Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
12-1314-001
FIRE ALARM INSTALLATION & OPERATION NOTES: SYMBOL FiRE ALARM SEQUENCE OF OPERATION: ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. AND N.E.C. 760. ACTUATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT B DETECTOR OR WATER FLOW SWITCH SHALL CAUSE THE FOLLOWING OPERATIONS TO CONNECTIONS TO LIGHTS AND POWER SERVICE SHALL BE ON A OCCUR; DEDICATED BRANCH CIRCUIT. THE CIRCUIT AND CONNECTIONS SHALL BE 1. GENERAL ALARM ACTIVATION OF ALL PROGRAMMED SIGNAL CIRCUITS MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS SHALL 4X9 HAVE A RED MARKING AND BE ACCESSIBLE ONLY TO AUTHORIZED FOR ENTIRE BUILDING. PERSONNEL AND BE PER N.F.P.A, 72 2007 EDITION 2. LIGHT THE ASSOCIATED INDICATORS CORRESPONDING TO THE FIRE ALARM PANEL IS PROVIDED WITH STANDBY BATTERY PER N.F.P.A. ACTIVE SIGNAL CIRCUITS. 72 WITH 24 HOURS OF STANDBY AND 15 MINUTES OF ALARM (AS 3. A GENERAL ALARM SHALL BE ANNUNICATED UPON ACTIVATION OF REQUIRED). SHOULD LOSS OF NORMAL 120VAC POWER OCCUR, FiRE ANY PULL STATION, FLOW SWITCH & DETECTION DEVICE. A TROUBLE ALARM PANEL WiLL AUTOMATICALLY TRANSFER TO BATTERY. SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF A A CERTIFICATE OF COMPLETION WILL BE PREPARED AND A COPY DETECTION OR MANUAL DEVICE. A SUPERVISORY SIGNAL SHALL D PROVIDED TO THE OWNER AND THE CiTY FIRE RESCUE DEPARTMENT_ ANNUNCIATE ANY TAMPER, HVAC, OR DUCT DETECTOR ACTIVATION. SPS10A 4. IF MULTIPLE FLOORS, EACH ELEVATOR LOBBY, HOIST, AND MACHINE OWNER MANUALS, INSTALLATION INSTRUCTIONS, OPERATION ROOM SMOKE DETECTOR SHALL INITIATE AN ALARM CONDITION IN INSTRUCTIONS AND RECORD DRAWINGS SHALL BE AT THE SITE ON THE BUILDING AND RETURN ALL ELEVATORS TO THE PRIMARY OR COMPLETION OF JOB AND FINAL ACCEPTANCE. ALTERNATE FLOOR OF EGRESS IN COMPLIANCE WiTH ANSI ASIWE A17.1. INSTALLATION NOTES: 5. WATERFLOW SWITCH SHALL ACTIVATE GENERAL ALARM. ALL FIRE STOP PENETRATIONS SHALL BE MADE WiTH APPROVED N-=C. A VALVE TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY ELECTRICAL TUBING AND SHALL BE SEALED WiTH U.L. APPROVE FIRE STOP ALARM INDICATION. MATERIAL. 6. ANNUNCIATION OF THE ACTIVE DEVICE AT THE FIRE ALARM CONTROL COLOR CODING MAY NOT APPLY TO WiRE. PANEL AND ANY ANNUCIATORS, IN MONITORED BUILDING, SEND A (WIRE TO BE LABELED ACCORDINGLY.) SIGNAL TO THE U.L. MONITORING CENTER FOR ALARM, TROUBLE, CONDUIT SHALL BE A MINIMUM OF i /T AND 40% FILL MAXIMUM. WATERFLOW AND SUPERVISORY CONDITIONS. EST b TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE CONTROL FIRE ALARM SPECIFICATIONS: COMMUNICATOR. ALL EQUIPMENT TO BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE COMPATIBLE WiTH THE ALARM (AMPS) SYSTEM BEING USED. SYSTEM iS TO BE POWER LiMITED. ALL FLOW, TAMPER, PIV AND BACKFLOW WiLL HAVE MONITOR MODULES; SYSTEM TO BE CENTRAL STATION SERVICE AS PER NFPA -72. FIRE PROTECTION SPRINKLER PUMP MONITORING. (3 POINTS) 37 (A).FIRE PUMP RUN (B).FiRE PUMP FAIL (C).FIRE PUMP PHASE REVERSAL. FIRE ALARM PANEL SHALL BE LISTED FOR CENTRAL STATION SERVICE PER NFPA 72, 2007, ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC. VERIFY SECTION 8.3, UNLESS OTHERWISE SPECIFIED. EXACT LOCATIONS OF DEVICES AND WIRE ROUTING PRIOR TO STARTING THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY WORK. THE SYSTEM MANUFACTURER AND ARTICLE 760 OF THE NATIONAL ELECTRICAL CODE_ MOUNTING REQUIREMENTS: MINIMUM WIRE SIZE IS 12 AWG FOR GROUND CONNECTION. (NOTE: PANEL NEUTRAL OR MANUAL PULL STATIONS TO BE INSTALLED AT 48" A.F.F. CONDUIT GC -VM GROUND IS NOT ACCEPTABLE). MOUNT FIRE ALARM SYSTEM STROBES & SPEAKER / STROBES AT 8W A.F.F. ALL STROBE LIGHTS SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM AND FROM BOTTOM OF DEVICE OR 6' BELOW CEILING. SHALL BE SYNCHRONIZED IN OPEN AREAS. ALL AUDIBLE SIGNALS SHALL HAVE THREE (WHICH EVER IS LOWER) PULSE TEMPORAL PATTERN AND SOUND LEVEL SHALL BE AT LEAST 15 DBA ABOVE SMOKE DETECTOR SHALL NOT BE LOCATED WGH1N S OF AMBIENT SOUND LEVEL AND HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED SUPPLY AIR OUTLETS. 5 FT ABOVE THE FLOOR IN OCCUPIED AREAS. 32 FIRE ALARM CIRCUITS AND DEVICES SHALL BE CLASS "9% SMOKE DETECTORS TO BE INSTALLED AS PER NF.P.A. 72 WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM CEILING WiTH SIGA -278 12" MAXIMUM FROM CEILING_ 4" SQUARE (2 -1/8 "DEEP) BOX (OR 4- BOX). PROVIDE ADEQUATE SUPPORT FOR BOX iN CEILING FLEX IN CONDUIT 4" SQUARE :• fim MOIL- CEILING 4" SQUARE BOX TO 3-0 ADAPTER RiNG (OR NO RING IF 4-0 BOX IS USED) I I PLUG - IN DETECTOR BASE NOTE: MIN PIPE FLEX 1/2" FREE WiRE IN CEILING DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WiTH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. NOTE:3 CABLE NOTE: 3 FROM INTFC BOARD r TO NEXT DEVICE AT FACP[ * (WHERE APPLICABLE) NOTE: 1 300 �3121 0 \\ 0 a3TYP O p7lTYP LOOP ADDRESSJ LOOP` f ESS WIRING FOR ADB-FL BASE (STYLE 4) NOTE 1: DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE NOTE 2: DO NOT LOOP WIRE UNDER TERMINALS 1 & 2. BREAK WIRE RUN TO PROVIDE SUPERVISION NOTE 3: OBSERVE POLARITY. DO NOT GROUND CONTROL WIRES OR SHIELDS. TIE SHIELDS TOGETHER AT EACH DETECTOR. NOTE 4: SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE NOTE 5: RECORD THE LOOP ADDRESS & DEVICE TYPE IN THE SPACES PROVIDED ON TOTAL SQUARE FOOTAGE IS 243,680 96 DETECTORS AND 94 MODULES PER SLC WIRE LEGEND SYMBOL WIRE TYPE AND DESCRIPTION A 2 #16 FPLR ISOTEC P #- IR142SFPL1 -02 WIRE FOR DATA COMMUNICATION B 2 #14 FPLR ISOTEC P #- IR142SFPLI -02 WIRE FOR NOTIFICATION C 2 #16 FPLR ISOTEC P#-IR I 62SFPLI -02 WIRE FOR SPEAKER ADA HEIGHT REQUIRMENTS WITH DEEP 1900 BOX STROBE OR SPEAKER /STROBE . 80- A.F.F. OR 101011 6 "BELOW CEILING ° 0101 (WHICHEVER IS LOWER) PULL STATION 0 48" A.-. NOT TO SCAL' 1900 BOX PROVIDE ADEQUATE.UPPORT FOR BOX iN CEItNG 1 I CEILING 1 1 PLUG - IN 1 I DETECTOR BASE DETECTOR HEAD BIG MOUNTING M SHEET ROCK OR PLASTER TYPE CEILINGS (MUST BE INSTALLED WITFCONDUIT) THIS DIAGRAM IS FOR REPRESENTAiVE PURPOSES ONLY, AND iS NOT AN EXACT SPCIFiCATION. SCOPE OF WORK FIRE ALARM LEGEND COUNT SyU801- DEWCETYPE MODEL i1SANUFACTURE. STEM OHMS PER THOUSAND FIRE ALARM CONTROL PANEL ARE'BETWEEN 16VDC AND 33VDC REQUIRED STANDBY 2 F;�C_M WiTH (2 -LCX) SLC EXPANDER EST-2 EST 4X9 VD= VOLTAGE DROP & (AA -50) AMPLIFIERS 14 AWG 307 24 FP-/S-1 FIRE ALARM POWER SUPPLY BPS10A EST 1 ® REMOTE CABINET RACCR EST I O 25 WITH SIGA -APS & SiGA -AA50 SPS10A 0070 x 1 = 0 070 0 270 x 1 = 0 270 CIRCUIT #1 190 1.709 SPEAKER l STROBE G4RF -S7VM EST 1.498 Ix 1 1=1 1.498 CIRCUIT 93 2008 IxI 2 MS ER SPEAKER ! STROBE G4RFS7VM EST b S SPEAKER / STROBE (75cd) 757 -4A-RS EST ALARM (AMPS) 124 WEATHERPROOF 12 1498 37 7s, SPEAKER / STROBE (i IOcd) 757 -8A -RS EST CIRCXIT#3 180 WEATHERPROOF 12 2008 1 Q STROBE ONLY GC -VM EST CIRCUIT#4 129 CEIUNG MOUNT 12 2008 307 ® STROBE ONLY G1RF -VM EST 32 a PULL STATION SIGA -278 EST 8 © CONTROL MODULE SIGA -CCIS EST 182 O SMOKE DETECTOR SIGA -PS EST 2 �" J HEAT DETECTOR SIGA -HRS EST 4 DUCT DETECTOR SiGA -SD EST 4 [R� REMOTE TEST STATION SiGA -TRM EST - 3 CONTROL RELAY MODULE SIGA -CR EST 6 MONITOR MODULE SiGA -CT1 EST 810 TOTAL DEVICES (ER) EXISTING TO BE RELOCATED (WP) WATERPROOF RENOVATIONS TO DEUCES AS REQUIRED BY ACHA. AREA OF WORK iS SUITE 525aPACE ON FIFTH FLOOR ONLY. NO OTHER WORK WILL EE DONE UNDER THIS JOB. NEW SPEAKER /STROBE DNICE INSTALLED AND TIED INTO EXISTING LOOP. NEV SMOKE AND HEAT DETECTORS INSTALLED AND TED TO EXISTING DATA LOOP. NOTE: THIS IS WT A SPRINKLED BUILDING AD[ITIONAL NOTES 1. PRIVATE OFFICES COIFIRMED IN FIELD TO BE PRIVATE OFFICES ONiY. 2. ALL AUDIO VISUAL DEVICES HAVE BEEN CONFIRMED THROUGH OUT THE BfILDING TO MEET CODE PER OUR DESIGN. VD = 2 X L X R X I 5PERATW5 RANGE FOR DEVICES STEM OHMS PER THOUSAND 1000 ARE'BETWEEN 16VDC AND 33VDC REQUIRED STANDBY 18 AWG 7.77 REQUIRED ALARM TIME�� TOTAL ALARM 16 AWG 4X9 VD= VOLTAGE DROP TOTAL ALARM 14 AWG 307 L = ONE-WAY LENGTH OF CIRCUIT CURRENT PER 12 AWG 193 R- CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET - 3 568 10AWG 121 I = LOAD CURRENT PER UNIT (AMPS) POWER SUPPLY #15 TOTAL STEM AMPS MINIMUM ALARM REQUIRED STANDBY STANDBY STANDBY REQUIRED ALARM TIME�� TOTAL ALARM TOTAL STANDBY NT FACTOR 12 TOTAL ALARM DESCRIPTION (AMPS QTY CURRENT PER (AMPS) ON CURRENT - 3 568 PER UNIT (AMPS) 24 ITEM (AMPS) PER UNIT (AMPS) I O 25 (AMPS) SPS10A 0070 x 1 = 0 070 0 270 x 1 = 0 270 CIRCUIT #1 7 1.709 x 1 1.789 CIRCUIT #2 1.498 Ix 1 1=1 1.498 CIRCUIT 93 2008 IxI 1 1=1 2008 . CIRCUIT #4 2008 1XI 1 1=1 2008 TOTAL SYSTEM 0070 TOTAL SYSTEM 7' STANDBY (AMPS) ALARM (AMPS) 124 KCUUKtUtWr.KAIRA" 11Mr rKUM WYA !L 4.4.7.aL.L.(7jS4.4.1.a. it CTA?f11V•7At -"I71, At APU 1S IJIM RFC Y1Mifl= n- y9wItn" PS16 REQUIRED TOTAL REQUIRED AMPS MINIMUM REQUIRED REQUIRED STANDBY STANDBY STANDBY REQUIRED ALARM TIME�� TOTAL ALARM ALARM TIME (HOURS) FACTOR 12 CAPACITY (HOURS) (AMPS 0 DROP tOP AT (AMPS) I + 1.888 - 3 568 X 12 24 X1 0 070 1.080 I O 25 X 7553 1.888 PS16 REQUIRED REQUIRED NOTIFICATION TYPE AMPS MINIMUM STANDBY ALARM REQUIRED ABA. R DERATWG AMPIHOl1R CAPACITY CAPACITY TERY FACTOR 12 BATTERY (AMPHR) (AMPS 0 DROP tOP AT REQUIRED 1.600 + 1.888 - 3 568 X 12 =1 4 282 TOTALS FOR CIRCUIT 91 QTY NOTIFICATION TYPE AMPS TOTAL 1 G4RF-67VM 0239 0239 8 G1RF -VM 255 1.530 0 CIRCUIT 0 000 0.000 0 DROP tOP AT 0 000 0.000 0 WA77SRB1f4BWW PER CIRCiBT 0.000 0000 0 T LAS 0 000 0 000 0 ((F 0000 0 VOLTAGE 0.000 I 7 TOTAL AMPS: TOTALS FOR CIRCUIT #2 QTY I NOTIFICATION TYPE AMPS TOTAL 2 G4RF -S7VM 0239 0.478 4 G1RF -VM 0255 1.020 0 CIRCUIT 0 000 0.000 0 DROP tOP AT 0 000 0 000 0 WA77SRB1f4BWW PER CIRCiBT 0000 0000 0 T LAS 0 000 0 000 0 ((F 0 000 0 000 0 VOLTAGE 0 000 0 000 Ho TOTAL AMPS: 1 498 MINIMUM AMPIHOU R BATTERY REQUIRED 12 TOTALS FOR CIRCUIT #3 QTY NOTIFICATIONTYPE AMPS I TOTAL 2 G4RFS7VM 0239 0478 6 G1RF -VM 0255 I.SW 0 CIRCUIT 0000 0000 0 DROP tOP AT 0 000 0 000 o WA77SRB1f4BWW PER CIRCiBT 0000 CL 000 0 T LAS 0000 0 000 0 ((F 0 000 0 000 0 VOLTAGE Flow 0.000 8 TOTALAMPS, 2008 TOTALS FOR CIRCUIT #4 QTY I NOTIFICATION TYPE AMPS TOTAL 2 G4RF -S7VM 0239 0478 e G1RF -VM 0255 1.530 0 CIRCUIT 0.000 0 000 0 DROP tOP AT 0 000 0 000 0 WA77SRB1f4BWW PER CIRCiBT 0000 0000 0 T LAS 0 00o 0 000 0 ((F 0.000 0.100 00 VOLTAGE 0 000 0 000 8 i TOTALAMPS.1 2008 VOLTAGE DROP CALCULATIONS comes WIRE RUN OHMS PER TOTAL 20 POWER VOLTAGE VOLTAGE 27 CIRCUIT ONE WAY WIRE SIZE CIRCUIT 0.5 SUPPLY READING DROP tOP AT ACCEPTABLE NUMBER ET)) WA77SRB1f4BWW PER CIRCiBT 13.5 DROP 4-1/2(114) T LAS 2 (51) VOLTAGE DROP 2 ((F 1/2-20 (13 -508) DRAW 1 (25) VOLTAGE 4-1/2(114) END 3-1/4(83) 1 (25) 2 OHMS AWG 22 -30 (558 -762) 2 (51) 1/2(51) 2 5-1/2(140) 1/2-6 (13 -152) CIRCUIT 01 129 _193 12 1 789 0 881 204 1952 4% YES CIRCUIT #2 124 1.83 12 1498 0.717 204 1968 4% YES CIRCXIT#3 180 193 12 2008 1395 204 1900 7% YES CIRCUIT#4 129 1.93 12 2008 1000 20.4 19.40 5% YES . WORST CASE SCENARIO #1 SP01 10 T C4lCL/Jil nots AA50 SMMN C4LCL[A comes 094W 7t7TAL ORAW eWCWr.f 20 0.5 10 C17 aU2 27 0.5 13.5 CMCWr3 26 0.5 13 12 7t7TAL DA4 W (WATTS) ALL C 11=05 36.5 7VTAL WATTS ALLOWEV 50 WA77SRB1f4BWW PER CIRCiBT 13.5 #2 MM AA50 SMMN C4LCL[A 770M Min. Caulk Thkns in. (mm) CDUVI DRAW 7t7TAL DRAW C?RCWr4 25 0.5 12.5 CZRCiBTS 28 0.25 7 CNCWTO. 23 0.5 11.5 Cwaff7 24 1 0.5 12 1/4 (6) (a) MTAL DA4 W (WA 775) ALL C92LXQ75 43 707A WA 775 ALLOWED 50 WATI5RB 11111 G PER C7MCWT 7 AREA OF WORK 5TH FLOOR KEY PLAN f�_ SCALE. N.T.S. 4 SS 1 e.� FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS U L v LABORATORIES, INC.® FOR USE IN THROUGH - PENETRATION US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FiRE ® RESISTANCE DIRECTORY 50L6,9OG9 SECTION A -A System No. C-AJ -1044 June 15, 2005 F Ratings - 2, 3, and 4 Hr. (See items 2A and 4) T Rating - 0 Hr. L Rating at Ambient - 2 CFM /sq, ft. L Rating at 400 F - less than 1 CFM /sq. ft. W Rating - Class i (See item 4) 1. Floor or Wall Assembly Lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3) concrete. Except as noted in table under Item 4, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units *. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow -core precast concrete units is 7 in. (178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. IA. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit. D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Packing Material - Polyethylene backer rod or nom l in. (25 mm) ihickness of tightly- packed mineral wool butt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4). 4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table: Min. Flo1or or Wall Thkns M. (mm) Nom. Pipe Tube or Conduit Diam in. (mm) Max Annular Space in. (mm) Min. Caulk Thkns in. (mm) F Rating Hour 2-112(64) 1/2 -12 (13 -305) 1-3/8(35) 1/2(13) 2 2-1/2(64) 1/2 -12 (13 -305) 3 -1/4 (83) 1 (25) 2 4-112(114) 1/2-6 (13 -152) 1-3/8(35) 1/4 (6) (a) 2 4-1/2(114) 1/2-12 (13 -305) 1-1/4(32) 1/2(13) 2 4-1/2(114) 1/2-20 (13 -508) 2 (51) 1 (25) 2 4-1/2(114) 1/2-20 (13 -508) 2 (51) 1 (25) 2 4-1/2(114) 1/2-12 (13 -305) 3-1/4(83) 1 (25) 2 4-1/2(114) 22 -30 (558 -762) 2 (51) 1/2(51) 2 5-1/2(140) 1/2-6 (13 -152) 1-3/8(35) 1 (25) (b) 2 (a) Min 2 in. (51 mm) thickness of mineral wool batt insulation required in annular space. (b) Min 1 in. (25 mm) thickness of mineral wool batt insulation required in annular space on both sides of floor or wall assembly. Min 1 in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wall assembly. 3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant. (Note: W Rating applies only when FB -3000 WT sealant is used.) *Bearing the UL Classification Marking *NOTE This material was extracted by 3M fire protection products from 2004 edition of the UL fire resistance directory. 5TH FLOOR SUITE 525 FIRE ALARM PLAN n SCALE: 1/8" = V 14 , O Pg S P� o FILL VOID OR CAVITY MATERIALS CLASSIFIEC$Y UNDERWRITERS LABORATORIES, INC.® FOR USE IN THROUGH - PENETRATION US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE RESISTANCE DIRECTORY 5OL6,9OG9 SECTION A -A System No. WL -3001 September 07, 2004 F Ratings - 1 and 2 Hr. (See items T Rating - 3/4, 1, 1-1/2 and 2 Hr. (See iem 2) L Rating at ambient -15 CFM /sq. ft. (See item 3) L Rating at 400 F - less than 1 CFM /sq. ft. (be item 3) 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the mannerJescribed in the individual U300 or U400 Series Wall or Partition Designs in he UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studsor steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 6 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to bt min 3-5/8 in. wide by 1 -3/8 in. deep channels spaced max 24 in OC. B. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 ft wide witf• square or tapered edges. The gypsum wallboard type, thickness, number ollayers and sheet orientation shall be as specified in the individual Wall orfartition Design. Diam of circular through opening to be 3/8 in. to 5/8 in. larger then outside diam of cable or cable bundle. C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached to studs with cement coated nails as specifiedin the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self- tapping bugle -head steel screws as specified in the individual Wall or Partition Design. The hourly F Rating of the firestop system is equal to the Dourly fire rating of the wall assembly in which it is installed. 2. Cables - Individual cable or max 1 in. diam cable bundle installed in through opening with an annular space of min 0 in. (point contact) to max 3/4 in. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride PVC insulation and jacket materials. When max 25 pair telephone cable is used, T Rating is 2 hr.W hen 50 to 150 pair telephone cable is used in 1 hr fire rated wall, T Rating is 3/4 hr.When 50 to 150 pair telephone cable is used in 2 hr fire rated wall, T Rating is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ("Romer') nonmetallic sheathed cable with PVC insulation and jacket materials. When Type NM cable is used, max T Rating is 1 -1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of 5/8 in. When fiber optic cable is used, max T Rating is 2 hr. O. Max 12 AWG multi conductor (max seven conductors) power /control cable with cross - linked polyethylene (XLPE) insulation and XLPE or PVC jacket materials. When multi conductor power /control cable is used, max T Rating is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables Wth polyvinyl chloride insulation and jacket materials. 3. Fill,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material installed to completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 in. diam bead of caulk or putty applied to perimeter of cable(s) at its egress from each side of the wall. 3M COMPANY - MP+ Stix putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is used.) *Bearing the UL Classification Mark i N5 140o THE FOLLOWING LIFE SAFETY FEATURES SHALL BE PROVIDED AT 71ME OF OCCUPANCYs Lei°- P,-f 7-1,_ APPROVE0 NOTED ML"H -DALIE COUNTY FIRE DEPARTMENT BLDG. PERMIT_ FIRE ALARM FIRE SUPPRESSION WATER MAIN EXT.__ HATE: Ig Z By: FM ALARM SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NFPA 72; 70;101• FiRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FiNAL INSPECTION, AS PER NFPA 72 V Z �� m to J a _ > FW-5]p pU2 WW 17 511 ELI _nag �> M0 010 0to01 _jaw L v N �M � wQ W O Co .II O O W O W tZ REVISIONS: ti „ .� rn l' o N0 i_- 0 0 1- U `j N • �, E o 0 p J >n a.s W W c) v�� mN Co Lu it @)Q Z DLL[ o� tiQ� mW Q W �J C D 04a W o w v PROJECT NUMBER: 000000 DATE: SCALE: 11/05/12 1/811 DRAWN BY: CHECKED BY: S.D. D.N. 1 OF 2