12-707-021NOTES FOR BRANCH CIRCUIT PANELS O1 EXISTING BRANCH CIRCUIT AND CIRCUIT BREAKER TO REMAIN. O2 PROVIDE NEW BRANCH CIRCUIT AND CONNECT TO EXISTING SPARE BREAKER AS INDICATED. O4 REMOVE EXISTING SPARE BREAKER, PROVIDE NEW CIRCUIT BREAKER AS INDICATED, INSTALL IN SPACE IN PANEL AND CONNECT NEW BRANCH CIRCUIT FOR OPERATION. O5 PROVIDE CIRCUIT WITH DEDICATED GROUND. O EXISTING FEEDER AND FEEDER BREAKER TO REMAIN. O EXISTING FEEDER AND FEEDER BREAKER WITH LOAD MODIFIED FOR THIS SPECIFIC PROJECT. DP -7 1 1 r EXISTING r EXISTING PANEL "7LB" i i PANEL "7LA" I I I I I I I I I I I I I I I I I I I I I I I I I I �r -DP -7 SCHEDULE OF BRANCH CIRCUIT PANEL 7LB" MAIN: 225 AMP MAIN LUGS ONLY VOLTAGE: 208/12OV, 30, 4 WIRE SPEC: EXISTING MOUNTING: SURFACE AIC SYMM: EXISTING DESCRIPTION WIRE GND. COND. TRIP CKT. A PHASE KVA B PHASE KVA C PHASE KVA CKT. TRIP COND. GND. WIRE DESCRIPTION EXISTING SUB -PANEL + - - - 40 3 1 2.5 0.6 A PHASE KVA B PHASE KVA 2 20 1/2- 1#12 2 12 GENERAL RECEPTACLES 3 PANEL H 2.5 0.5 100 4 20 1/2- 1#12 2 12 TV RECEPT. 110 5 e SBA -2 2.5 0.6 6 20 1/2- 1#12 2#12 RECEPT. RM 110,109,108 LIGHTING RM 110 : 2#12 1#12 1 2 20 7 0.6 0.6 WATER PUMP 10.8 8 20 1 2 1#12 2#12 REFRIGERATOR 108 RECEPT. RM 116 2 2 12 1 12 1 2 20 9 10.8 0.6 0.6 100 10 20 1/2- 1#12 2#12 COFFEE 108 RECEPT. RM 114 2 2 12 1 12 1 2 20 11 100 3 0.6 0.5 12 20 1/2- 1#12 2#12 MICRO 108 RECEPT. RM 115 2 2 12 1 12 1 2 20 13 0.6 0.6 EXISTING 16.2 14 20 1/2" 1#12 2#12 RECEPT. RM 104,106 RECEPT. RM 117, 125 : 2 12 1 12 1 2 20 15 32.4 0.6 0.5 32.4 16 20 1/2- 1#12 2 12 RECEPT. RM 103 LIGHTING RM 133,134 : 2 12 1 12 1 2 20 17 32.4 e 0.5 0.6 18 20 1 2 1#12 2 12 FAX RM 103 RECEPT. RM 108,109,110 2 2#12 1#12 1 2 20 19 0.6 0.6 - PANEL DP THRU -TT4- 20 20 1/2" 1#12 212 COPIER RM 103 SPARE - - - 20 21 20 - 0.6 - 22 20 1/2- 1 12 - RECEPT. RM 100 SPARE - - - 20 23 20 - - 0.6 24 20 1/2- 1 12 RECEPT. RM 130 SPARE - - - 20 25 - 0.6 - - 26 20 1/2- 1 12 RECEPT. RM 130,128 RECEPT. RM 127 2 2 12 1#12 1/2" 20 27 27 0.6 0.5 3.0 1.5 28 20 1/2- 1 12 $2#12 RECEPT. RM 128 RECEPT. RM 127 2 12 1#12 1 2 20 29 29 0.6 0.5 30 20 1 2 1 12 - RECEPT. RM 123 RECEPT. RM 124 2 2#12 1#12 1 2 20 31 0.6 0.6 1.5 1.5 - 32 20 1/2- 1#12 - RECEPT. RM 123,122,121 RECEPT. RM 124 2 2#12 1#12 1 2 20 33 33 0.6 0.5 4.0 2.0 34 20 1/2" 1 12 - RECEPT. RM 122 MAMMOGRAM EQUIPMENT a 2#B 1 #10 3 4 35 2 35 NOTE: MULTI -WIRE BRANCH CIRCUITS ARE ACCEPTABLE IN LIEU OF 19.0 21.5 21.5 KVA PER PHASE THE SINGLE POLE BRANCH CIRCUITS INDICATED. PROVIDE 68.5 77.6 77.6 AMPS PER PHASE MULTI -POLE BREAKERS FOR ALL MULTI -WIRE BRANCH CIRCUITS AS 62.0 TOTAL KVA REQUIRED BY THE NATIONAL ELECTRIC CODE. PROVIDE DEDICATED NEUTRAL FOR ALL SINGLE POLE BRANCH CIRCUITS AS INSTALLED. - 1.5 0.5 36 20 1 2 1#12 2#12 RECEPT. RM 121 37 1.5 0.6 - - 38 20 II Z2 - 1#12 2#12 SERVER RECEPTACLE BIOPSY EQUIPMENT 2 2#8 1 #10 3/4- 40 2 39 20 2.0 1.5 - 40 30 344- 1 10 2#10 SERVER RECEPTACLE 41 1 39 2.0 0.6 42 20 1 2 1 12 2#12 1 SERVER RECEPTACLE NOTE: MULTI -WIRE BRANCH CIRCUITS ARE ACCEPTABLE IN LIEU OF 10.0 11.6 11.6 1 KVA PER PHASE THE SINGLE POLE BRANCH CIRCUITS INDICATED. PROVIDE 83.3 96.6 96.6 1 AMPS PER PHASE MULTI -POLE BREAKERS FOR ALL MULTI -WIRE BRANCH CIRCUITS AS 33.2 1 TOTAL KVA REQUIRED BY THE NATIONAL ELECTRIC CODE. PROVIDE DEDICATED NEUTRAL FOR ALL SINGLE POLE BRANCH CIRCUITS AS INSTALLED. r EXISTING PANEL "7H" I I I I I I I i I I I I I EXISTING GROUND ----T _I_ 7TH FLOOR (PH) SBA -9 NG 1- T .SBA" I I I I I I MAIN SWITCH I I I i EXISTING BUILDING MAIN GROUNDING ELECTRODE SYSTEM L - - - - - - - - - - - - - } TO EXISTING UTLITY COMPANY'S ELECTRICAL SERVICE VAULT. � Q � � D Q - Q � E � � � O � 4 SETS OF 4#600MCM IN 4" ELECc�T��C�a[� G���EG� DOQC "G�Q� � ((G NTS SCHEDULE OF SERVICE SWITCHBOARD "SBA" (EXISTING) (EXISTING) WIRE GND. COND. TRIP CKT. A PHASE KVA B PHASE KVA C PHASE KVA MAIN: SPEC: 1600 AMP / 3 POLE, MAIN CIRCUIT BREAKER EXISTING COND. GND. WIRE VOLTAGE: 480/277V, 30, 4 WIRE AIC SYMM: 65,000 DESIGNATION DESCRIPTION DESIGNATION CIRCUIT BREAKER CIRCUIT BREAKER FEEDER A PHASE KVA B PHASE KVA C PHASE KVA NOTES FRAME TRIP POLES SBA -1 LIGHTING PH -A PANEL H 100 100 100 3 5.0 EXISTING 16.2 16.2 16.2 e SBA -2 200 PANEL HP 3 100 100 3 10.8 EXISTING 16.2 16.2 16.2 e SBA -3 3 WATER PUMP 10.8 100 100 3 DP -4 EXISTING 16.2 16.2 16.2 e SBA -4 10.8 TRASH COMPACTOR 10.8 100 100 3 PANEL 5L EXISTING 16.2 16.2 16.2 e SBA -5 10.8 X -RAY DP -6 100 100 3 150 EXISTING 16.2 16.2 16.2 s SBA -6 DP -7 X -RAY PANEL 7L 100 100 3 EXISTING EXISTING 16.2 16.2 16.2 e SBA -7 BREAKER PROVISION PANEL -2H-, 3H - 200 200 3 - EXISTING 32.4 32.4 32.4 s SBA -8 - PANEL "4H". 5H - 200 200 3 - EXISTING 32.4 32.4 32.4 e SBA -9 - PANEL 6H-. 7H - 200 200 3 20 4#3/0 & 1#6G IN 2-1 72 19.0 21.5 21.5 76.6 638.3 SBA -10 - PANEL DP THRU -TT4- - 1 400 400 3 1 4#500MCM & 1#3G IN 4 17.6 19.4 18.6 - - 20 20 - - - 198.6 716.9 202.9 732.4 603.6 202.1 KVA PER PHASE 729.6 AMPS PER PHASE 1 TOTAL KVA SCHEDULE OF BRANCH CIRCUIT PANEL 7H" (EXISTING) SCHEDULE OF DISTRIBUTION PANEL "DP" (EXISTING) WIRE GND. COND. TRIP CKT. A PHASE KVA B PHASE KVA C PHASE KVA MAIN: SPEC: 1200 AMP MAIN LUGS ONLY EXISTING COND. GND. WIRE DESCRIPTION VAV -A PHA -A 2 VOLTAGE: 208/12OV, 30, 4 WIRE AIC SYMM: 65,000 DESIGNATION DESCRIPTION CIRCUIT BREAKER FEEDER A PHASE KVA B PHASE KVA C PHASE KVA NOTES FRAME TRIP POLES DP -1 LIGHTING PH -A PANEL I L7 100 50 3 EXISTING 5.0 5.0 5.0 a DP -2 20 PANEL 2L 200 150 3 EXISTING 10.8 10.8 10.8 e DP -3 PANEL 3L 200 150 3 EXISTING 10.8 10.8 10.8 e DP -4 1 #12 PANEL 4L 200 150 3 EXISTING 10.8 10.8 10.8 e DP -5 2 #12 PANEL 5L 200 150 3 EXISTING 10.8 10.8 10.8 a DP -6 10 PANEL 6L 200 150 3 EXISTING 10.8 10.8 10.8 e DP -7 11 PANEL 7L 200 175 3 EXISTING 17.6 19.4 18.6 EXISTING LIGHTING + DP -8 - BREAKER PROVISION - - 3 - - - - 20 DP -9 - BREAKER PROVISION - - .3 - - - - - DP -10 - BREAKER PROVISION - - 3 - - - - - - 20 17 - - 1.5 1.5 76.6 638.3 78.4 77.6 KVA PER PHASE 1 653.3 1 646.6 AMPS PER PHASE 232.6 TOTAL KVA SCHEDULE OF BRANCH CIRCUIT PANEL 7H" (EXISTING) MAIN: 225 AMP MAIN LUGS ONLY VOLTAGE: 480/277V, 30, 4 WIRE SPEC: EXISTING MOUNTING: SURFACE AIC SYMM: EXISTING DESCRIPTION WIRE GND. COND. TRIP CKT. A PHASE KVA B PHASE KVA C PHASE KVA CKT. TRIP COND. GND. WIRE DESCRIPTION VAV -A PHA -A 2 2#1 1 12 1 2 20 1 2.0 2.0 2 20 - - 2 12 LIGHTING PH -A EXISTING VAV BOXES PH -A 2 2 12 1 12 1 2 20 3 1.0 2.0 4 20 1121--f-#-12 1 #12 2 #12 LIGHTING PH -A 2 INST -HOT PH -A 2 2 12 1 #12 1 2 20 5 3.0 2.0 6 20 - 1 #12 2 #12 LIGHTING PH -A INST -HOT PH -A 2 2 #12 1 #12 1 2 20 7 3.0 2.0 8 20 - 1 #12 2 #12 LIGHTING PH -A 2 INST -HOT PH -A 2 2#12 1#12 1 2 20 9 - 3.0 1.5 - 10 20 - - - EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 11 - - 1.5 1.5 12 20 - - - EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 13 1.5 1.5 - - 14 20 - - - EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 15 - 1.5 1.5 - 16 20 - - - EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 17 - - 1.5 1.5 18 20 - - - EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 19 1.5 1.5 - - 20 20 - - - I EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 21 - 1.5 1.5 - 22 20 - - - EXISTING LIGHTING + EXISTING EQUIPMENT 0.4 0.4 3 23 - - 3.0 1.5 24 20 - - - EXISTING LIGHTING + 25 3.0 1.5 26 20 - - - EXISTING LIGHTING + 27 - 3.0 1.5 - 28 20 - - - EXISTING UGH71NG + EXISTING LIGHTING + - I - I - 20 29 1.5 1.5 30 20 - - - EXISTING LIGHTING + EXISTING LIGHTING + - - - 20 31 1.5 1.5 - - 32 20 - - - EXISTING LIGHTING + EXISTING EQUIPMENT + - - - 5 2 33 - 4.0 2.0 - 34 0 12 - - - EXISTING EQUIPMENT + 35 - - 4.0 2.0 36 NOTE: MULTI -WIRE BRANCH CIRCUITS ARE ACCEPTABLE IN LIEU OF 19.0 21.5 21.5 KVA PER PHASE THE SINGLE POLE BRANCH CIRCUITS INDICATED. PROVIDE 68.5 77.6 77.6 AMPS PER PHASE MULTI -POLE BREAKERS FOR ALL MULTI -WIRE BRANCH CIRCUITS AS 62.0 TOTAL KVA REQUIRED BY THE NATIONAL ELECTRIC CODE. PROVIDE DEDICATED NEUTRAL FOR ALL SINGLE POLE BRANCH CIRCUITS AS INSTALLED. SCHEDULE OF BRANCH CIRCUIT PANEL "7LA" (EXISTING) MAIN: 225 AMP MAIN LUGS ONLY (PROVIDE PANEL WITH SUB FEED LUGS) VOLTAGE: 208/12OV, 30, 4 WIRE SPEC: EXISTING MOUNTING: SURFACE AIC SYMM: EXISTING DESCRIPTION WIRE GND. COND. TRIP CKT. A PHASE KVA B PHASE KVA C PHASE KVA CKT. TRIP COND. GND. WIRE DESCRIPTION EXISTING NO LABEL + - - - 20 1 0.6 0.6 2 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 3 0.6 0.4 4 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 5 0.6 0.4 6 0 2 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 7 0.6 0.4 8 EXISTING NO LABEL + - - - 20 9 0.6 0.4 10 20 - - - I EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 11 0.6 0.6 12 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 13 0.6 0.4 14 1 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 15 0.6 0.6 16 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 17 0.4 0.6 18 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 19 0.5 0.6 20 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 21 0.6 0.6 22 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 23 0.4 0.4 24 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 25 0.6 0.5 26 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 27 0.6 0.6 28 20 - - - EXISTING NO LABEL + EXISTING NO LABEL QA 20 29 6.670.4 30 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 31 0.5 0.6 32 20 - - - EXISTING NO LABEL Q9 EXISTING NO LABEL + - - - 20 33 0.6 0.4 34 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 35 0.4 0.4 36 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 37 0.6 0.5 38 20 - - - EXISTING NO LABEL + EXISTING NO LABEL + - - - 20 1 39 0.6 1 0.6 40 20 - - - EXISTING NO LABEL + EXISTING NO LABEL QA 20 1 41 0.6 0.6 42 20 - - - EXISTING NO LABEL + NOTE: MULTI -WIRE BRANCH CIRCUITS ARE ACCEPTABLE IN LIEU 7.6 7.8 7.0 KVA PER PHASE PANEL 7LA OF THE SINGLE POLE BRANCH CIRCUITS INDICATED. PROVIDE 10.0 11.6 11.6 KVA PER PHASE PANEL 7LB MULTI -POLE BREAKERS FOR ALL MULTI -WIRE BRANCH CIRCUITS 17.6 19.4 18.6 1 SUBTOTAL AS REQUIRED BY THE NATIONAL ELECTRIC CODE. PROVIDE 146.6 161.6 1 155.0 1 AMPS PER PHASE DEDICATED NEUTRAL FOR ALL SINGLE POLE BRANCH CIRCUITS 1 55.6 1 TOTAL KVA AS INSTALLED. i i' L RJE-s-co ARCHITBCTS T750 PONCE DE LEON BLVD CORAL. GABLES, FL 33134 305.448.4288 305.444.4986 AA0002678 SEAL KAMM CONSULTING 1407 W. NEUVP= C3M DM DMA MACK FL 334Q (964) 949.2200 FAX (964) 94P -?201 zLu X o a.� oZw� 8 a: J � 0 J w °C Q w ' W Q = o (j) (jam ow�� IL 0 a m� co REVSIONS PROJECT NUMBER 2012 -0423 DATE 07 -06 -12 E5.1