12-707-013MECHANICAL NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE DRAWINGS, THE FLORIDA BUILDING CODE 2010 AND ALL OTHER APPLICABLE STATE, COUNTY AND LOCAL ORDINANCES AND THE LATEST EDITION OF THE FOLLOWING PUBLICATIONS; SMACNA -85, 95, 03, 05; ASHRAE 15 -04, 34 -04, 62 -04; NFPA 70 -08, 72 -07, 90A -02, 908 -02, 91 -04, 96 -04, 101 -06; ANSI Z10.1 -98, Z10.3 -98, Z21.8 -94, Z21.83 -98. 2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK. 3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES. 4• THE CONTRACTOR SHALL SUPPLY THE ARCHITECT /ENGINEER WITH "AS- BUILT" DRAWINGS. 5• CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE [5] COPIES OF A COMPLETE SET OF SHOP DWGS, MANUFACTURER'S SUBMITTALS FOR EACH PIECE OF EQUIPMENT & CONTROLS INCLUDED IN CONTRACT 6. ALL MATERIAL SHALL BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS. ALL EQUIPMENT SHALL BE UL OR ETL LISTED. ALL INSTALLATIONS SHALL COMPLY WITH FMC 2010, CH. 3, GENERAL REGULATIONS. BUILDINGS LOCATED WITHIN 3,000 FT FROM THE OCEAN SHALL UTILIZE NON- FERROUS MATERIALS FOR ALL OUTDOOR EXPOSED SUPPORTS, STANDS, FASTENERS, ETC. 7. DUCTWORK: A, ALL DUCTWORK SHALL BE GALVANIZED SHEETMETAL WITH SEALED SEAMS AND JOINTS WITH EXTERNAL BLANKET INSULATION R -6 MIN. THE CONTRACTOR SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT STEEL, ETC., ALL FLEX DUCT SHALL BE RATED CLASS I, UL -181 LISTED WITH METALLIZED INNER AND OUTER FOIL LINERS, MIN. R -6 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 20 FT. INSTALL UL LISTED FOR PLENUM, FLEXIBLE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER, GRILLE, AND REGISTER EQUAL TO "FLEXFLOW ELBOW" AS MANUFACTURED BY "THERMAFLEX ". ALL METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A. SPECIAL NOTE: SMACNA DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2 ", 1 ", 2 ", 3 ", 4 ", 6 AND 10 ". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE CLASS SHOWN ON PLANS. WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY. WHERE NO PRESSURE CLASS IS SPECIFIED FOR VARIABLE VOLUME SYSTEMS, 2" W.G. PRESSURE CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS FOR DUCTWORK UPSTREAM OF VAV BOXES. ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS" FOR ITS PRESSURE CLASS SEALING METHODS. 8. ALL EXHAUST DUCTS AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE INSULATED WITH EXTERNAL BLANKET INSULATION R -6 MIN. ALL METAL EXHAUST, MAKE -UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R -6 MIN. AIR INTAKE AND EXHAUST OPENINGS SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL PER FMC 2010, TABLE 401.5. 9. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS. 10. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAZRE. PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS TO ENSURE COMPLIANCE AIR FLOW AND WITH FMC 2010 PAR.601.4 FOR BALANCED RETURN TRANSFER AIR FLOW. 11. TEMPERATURE CONTROLS/THERMOSTAT- A. FOR VAV BOXES: DDC CONTROLS PER CONTROL PLANS, PROVIDE ROOM T'STAT /SENSOR WITH OVERRIDE B. FOR EXISTING EQUIPMENT: SHALL BE SERVICED AND RELOCATED AS SHOWN. IF NEW THERMOSTAT IS PROVIDED IT SHALL MATCH BUILDING STANDARDS. 12. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION. INSTALL THERMOSTAT PER A.D.A REQUIREMENTS WHERE APPLICABLE; MAX. 48" HIGH FOR FORWARD REACH, MAX. 54" HIGH FOR SIDE REACH. MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS FOR JUNCTION BOXES, CONDUITS, CONTROL WIRING, POWER, ETC. AND DEFINE RESPONSIBILITIES AND SCOPE OF WORK FOR EACH TRADE PRIOR TO PURCHASING/INSTALLATION. 13. ALL BRANCH TAKE -OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W /SINGLE FOIL TURNING VANES. PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE -OFFS. PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS, "YOUNG REGULATOR" OR EQUAL. 14. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START -UP, REPLACE PRIOR TO FINAL ACCEPTANCE BY OWNER. 15. PROVIDE TYPE "B" DYNAMIC FIRE DAMPERS WITH SERVICE ACCESS DOORS IN ALL DUCTS AND OPENINGS PENETRATING FIRE RATED WALLS, MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, TENANT SEPARATION, PARTITIONS, FLOOR OR ROOF SLABS AND AT OUTSIDE AIR INTAKES AS REQUIRED. PROVIDE RADIATION DAMPERS IN RATED CEILINGS FOR ALL CEILING OPENINGS, CEILING FANS, DIFFUSERS OR GRILLES RATED FOR USE IN THE CEILING ASSEMBLY. PROVIDE LOW- LEAKAGE CLASS DAMPERS FOR ALL SITUATIONS WHERE THE AIRFLOW CFM HAS TO BE CONTROLLED. VERIFY AND REPLACE AS REQUIRED FOR EXISTING SYSTEMS. 16. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER FEC 2010, SEC.503.2.9.1 (THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS) FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AND ANY AIR MOVING SYSTEMS. THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AABC OR NEBB STANDARDS AND PROCEDURES AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RETURN GRILLES AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE ('F) FROM SUPPLY GRILLES, EVAPORATORS, ENERGY RECOVERY UNITS AND ANY TYPE OF HEAT EXCHANGERS. SPECIAL NOTE: AS PART OF BID, CONTRACTOR SHALL INCLUDE COSTS NECESSARY TO MAKE ONE CHANGE IN EACH UNITS SHEAVE, BUSHINGS AND BELTS, BALANCING DAMPERS REQUIRED AND ANY OTHER DEVICES REQUIRED FOR THE CORRECT BALANCE OF THE SYSTEM AS REQUIRED BY THE TAB FIRM. 17. ALL INSULATION WILL HAVE FIRE /SMOKE RATING LESS THAN 25/50. 18. HVAC CONTRACTOR SHALL PROVIDE VENTILATION CONTROLS COMPLIANT WITH FMC 2010, SEC.405 FOR ALL SYSTEMS AND SHALL VERIFY EXISTING CONDITIONS FOR COMPLIANCE, AS REQUIRED, FOR A FULLY OPERATIONAL SYSTEM. 19. PROVIDE A MIN. OF 36" CLEARANCE IN FRONT OF ALL 120 -208 VOLT PANELS AND MIN. 42" CLEARANCE IN FRONT OF ANY 240 -480 VOLT PANEL. PROVIDE ADEQUATE SIDE CLEARANCE PER NEC. 20. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. DUCT AND PIPING OFFSETS, BENDS AND TRANSITIONS SHALL BE REQUIRED TO PROVIDE AND INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT. 21. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING, FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT, IN ORDER TO PROVIDE A FULLY INTEGRATED MECHANICAL AND CONTROLS SYSTEMS WITH THE EXISTING ONES. ANY DISCREPANCY BETWEEN EXISTING CONDITIONS AND PLANS, OR ADDITIONAL CLARIFICATION REQ'D SHALL BE BROUGHT TO THE ATTENTION OF ENGINEER PRIOR TO FINAL BIDDING AND WORK. 22. MATERIALS ALLOWED IN RETURN AIR PLENUMS OR ABOVE CEILINGS USED AS RETURN AIR PLENUM SHALL COMPLY WITH FMC 2010, SEC. 602.2.1. IF SPACE WITH RETURN AIR PLENUM HAS ANY DECK TO DECK PARTITIONS, AIR TRANSFER DUCTS MUST BE INSTALLED. 23. CLEARANCE FOR MAINTENANCE, SERVICE, REPAIRS, AND REPLACEMENT FOR ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED TO COMPLY WITH FMC 2010, SEC. 306. SERVICE ACCESS PANELS FOR MECH. EQUIPMENT IN CONCEALED SPACES SHALL BE PROVIDED TO COMPLY WITH THE REQUIREMENTS OF SEC. 306. 24• MANUFACTURER'S WARRANTY: CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF (1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR (5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING NON - OPERATIONAL PERIODS OR AS AGREED WITH OWNER. 25. IF REMODELLING AN EXISTING SPACE, THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID. CONTRACTOR SHALL INSPECT ALL EXISTING AND NEW COMPONENTS OF THE MECHANICAL SYSTEMS AND ENSURE THAT ALL ARE OPERATIONAL AND WORKING AS SHOWN ON THE APPROVED CD PLANS AT THE TIME OF C.O. ?l r� Z U z U w m RMSCO ARCHITECTS 1750 PONCE DE LEON BLVD CORAL GABLES, FL 33134 305.44SA288 305.444.4986 SEAL KAMM CONSULTING 1407 W. NEWPORT CII lM UM DMA BEACK R_ We (964) 94 M FAX MQ 9491201 Cc 0 U. Z 0 Q W Q .J W Z 0 W Cn 0 d. O IL C w z w U z J Q ui 2 F-- cn a w m m 0. W F_ W Z W Q 0 Z N W C 0 0 0 N PROJECT NUMBER 2012 -0423 DATE 07 -06 -12 SHEET M0.1 D a d 8 0 MECHANICAL SHEET INDEX ® DESCRvnc*4 FM6.1 MECHANICAL NOTES, SCHEDULES, LEGEND & INDEX MECHANICAL PLAN El MECHANICAL SCHEDULES AND DETAILS ?l r� Z U z U w m RMSCO ARCHITECTS 1750 PONCE DE LEON BLVD CORAL GABLES, FL 33134 305.44SA288 305.444.4986 SEAL KAMM CONSULTING 1407 W. NEWPORT CII lM UM DMA BEACK R_ We (964) 94 M FAX MQ 9491201 Cc 0 U. Z 0 Q W Q .J W Z 0 W Cn 0 d. O IL C w z w U z J Q ui 2 F-- cn a w m m 0. W F_ W Z W Q 0 Z N W C 0 0 0 N PROJECT NUMBER 2012 -0423 DATE 07 -06 -12 SHEET M0.1 D a d 8 0 MECHANICAL LEGEND ® NEW S/A CEILING DIFFUSER 4 CEILING EXHAUST FAN NEW R/A CEILING GRILLE El INLINE EXHAUST FAN EXISTING S/A CEILING DIFFUSER VARIABLE FREQ. DRIVE CONTROL PANEL EXISTING R/A CEILING GRILLE SUPPLY AIR SLOT / LINEAR DIFFUSER DIFFUSER OR GRILLE DESIGNATION WALL LOUVER / WALL DIFFUSER. EORAUST AI c DIFFUSER DESIGNATION L_ VOLUME CONTROL DAMPER Epp _ X EQUIPMENT TAG ► REDUCER OR INCREASER O THERMOSTAT NEW FLEX DUCT O HUMIDISTAT EXISTING FLEX DUCT O TEMPERATURE SENSOR NEW DUCTWORK POC- POINT OF CONNECTION ~ SUPPLY AIR _ _ _ EXISTING DUCTWORK RETURN AIR --'-u /c DOOR UNDER CUT S "Z" BOOT TRANSFER DUCT AP - ACCESS PANEL OROUND UP - SECTION MARK BELLMOUTH TAP A FIRE DAMPER (Z)DO DUCT SMOKE DETECTOR NOT ALL SYMBOLS MAY APPLY TO THESE PLANS ?l r� Z U z U w m RMSCO ARCHITECTS 1750 PONCE DE LEON BLVD CORAL GABLES, FL 33134 305.44SA288 305.444.4986 SEAL KAMM CONSULTING 1407 W. NEWPORT CII lM UM DMA BEACK R_ We (964) 94 M FAX MQ 9491201 Cc 0 U. Z 0 Q W Q .J W Z 0 W Cn 0 d. O IL C w z w U z J Q ui 2 F-- cn a w m m 0. W F_ W Z W Q 0 Z N W C 0 0 0 N PROJECT NUMBER 2012 -0423 DATE 07 -06 -12 SHEET M0.1 D a d 8 0