
W Qw
z
D
z
O cf) 0
ow��
�
o
am °�
PROJECT NUMBER
2012 -0423
DATE
07 -06 -12
SHEET
FA0,1