12-707-010LOCATE FLOOR DRAINS WHERE SHOWN ON DIMENSIONED ARCHITEC-
TURAL PLAN. IF FLOOR STRUCTURE INTERFERES WITH FLOOR DRAIN,
MOVE SIDEWAYS IF POSSIBLE, OTHERWISE MOVE BACK. ALWAYS LOCATE
WHERE EASILY ACCESSIBLE, BUT NOT IN FOOT TRAFFIC. IF SITUATION
IS FLOOR SLAB ON GRADE, PROVIDE BACKFILL PER SPECIFICATIONS.
IF CONCRETE FLOOR IS NOT EXISTING, SET DRAIN IN PLACE AND POUR
AROUND IT. IF CONCRETE FLOOR IS EXISTING, SAW CUT OR CORE DRILL
IT. SET DRAIN BODY IN PLACE AND POUR AROUND IT. RECESS TOP OF
FLOOR DRAIN 1/2" BELOW FLOOR SURFACE AND SLOPE FLOOR TO IT.
_ WALL BRANCH LINE FLOW TO FIXTURE.
WATER SUPPLY TO FIXTUR _ VERIFY 10 PSI DROP WHEN
FIXTURE IS OPEN TO ACTIVATE
AUTOMATIC TRAP TRAP PRIMER ACCORDINGLY.
PRIMER VALVE. SIOUX
CHIEF, 695 SERIES. KARP
FOLLOW ACCESS
MANUFACTURES DOOR
INSTRUCTIONS.
VACUUM CHROME
BREAKER ESCUTCHEON
PLATE
PROVIDE WYE SPUTTER
WITH DISTRIBUTOR FOR
MULTIPLE TRAP PRIMER
APPLICATION. FOLLOW
MANUFACTURES
INSTRUCTIONS.
WALL
CONCRETE FLOOR
FLOOR DRAIN. SEE
PLUMBING FIXTURE
SCHEDULE FOR SPEC.
• V.
MEMBRANE CLAMP-
ING COLLAR AND
SEEPAGE PAN
MAXIMUM TAILPIECE
LENGTH IS 2 FEET-
PRIME EZE WATER SAVER TRAP PRIMER, J
JAY R. SMITH, OR EQUAL SHALL BE AN lll�
ACCEPTABLE TRAP PRIMER ALTERNATIVE.
UNLIMITED DISTANCE WHERE ENLARGED WASTE
LINE IS USED AN A COMBINATION DRAIN AND
VENT SYSTEM PER FBC PLUMBING 2010
SECTION 912. OTHERWISE VENT PER CHAPTER 9.
(SEE FLOOR PLANS).
SLOPE WASTE IN ACCORDANCE WITH
TABLE 704.1 FBCP 2010. (CHART, THIS SHEET).
FLOOR DRAIN AND TRAP PRIMER DETAIL
NOT TO SCALE
A
MAR p
FL 3
'/
WA
RUNE TOLIN .
t G
2" GOLD EAM Y sio ANp
Ect 0 D W T5 05 LP VERI
5XISTItNG TOR ON.
.�, COACT HOC
EX
/ .
"
r
I
R LINE CEILING.
k" cOL�tEM IF'r � E AND
NEW 3 /1ER 5 VER FlaP
CONNE G COLSN LL
EXjS?i ACTIATION.
CON L10
EX
DOMESTIC WATER ISOMETRIC
NOT TO SCALE
E TO ERFYG
NT UNFl�
cT
NEW 5 o� TION.
C NT 015E AND
L
EXACT
21
i
1
Ir
2
I I
( I "
I I TO 'f
tRIFI LINE ' �p �r'� nN ON 05LP
" ANITAS�B CATION 4" SAN OW 0 ocAnON. , TO EOIFY
NEW 2M BEN ANp I,0 ECt N OTEMAn0N AN 2" V NG pE
CON NARY 51 LCV O G�NINA f EU= NNECtEN�B Np 051 A110N
5 Aft 5IZE� EXACT \X NT US ZE. A
EX EXACT
SANITARY ISOMETRIC
� r
i2 I r
I
(
J'
PLUMBING FIXTURE SCHEDULE
PLUMBING LEGEND
LAVATORY, KOHLER "CHESAPEAKE" K -1728 WALL MOUNT LAVATORY WHITE WITH KOHLER
HLAV
CORALIAS SINGLE CONTROL LAVATORY FAUCET MODEL# K -15593 & SELF CONTAINED
SANITARY SEWER PIPING
TEMPERATURE CONTROL NOT TO EXCEED 110'. ADA 34" TO TOP OF RIM MAX.
SHUT -OFF VALVE
ARM SUPPORT CARRIER FOR MOUNTING OF LAV. ZURN MODEL Z1231. (SPECIFY DOMESTIC MADE).
HWC
HANDICAPPED WATER CLOSET, TANK TYPE BOWL, KOHLER "HIGHLINE COMFORT HEIGHT" K -3427
CLEAN OUT TO GRADE
FLOOR MOUNTED WHITE, WITH LUSTRA OPEN FRONT SEAT WITH COVER K -4650.
FD
FLOOR DRAIN, SIOUX CHIEF 863 SERIES. PROVIDE TRAP PRIMER SIOUX CHIEF 695 SERIES.
SK
SINGLE STAINLESS STEEL SINK, 25 X 22 DAYTON MODEL #K -12522 WITH
HOT WATER PIPING (110')
KOHLER "FORTE" K- 10411 -K SINGLE HANDLE KITCHEN SINK FAUCET
IWH
TANKLESS WATER HEATER SHALL BE EEMAX MODEL# SP3208 /277 10 3.OKW
GENERAL NOTES:
1) - FIXTURES SHALL BE AS SHOWN OR EQUAL.
2) - ALL FIXTURES SHALL COMPLY WITH TABLE 604.4 OF FBC 2010.
3 - ALL FIXTURE TRIM PACKAGES INCLUDING BUT NOT LIMITED TO TRAP, ANGLE STOP, FLUSH VALVE,
SUPPLY TUBES, AND CLEANOUT COVER PLATES SHALL BE OF THE SAME FINISH AS THE ABOVE
SPECIFIED FAUCET AND PER ARCHITECTURAL FINISH SCHEDULE.
(4) - ALL FIXTURES SHALL BE ROUGHED IN PER MANUFACTURER CUT SHEET TO MAINTAIN UNIFORMITY.
PROVIDE TEST TEE
WITH SCREWED COUNTER-
SUNK ABS PLASTIC PLUG:
TAPERED - THREAD WITH
TFE JOINT COMPOUND. -
WHERE CLEANOUT TEE
IS CONCEALED IN A
CHASE OR PARTITION,
PROVIDE A ROUND 18
GAUGE STAINLESS STEEL
COVER WITH BEVELED
EDGES AND FLATHEAD
MACHINE SCREW.
CONCRETE
FLOOR
SLAB
a
i
i
i
0
• a
COLUMN OR PARTITION
AS SHOWN ON FLOOR PLAN
CLEANOUT FACE SHALL
BE WITHIN 4" OF WALL
SURFACE. PROVIDE
PIPE EXTENSION IF REQUIRED.
NOTE:
PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SANITARY WASTE BRANCHES
NOT SERVED WITH A FLOOR CLEANOUT: LOCATE ABOVE FIXTURE FLOOD RIM
WITHIN 4' OF FLOOR. CONSULT LOCAL CODES FOR OTHER WCO REQUIREMENTS.
WALL CLEANOUT DETAIL
NOT TO SCALE
PLUMBING LEGEND
CO
CLEAN OUT
5 -- -S
SANITARY SEWER PIPING
S.O.V.
SHUT -OFF VALVE
Sr - - - -3
VENT PIPING
COTC
CLEAN OUT TO GRADE
S- -
DOMESTIC COLD WATER PIPING
FD
FLOOR DRAIN
S- - - -S
HOT WATER PIPING (110')
CW
DOMESTIC COLD WATER
S- - - - JS
HOT WATER PIPING (140')
HW
DOMESTIC HOT WATER
S- - - - -j
HOT WATER RECIRCULATING PIPING
HWR
DOMESTIC HOT WATER RECIRCULATING
S- CD --- 6
CONDENSATE PIPING
HB
HOSE BIBB
SPCA -S
COMPRESSED AIR PIPING
VTR
VENT THRU ROOF
Sr -T &P -S
TEMPERATURE AND PRESSURE RELIEF
GATE VALVE
S- SD -S
STORM DRAIN PIPING
GLOBE VALVE
S- G -S
GAS PIPING
N
CHECK VALVE
x-0-3
PIPE RISE UP
GAS SOLENOID VALVE
PIPE DOWN OR DROP
GAS COCK
E--
CAPPED END OF PIPE
4#
WATER HAMMER ARRESTER (PDI No.)
POINT OF CONNECTION
9 FD
FLOOR DRAIN
P -TRAP
PROVIDE TEST TEE
WITH SCREWED COUNTER-
SUNK ABS PLASTIC PLUG:
TAPERED - THREAD WITH
TFE JOINT COMPOUND. -
WHERE CLEANOUT TEE
IS CONCEALED IN A
CHASE OR PARTITION,
PROVIDE A ROUND 18
GAUGE STAINLESS STEEL
COVER WITH BEVELED
EDGES AND FLATHEAD
MACHINE SCREW.
CONCRETE
FLOOR
SLAB
a
i
i
i
0
• a
COLUMN OR PARTITION
AS SHOWN ON FLOOR PLAN
CLEANOUT FACE SHALL
BE WITHIN 4" OF WALL
SURFACE. PROVIDE
PIPE EXTENSION IF REQUIRED.
NOTE:
PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SANITARY WASTE BRANCHES
NOT SERVED WITH A FLOOR CLEANOUT: LOCATE ABOVE FIXTURE FLOOD RIM
WITHIN 4' OF FLOOR. CONSULT LOCAL CODES FOR OTHER WCO REQUIREMENTS.
WALL CLEANOUT DETAIL
NOT TO SCALE
PLUMBING NOTES
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH FBC 2010,
APPLICABLE LOCAL CODES, RULES AND ORDINANCES.
2. PLUMBING CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE
HIMSELF WITH ALL EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL
EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE
A PART OF THIS CONTRACT.
5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
6. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND
TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO
BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR
ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES.
7. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
8. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH
THE PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ENGINEER /ARCHITECT
PRIOR TO BEGINNING CONSTRUCTION.
9. VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERTS OF ALL EXISTING UTILITIES
PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES.
10. WATER DISTRIBUTION PIPING ABOVE AND BELOW GROUND SHALL BE TYPE "L" COPPER.
ALTERNATIVE MAY BE USED IN COMPLIANCE WITH FBC PLUMBING 2010 TABLES 605.3 AND 605.4
WHEN APPROVED BY LOCAL JURISDICTION AND ENGINEER ON RECORD.
COORDINATE WITH LOCAL JURISDICTION FOR ADDITIONAL REQUIREMENTS.
PROVIDE ALTERNATE FOR CPVC PIPING EQUAL TO BFGOODRICH "FLOWGUARD GOLD" FOR WATER
KNOWN OR DETERMINED TO HAVE ACIDIC CHARACTERISTICS. CONTRACTOR SHALL PERFORM A
WATER TEST TO DETERMINE WATER CHEMISTRY PRIOR TO ANY WORK OR PIPING INSTALLATION
AND SHALL SUBMIT TEST RESULTS TO ENGINEER FOR REVIEW AND APPROVAL.
DISENFECTION OF POTABLE WATER SYSTEM SHALL COMPLY WITH FRCP 2010 SECTION 610.
11. SOIL, WASTE, VENT AND RAINWATER PIPING SHALL BE CAST IRON OR PVC, WHERE CODE ALLOWS.
PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUMS.
12. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY
MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR
TO INSTALLATION.
13. FURNISH AND INSTALL APPROVED WATER HAMMER ARRESTORS FOR ALL (GROUP) PLUMBING
FIXTURES. SIZED AND LOCATED PER MANUF.'S INSTALLATION INSTRUCTIONS AND WH -PDI 201.
14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND
EQUIPMENT CONNECTIONS.
15. ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PADS OR MATERIAL.
16. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM
FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL /FLOOR
SLEEVES WITH FIRE RATED FOAM, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS
AS PART OF THE PLUMBER'S WORK.
17. PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM
DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE BY
OWNER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE
AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
WHICH MAY HAVE BEEN DAMAGED.
18. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER
ARRESTORS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND
MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED.
19. PROVIDE COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS
PANEL FOR ALL WALL CLEANOUTS FINISH TO MATCH FIXTURE TRIM.
20. NO COMBUSTIBLE MATERIAL TO BE USED IN MECHANICAL ROOMS OR IN CEILING SPACES
WHERE USED AS RETURN AIR PLENUMS.
21. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN ELECTRICAL OR ELEVATOR
EQUIPMENT ROOMS.
22. ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM
LOCATING ALL VALVES SHALL BE PROVIDED FOR OWNER /OPERATOR.
23. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH ARMAFLEX INSULATION
PER TABLE 411.1 F.E.C. 2010. WHERE USED IN A RETURN AIR PLENUM PVC PIPING WITH
ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES.
SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING.
24. CONDENSATE LINES SHALL NOT DRAIN ON THE ROOFING SYSTEM OR ANY OF ITS COMPONENTS
AND CONDENSATE LINES NEED NOT COMPLY WITH MIN. CLEARANCE REQUIREMENTS
PER FBC 2010, PAR. 1522.3.5
25. PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL
SHUT -OFF.
26. HOT WATER PIPING INSULATION SHALL BE INSTALLED IN ACCORDANCE WITH FLORIDA BUILDING CODE
PLUMBING 2010 TABLE 607.2.1 CONTRACTOR SHALL USE ARMAFLEX OR EQUAL WHERE APPLICABLE.
WHERE DOMESTIC WATER TEMPERATURES CAN CAUSE SWEATING ALL COLD WATER PIPING SHALL BE
INSULATED WITH ARMAFLEX INSULATION, THICKNESS AS PER TABLE 503.2.8 OF FBC
ENRGY CONSERVATION.
27. STUDOR MINI/MAXI AIR ADMITTANCE VALVES MAY BE USED AS AN ALTERNATE TO
VENT PIPING THRU ROOF WHERE ACCEPTABLE BY THE PLUMBING OFFICIAL AND LOCAL
CODES. INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS.
ISSUED FOR PERMIT 7 -9 -12
ISSUED FOR CONSTRUCTION -
KAMM CONSULTING PROJECT #: 20
PROJECT MANAGER: GREG KEMP
�G 1407
..- CEA P
I i d Be;ich, Florida 33442
54.949.2 '06 R8N5.949*-;201
nng;g*ammco ultin .cord ..
atiott ofAuthti #81$9
STATE 9
ry
�I1
L_J
z
z
a-
RIESCO
ARCHITECTS
1750 PONCE DE LEON BLVD
CORAL GABLE% FL 33134
305.4484288 3054444986
AA0002678
SEAL
I;I_1 Lq
1407 W. NEWPOFI<T CEWS DAVE
DEE�W BEACH, FL 33442
W W -2200 FAX 041949.2201
ao
LL 0
oz��
aWcl) B
�z
Q
o �D
W QZ
� WQz =
0
z
co cf) �
ow�-
a: 0
am° 0
PEVOONS
PROJECT NUMBER
2012 -0423
DATE
07 -06 -12
P0.1
PLUMBING SHEET INDEX
SHEET#
DESCRIPTION 1
PO.1
PLUMBING NOTES, LEGENDS, DETAILS AND ISOMETRICS
P2.1
SANITARY DRAWINGS
P3.1
DOMESTIC WATER DRAWINGS
PLUMBING NOTES
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH FBC 2010,
APPLICABLE LOCAL CODES, RULES AND ORDINANCES.
2. PLUMBING CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE
HIMSELF WITH ALL EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL
EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE
A PART OF THIS CONTRACT.
5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
6. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND
TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO
BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR
ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES.
7. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
8. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH
THE PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ENGINEER /ARCHITECT
PRIOR TO BEGINNING CONSTRUCTION.
9. VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERTS OF ALL EXISTING UTILITIES
PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES.
10. WATER DISTRIBUTION PIPING ABOVE AND BELOW GROUND SHALL BE TYPE "L" COPPER.
ALTERNATIVE MAY BE USED IN COMPLIANCE WITH FBC PLUMBING 2010 TABLES 605.3 AND 605.4
WHEN APPROVED BY LOCAL JURISDICTION AND ENGINEER ON RECORD.
COORDINATE WITH LOCAL JURISDICTION FOR ADDITIONAL REQUIREMENTS.
PROVIDE ALTERNATE FOR CPVC PIPING EQUAL TO BFGOODRICH "FLOWGUARD GOLD" FOR WATER
KNOWN OR DETERMINED TO HAVE ACIDIC CHARACTERISTICS. CONTRACTOR SHALL PERFORM A
WATER TEST TO DETERMINE WATER CHEMISTRY PRIOR TO ANY WORK OR PIPING INSTALLATION
AND SHALL SUBMIT TEST RESULTS TO ENGINEER FOR REVIEW AND APPROVAL.
DISENFECTION OF POTABLE WATER SYSTEM SHALL COMPLY WITH FRCP 2010 SECTION 610.
11. SOIL, WASTE, VENT AND RAINWATER PIPING SHALL BE CAST IRON OR PVC, WHERE CODE ALLOWS.
PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUMS.
12. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY
MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR
TO INSTALLATION.
13. FURNISH AND INSTALL APPROVED WATER HAMMER ARRESTORS FOR ALL (GROUP) PLUMBING
FIXTURES. SIZED AND LOCATED PER MANUF.'S INSTALLATION INSTRUCTIONS AND WH -PDI 201.
14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND
EQUIPMENT CONNECTIONS.
15. ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PADS OR MATERIAL.
16. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM
FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL /FLOOR
SLEEVES WITH FIRE RATED FOAM, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS
AS PART OF THE PLUMBER'S WORK.
17. PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM
DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE BY
OWNER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE
AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
WHICH MAY HAVE BEEN DAMAGED.
18. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER
ARRESTORS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND
MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED.
19. PROVIDE COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS
PANEL FOR ALL WALL CLEANOUTS FINISH TO MATCH FIXTURE TRIM.
20. NO COMBUSTIBLE MATERIAL TO BE USED IN MECHANICAL ROOMS OR IN CEILING SPACES
WHERE USED AS RETURN AIR PLENUMS.
21. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN ELECTRICAL OR ELEVATOR
EQUIPMENT ROOMS.
22. ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM
LOCATING ALL VALVES SHALL BE PROVIDED FOR OWNER /OPERATOR.
23. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH ARMAFLEX INSULATION
PER TABLE 411.1 F.E.C. 2010. WHERE USED IN A RETURN AIR PLENUM PVC PIPING WITH
ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES.
SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING.
24. CONDENSATE LINES SHALL NOT DRAIN ON THE ROOFING SYSTEM OR ANY OF ITS COMPONENTS
AND CONDENSATE LINES NEED NOT COMPLY WITH MIN. CLEARANCE REQUIREMENTS
PER FBC 2010, PAR. 1522.3.5
25. PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL
SHUT -OFF.
26. HOT WATER PIPING INSULATION SHALL BE INSTALLED IN ACCORDANCE WITH FLORIDA BUILDING CODE
PLUMBING 2010 TABLE 607.2.1 CONTRACTOR SHALL USE ARMAFLEX OR EQUAL WHERE APPLICABLE.
WHERE DOMESTIC WATER TEMPERATURES CAN CAUSE SWEATING ALL COLD WATER PIPING SHALL BE
INSULATED WITH ARMAFLEX INSULATION, THICKNESS AS PER TABLE 503.2.8 OF FBC
ENRGY CONSERVATION.
27. STUDOR MINI/MAXI AIR ADMITTANCE VALVES MAY BE USED AS AN ALTERNATE TO
VENT PIPING THRU ROOF WHERE ACCEPTABLE BY THE PLUMBING OFFICIAL AND LOCAL
CODES. INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS.
ISSUED FOR PERMIT 7 -9 -12
ISSUED FOR CONSTRUCTION -
KAMM CONSULTING PROJECT #: 20
PROJECT MANAGER: GREG KEMP
�G 1407
..- CEA P
I i d Be;ich, Florida 33442
54.949.2 '06 R8N5.949*-;201
nng;g*ammco ultin .cord ..
atiott ofAuthti #81$9
STATE 9
ry
�I1
L_J
z
z
a-
RIESCO
ARCHITECTS
1750 PONCE DE LEON BLVD
CORAL GABLE% FL 33134
305.4484288 3054444986
AA0002678
SEAL
I;I_1 Lq
1407 W. NEWPOFI<T CEWS DAVE
DEE�W BEACH, FL 33442
W W -2200 FAX 041949.2201
ao
LL 0
oz��
aWcl) B
�z
Q
o �D
W QZ
� WQz =
0
z
co cf) �
ow�-
a: 0
am° 0
PEVOONS
PROJECT NUMBER
2012 -0423
DATE
07 -06 -12
P0.1