12-707-017TELEPHONE WOOD BACKBOARD
4'Wx8'Hx3 /4" E
PAINT WITH TW
FIRE RETARD4
TO BRANCH
CIRCUIT PANEL
MOUNT RECEPI
DIRECTLY TO T
BOARD
GROUND BAR,'
THIS SHEET.
1 #2 GROUND
TO NEAREST El
GROUNDED BUILUrrv� -
STRUCTURAL STEEL MEMBER.
ELECTRICAL SPECIFICATIONS
PART 1 - GENERAL
A. THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED.
CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS.
IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY
THE ARCHITECT /ENGINEER AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND
SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL ARCHITECT /ENGINEER HAS DIRECTED
CORRECTIVE ACTION TO BE TAKEN.
B. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL
CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROVISIONS AS TO
THE COST THEREOF.
C. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC
CODE (AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION) AND ALL CODES AND ORDINANCES OF THE
AUTHORITY HAVING JURISDICTION. THE SPECIFICATION, CODES AND STANDARDS LISTED BELOW ARE
UTILIZED IN THIS PROJECT.
1. NATIONAL ELECTRICAL CODE (NFPA -70, 2008 EDITION)
2. CODE FOR SAFETY TO LIFE (NFPA -101, 2006 EDITION)
3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING
SYSTEMS (NFPA -72, 2007 EDITION
4. UNDERWRITERS' LABORATORIES (UL
5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
7. FEDERAL SPECIFICATION (FED. SPEC.)
8. INSULATED POWER CABLE ENGINEERS ASSOCIATION (IPCEA)
9. FLORIDA BUILDING CODE. 2010 EDITION (AS AMENDED)
10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
11. CITY OF SOUTH MIAMI BUILDING CODE. (AMENDMENTS TO FLORIDA BUILDING CODE 2010)
12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE
OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA)
D. DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS
FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE.
E. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM
AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
F. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE.
G. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED
THERE BY.
H. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
I. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR
TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT.
J. THE TERM "PROVIDE" USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS SHALL MEAN THAT
THE CONTRACTOR IS TO FURNISH, INSTALL AND CONNECT COMPLETE.
PART 2 - PRODUCTS
A. MINIMUM WIRE SIZE SHALL BE #12 A.W.G. (EXCEPT AS NOTED OTHERWISE FOR CONTROL WIRING).
B. ALL CONDUCTORS SHALL BE 98% CONDUCTIVITY, COPPER WITH "THHN -THWN" INSULATION UNLESS
OTHERWISE NOTED.
B. ELECTRICAL METALLIC TUBING (EMT) SHALL BE OF BEST QUALITY STEEL, SMOOTH INSIDE AND OUT
AND SHALL BE HOT- DIPPED GALVANIZED.
C. RIGID NONMETALLIC CONDUIT SHALL BE SCHEDULE 40 PVC.
D. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS.
E. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE.
F. PANELBOARDS:
1. CIRCUIT BREAKERS USED AS SWITCHES IN FLUORESCENT OR HID LIGHTING CIRCUITS SHALL
BE LISTED AND MARKED "SWD" OR "HID" AS REQUIRED.
2. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE.
3. A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES.
4. ALL EXISTING PANELBOARDS UTILIZED FOR THIS SPECIFIC PROJECT SHALL BE PROVIDED WITH
AN UP TO DATE TYPE- WRITTEN DIRECTORY OF BRANCH CIRCUIT DESIGNATIONS.
G. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE, QUICK- BREAK.
H. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED ON THE ELECTRICAL DRAWINGS, WITH
OVERLOAD RELAYS IN EACH PHASE. PROVIDE MAGNETIC STARTERS WITH "H-0-A" SWITCH.
I. ENCLOSURES SHALL BE NEMA -1 FOR INDOOR LOCATIONS, NEMA 3R FOR OUTDOOR LOCATIONS
OR AS OTHERWISE NOTED.
J. WIRING DEVICES (GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES) SHALL BE WHITE COLOR UNLESS
OTHERWISE NOTED. FACEPLATES SHALL BE SMOOTH, WHITE NYLON.
10"
EQUIPMENT GROUND
i
1 -1 /2" l III o 0
1/4" COPPER BAR
GLASTIC INSULATOR
PLYWOOD BACKBOARD-
1 -2" CONDUIT WITH PULL
STRING TO MAIN
TELEPHONE BOARD ON
- FLOOR
TERMINATE CONDUIT WITH
INSULATED BUSHING
0 0 He)
TMOUNTED AT BASE OF
PLYWOOD BACKBOARD
3' -0" A.F.F.
SIDE VIEW
TELEPHONE RISER DIAGRAM
NOT TO SCALE
PART 3 - EXECUTION
A. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS:
1. 208/120 VOLTS, 3 PHASE, 4 -WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BLACK, 1 RED AND 1
BLUE. GROUNDED (NEUTRAL) CONDUCTOR; WHITE. GROUNDING CONDUCTORS SHALL BE GREEN.
2. 480/277 VOLT, 3- PHASE, 4 -WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BROWN, 1 YELLOW, AND
1 PURPLE. GROUNDED (NEUTRAL) CONDUCTORS; GREY. GROUNDING CONDUCTORS SHALL BE GREEN.
3. BRANCH CIRCUIT WIRING ( #6 AND SMALLER) SHALL BE COLOR CODED BY CONTINUOUS INSULATION
COLOR AND FEEDERS AND SERVICES ( #4 AND LARGER) SHALL BE CODED AT ALL JUNCTION OR
PULL POINTS (EXCEPT LB'S OR LBD'S) USING COLOR MARKERS OR PLASTIC TAPE MANUFACTURED
FOR THE PURPOSE.
B. WIRING METHODS
1. ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS
OTHERWISE NOTED, SPECIFIED OR AS SPECIFICALLY PROHIBITED BY THE AUTHORITY HAVING
JURISDICTION. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL
RAIN TIGHT COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE.
2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL
BE INSTALLED UNDERGROUND OR BELOW SLABS ON GRADE.
3. TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR
USE AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES OR LESS AND CONCEALED
IN WALLS OR ABOVE SUSPENDED CEILING AND AS APPROVED BY THE AUTHORITY HAVING
JURISDICTION.
C. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST
EDITION OF THE N.E.C. AND LOCAL CODES.
D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE.
E. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS
OF CONSTRUCTION.
F. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND TELEPHONE
COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK.
G. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES, AND WIRING
DEVICES, FOR ALL OUTLETS AS INDICATED.
H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW
AND SUCH AS APPEAR ON THE UL LIST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE
REQUIREMENTS OF NEC, NEMA, AND IECE.
I. CONTRACTOR SUBMITTALS:
I, SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING
FIXTURES, SWITCHES, AND OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER /ARCHITECT.
2, AS -BUILT ELECTRICAL DRAWINGS SHALL BE PROVIDED TO THE OWNER AS REQUIRED BY FLORIDA
BUILDING CODE, ARTICLE 13.413.1
3. OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE OWNER AS REQUIRED BY
FLORIDA BUILDING CODE, ARTICLE 13.413.1
J. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED OF HIS WORK.
K. ALL LAY -IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEILING GRID AT EACH CORNER.
L. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL
WIRING.
M. ALL ELECTRICAL POWER WIRING FOR THE HVAC SYSTEM INCLUDING WIRING THRU LINE VOLTAGE CONTROL
DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
N. VOLTAGE DROP
1. CONDUCTORS FOR ALL FEEDERS SHALL BE INCREASED FROM SIZES INDICATED ON DRAWINGS TO
PREVENT VOLTAGE DROP EXCEEDING 27.
2• CONDUCTORS FOR ALL BRANCH CIRCUITS SHALL BE INCREASED FROM SIZES INDICATED ON
DRAWINGS TO PREVENT VOLTAGE DROP EXCEEDING 37.. FROM THE FURTHEST DEVICE.
3. DETERMINING CONDUCTOR SIZES SHALL BE BASED ON 80% OF THE BREAKER RATING.
4. FOR DETERMINATION OF WIRE SIZE FOR BID PURPOSES:
* INCREASE WIRE BY 1 WIRE SIZE FOR RUNS 60 FT. TO 100 FT.
* INCREASE WIRE BY 2 WIRE SIZES FOR RUNS 100 FT. TO 150 FT.
* INCREASE WIRE BY 3 WIRE SIZES FOR RUNS FROM 150 FT. TO 230 FT.
0. PROVIDE CABLE LUGS SIZED FOR THE LINE AND /OR LOAD SIDE FEEDERS AS SCHEDULED FOR ALL
SWITCHBOARDS, PANELBOARDS AND DISCONNECTS. WHERE CABLE LUGS ARE NOT AVAILABLE FOR THE
SPECIFIC WIRE SIZE AND NUMBER OF SETS SCHEDULED, PROVIDE A TAP BOX ADJACENT TO THE
EQUIPMENT WITH "POLARIS" TAPS TO TRANSITION TO CONDUCTORS TO MATCH THE CABLE LUGS
AVAILABLE AND THE AMPERE RATING OF THE OVER- CURRENT DEVICE PROTECTING THE FEEDER.
P. THE CONTRACTOR SHALL CONFIRM WITH THE ELECTRICAL UTILITY COMPANY ANY AND ALL REQUIREMENTS
SUCH AS: METERING EQUIPMENT REQUIREMENTS AND METERING EQUIPMENT LOCATION, TRANSFORMER
SIZE AND LOCATION OR SERVICE POINT, CONDUIT ENTRY AND LUG SIZE RESTRICTIONS.
Q. THE CONTRACTOR SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE-OWNERS CONFIRMATION.
R. ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
PROCEEDING WITH ANY WORK.
LIGHTING FIXTURE SCHEDULE
SFlEET#
DESCRIPTION
LAMPS
BALLAST
INPUT
ELECTRICAL LIGHTING PLAN
E3.1
N0.
I TYPE
WATT
TYPE
SYMBOL
DESCRIPTION
WATTS
MOUNTING
REMARKS
Ml-
x2'x4'
FLUORESCENT STATIC TROFFER WITH FLUSH STEEL DOOR, WHITE BAKED ENAMEL FINISH AND
2
T8
28
HIGH FREQ.
60
CEILING
CLEAR Al2.125 LENS. COLUMBIA ' J24 ' SERIES.
35001(
ELECTRONIC
RECESSED
1 2 3 4
2'x4' FLUORESCENT PARABOLIC STATIC TROFFER WITH 3" DEEP, 18 CELL LOUVER, LOW IRIDESCENT
3
T8
32
HIGH FREQ.
101
CEILING
SILVER FINISH AND BLACK REVEAL COLUMBIA " P2 " SERIES.
35001(
ELECTRONIC
RECESSED
1 2 3 4
FLUORESCENT PARABOLIC TROFFER SAME AS ABOVE EXCEPT WITH FLUORESCENT EMERGENCY
3
T8
32
HIGH FREQ.
101
CEILING
O2'x4'
LIGHTING BATTERY PACK 'BODINE B50' (1400 LUMEN OUTPUT).
35001(
ELECTRONIC
RECESSED
1 2 3 4
2'x2' FLUORESCENT PARABOLIC TROFFER WITH 3' DEEP, 9 CELL LOUVER, LOW IRIDESCENT SILVER
2
78
32
HIGH FREQ.
67
CEILING
VIM HIM
FINISH AND BLACK REVEAL COLUMBIA ' P422' SERIES.
35001(
ELECTRONIC
RECESSED
1 2 3 4
2'x2' FLUORESCENT PARABOLIC TROFFER SAME AS ABOVE EXCEPT WITH FLUORESCENT EMERGENCY
2
T8
32
HIGH FREQ.
67
CEILING
a
LIGHTING BATTERY PACK 'BODINE B50' (1400 LUMEN OUTPUT).
35001(
ELECTRONIC
RECESSED
1 2 3 4
FLUORESCENT OPEN REFLECTOR DOWN LIGHT WITH 6" APERTURE, CLEAR TRIM AND SPECULAR LOW
1
TRT
32
HIGH FREQ.
34
CEILING
0
IRIDESCENT FINISH. PRESCOLITE 'CFT632' SERIES.
ELECTRONIC
RECESSED
1 3 4
FLUORESCENT OPEN REFLECTOR DOWN LIGHT SAME AS ABOVE EXCEPT WITH EMERGENCY
1
TRT
32
HIGH FREQ.
34
CEILING
0
UGHITNG BATTERY PACK. - BODINE 894C" (1400 LUMEN OUTPUT).
ELECTRONIC
RECESSED
1 3 4
FLUORESCENT WALL WASHER DOWN LIGHT WITH 4' APERTURE, CLEAR TRIM AND SPECULAR LOW
1
TRT
32
HIGH FREQ.
34
CEILING
0
IRIDESCENT FINISH. PRESCOLITE "CFT432' SERIES.
ELECTRONIC
RECESSED
1 3 4
DECORATIVE HALOGEN PUCK LIGHTS.
1
MR16
50
-
50
CEILING
®
WAC LIGHTING 'HR -88'. SEE INTERIOR DESIGN DRAWINGS. MOUNT AT 71" A.F.F. IN SHELF.
RECESSED
1 3 4
DECORATIVE WALL SCONCE (CORRIDOR)
1
TRT
13
HIGH FREQ.
15
CEILING
V
MINKA GROUP LIGHTING "P1705- 613 ", VERIFY FINISH AND COLOR WITH INTERIOR DESIGNER
ELECTRONIC
RECESSED
3 4
DECORATIVE WALL SCONCE (BATHROOM)
1
TRT
60
-
60
CEILING
MINKA GROUP LIGHTING 'P1705 -613, VERIFY FINISH AND COLOR WITH INTERIOR DESIGNER
RECESSED
DECORATIVE PENDANT FIXTURE (ROOM 110)
12
TRT
60
-
720
CEILING
O
CORBET LIGHTING 'DOLCE 109 -512', VERIFY FINISH AND COLOR WITH INTERIOR DESIGNER
RECESSED
1
DUAL FACE THERMOPLASTIC EXIT SIGN/LIGHT WITH WHITE HOUSING AND RED LETTERS. PROVIDE
-
LED
-
-
UNIVERSAL
DIRECTIONAL ARROWS AS INDICATED. PROVIDE FIXTURE WITH 90 MINUTE BATTERY BACK UP.
_
'DUAL -LITE' " LX ' SERIES.
SINGLE FACE THERMOPLASTIC EXIT SIGN/UGHT WITH WHITE HOUSING AND RED LETTERS. PROVIDE
-
LED
-
-
UNIVERSAL
®
DIRECTIONAL ARROWS AS INDICATED. PROVIDE FIXTURE WITH 90 MINUTE BATTERY BACK UP.
_
'DUAL -LITE " LX ' SERIES.
O VERIFY CEILING TYPES PRIOR TO ORDERING FIXTURES.
l�2 FIXTURE SHALL COMPLY WITH 2005 NEC- 410.73(G) - DISCONNECTING MEANS FOR BALLAST.
O VERIFY BALLAST REQUIREMENTS FOR ALL FLUORESCENT FIXTURES. PROVIDE
ELECTRONIC DIMMING BALLASTS FOR SPECIFIC FIXTURES INDICATED WITH
DIMMER CONTROL
O PROVIDE ALL FLUORESCENT FIXTURES WITH UNIVERSAL BALLAST.
ELECTRICAL SHEET INDEX
SFlEET#
DESCRIPTION
EO.1
ELECTRICAL NOTES, LEGEND & INDEX
E2.1
ELECTRICAL LIGHTING PLAN
E3.1
ELECTRICAL POWER PLAN
E4.1
HVAC POWER PLAN
E5.1
ELECTRICAL RISER DIAGRAM
E6.1
ELECTRICAL PANEL SCHEDULES
ELECTRICAL SYMBOLS
TELEPHONE /DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.
v MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
TELEVISION OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.
MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
(I11 DUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING) MOUNTED AT
18" A.F.F. TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE.
QUADRUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING)
MOUNTED AT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE.
tmGFI DUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING) WITH GROUND
FAULT CIRCUIT INTERRUPTER, MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET. UNLESS
NOTED OTHERWISE.
(n DUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING) WITH DEDICATED
Tiff GROUND, MOUNT AT 18" A.F.F. TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED.
SPECIAL- PURPOSE RECEPTACLE
JUNCTION BOX
4 EXHAUST FAN. SEE MECHANICAL DRAWINGS FOR SPECIFICATIONS.
SINGLE POLE, 20 AMP, SWITCH. MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH UNLESS
OTHERWISE NOTED.
$OS DUAL TECHNOLOGY WALL SWITCH /OCCUPANCY SENSOR, WATT STOPPER DW -100 SERIES.
MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH UNLESS OTHERWISE NOTED.
30 MINUTE MAXIMUM TIME DELAY.
$OSD UNIVERSAL DECORATOR STYLE DIMMABLE WALL SWITCH, WATT STOPPER WD -280 SERIES.
MOUNT 48" A.F.F. TO CENTERLINE OF SWITCH UNLESS OTHERWISE NOTED.
sv DECORATOR LOW VOLTAGE MOMENTARY OVERIDE SWITCH
WATTSTOPPER #DCC2. FOUR HOUR MAXIMUM TIME DEALY.
I[= �A FUSIBLE DISCONNECT SWITCH A = POLES, B= FRAME SIZE, C= FUSE RATING
tM FA FUSIBLE DISCONNECT SWITCH TYPE COMBINATION MOTOR STARTER A = POLES, B= NEMA SIZE,
C= FUSE RATING
GROUNDING ELECTRODE & CONDUCTOR SYSTEM
® TRANSFORMER
O ELECTRICAL PANELBOARD
m TELEPHONE WOOD BACKBOARD
WP WEATHERPROOF
T/C TIME CLOCK
RE RELOCATED
E EXISTING TO REMAIN
A.F.F. ABOVE FINISH FLOOR
ISSUED FOR PERMIT 7 -9 -12
ISSUED FOR CONSTRUCTION -
�-J
Z
U
J
W
RMSCO
ARCHITECTS
1750 PONCE DE LEON BLVD
CORAL GAR .M FL 33134
305.448.4288 305.444986
AA0002678
SEAL
KAMM CONSULTING
1407 W. I�EWPOfiT CB1iti�t DRVE
DAD BEACH, FL 334�t2
00 X49.= FAX (9d4)WW
o Lij
z
oZ��
awn $
a:U �
J
0
J W
W � W
~ W Q
Z
D
z
c\l
O cf) W
owco�
a: 0
(L 0
am° 0
as /��.� ►.
PROJECT NUMBER
2012 -0423
��
07 -06 -12
E0.1