SCOPE OF WORK
1. SCOPE OF WORK iNVOVLES THE RELOCATION OF EXISTING
DEVICES IN AN EXISTING CORRIDOR SPACE. SCOPE OF
WORK HAS A TOTAL AREA OFA00 SQ. FT. OF AN EXISTING
CORRIDOR ON THE 7TH FLOOR.
THE FIRE ALARM SYSTEM IS AN ADDRESSABLE INTELLIGENT
SYSTEM. THE SYSTEM HAS A SLC DEVICE CAPACITY OF 97
DETECTORS, AND 94 MODULES, X2 SLC LOOPS, FOR A TOTAL OF
380 POINTS.
2. THE MAXIMUM HEIGHT OF CEILING 9'-8 ".
3. SEE BATTERY CALCULATIONS FOR MAXIMUM LENGTH PER
INDICATING CIRCUIT.
4. BUILDING IS FULLY SPRINKLERED.
cg s r o FiLL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS
o LABORATORIES, iNC.0 FOR THROUGH - PENETRATION
US FiRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE
•+ RESISTANCE DIRECTORY 50L6,90G9
2 4 1
4
A
A
NOTIFICATION DEVICES x
,WJSTR 75cd
13
...
A 3
2
SECTION
AA
System No. C-AJ -1044
June 15, 2005
F Ratings - 2, 3, and 4 Hr. (See items 2A and 4)
T Rating- 0 Hr.
L Rating at Ambient - 2 CFM/sq. ft
L Rating at 400 F - less thaw 1 CFM/sq. ft
W Rating - Class I (See item 4)
1. Floor or Wait Assembly
Lightweight or normal weight (100 -150 pcf or 1600 -2400 kgtm3) concrete. Except as
noted in table under Item 4, min thickness of solid concrete floor or wall assembly is
4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL
Classified hollow lore Precast Concrete Units*. When floor is constructed of hollow
core precast concrete units, pacing material (Itenr 3) and caulk ffdl material (Hens 4) to
be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly
may also be constructed of any UL Classified Concrete Blocs *. Max diam of'opening is
in solid lightweight or normal weight concrete. Floor is 32 in. (813 min). Max diam of
opening in floor constructed of hollow -core precast concrete units is 7 in. (178 mm). See
Concrete Blacks- (CAZT) and Precast. Concrete. Units (CFTV) cftVwies in the Fire
Resistance Directory for names of manufacturers.
IA. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule
10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may
extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wa1L Max
16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier)
galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a
max of 1/2 in. 0 3 mm) beyond either surface of floor or wall.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either
concentrically or eccentrically within the firestop system. Max annular space between
pipe, conduit or tubing and edge of through opening or sleeve is dependent on the
parameters shown in Item 4. Min annular space between pipe or conduit and edge of
through opening is 0 in. (0 mm) (pant contact). Pipe conduit or tubing to be rigidly
supported on both sides of floor or wall assembly. The following types and sizes of
metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nan 30 in. (762 mm) diem (or smaller) Schedule 10
(or heavier) steel pipe.
B_ Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile lion pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.
D Conduit - Nom 4 in. (102 mm) dam (or smaller) steel electrical metallic tubing.
E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L
(or heavier) copper tube.
F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular
(or heavier) copper pipe.
3. Packing Material - Polyethylene backer rod or norm 1 in. (25 mm) thickness of
tightly- packed mineral wool batt or glass fiber insulation firmly packed into opening as a
permanent form. Packing material to be recessed from top surface of floor or from both
surfaces of wall as required to accommodate the required thickness of caulk fill material
(item 4).
4. Fi1L,Vad or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush
with top surface of floor. In wall assemblies, required caulk thickness to be installed,
symmetrically on both sides of wall, flush with wall surface. At pant contact location
between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm)
dram bead of caulk shall be applied at top surface of floor and at both surfaces of wall.
The hourly F Ratings and the min required caulk thicknesses are dependent upon a
number of parameters, as shown in the following table:
Min. Floor or Wall
Non. Pipe Tube or
Max Annular
Min. Caulk
F Rating
Thkns in. (mm)
Conduit Diam in. (mm)
Space in. (mm)
Thkns in. (mm)
Hour
2-1/2(64)
1/2 -12 (13-305)
1-318(35)
12 (13)
2
2-1/2(64)
1/2 -12 (13- 305)
3-1/4(83)
1 (25)
2
4-1/2(114)
1/2-6 (13 -152)
1- 3/8(35)
1/4 (6) (a)
2
4-112 (114)
1/2 -12 (13 -305)
1- 114(32)
12 (13)
2
4-1/2(114)
1/2:20 (13- 508)
2 (51)
1 (25)
2.
4-1/2(114)
1/2 -20 (13-508)
2 (51)
1 (25)
2
4-1/2(114)
12 -12 (13-305)
3-1/4 (83)
1 (25)
2
4-1/2(114)
22-30 (558 -762)
2 (51)
1/2(51)
2
542 (140)
12-6 (13 -152)
1-3/8 (35)
1(25) (b)
2
(a)Min 2 in. (51 mm) thickness of mineral wool batt insulation required in annular space.
(b)Min 1 in. (25 mm) thickness of mineral wool bait insulation required in annular space
on both sides of floor or wall assembly. Min 1 in. (25 mm) thickness of caulk to be
installed flush with each surface of flair or wall assembly.
3M COMPANY - CP 25WB+ caulk or FB -3000 Wr sealant. (Note: W Rating applies
only when FB -3000 WT sealant is used.)
*Bearing the UL Classification Marking
*NOTE
This material was extracted by 3M fire protection products from 2004 edition of the
UL fire resistance directory.
vrig s ' F.� FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS
0 o LABORATORIES, INCAD FOR USE IN THROUGH - PENETRATION
FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FiRE
RESISTANCE DIRECTORY 501.6,90G9
SECTION
AA
System No. WIL-3001
September 07, 2004
F Ratings -1 and 2 Hr. (San items 1)
T Rating- 314,1.1-1/2 and 2 Hr. (See item 2)
L Rating at ambient -15 CFM/sq. R (See item 3)
L Rating at 400-F - less than 1 CFM/sq_ fL (See item 3)
1. Waft Assembly - The 1 or 2 hr fire -rated gypsum waflboardfstud wall assembly shall
be constructed of the materials and in the manner described in the indnidual U300 or
U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features:
A. Studs - Wall framing may consist of either woad studs or steel channel studs. Wood
studs to consist of nom 2 by 4 in. lumber spaced 16-in. OC with nom 2 by 4 in. lumber
4 end plates and cross braces. Steel studs to be min 3-5/8 in. wide by 1-3/8 in, deep
channels spaced max 24 in OC.
B. Gypsum Board* - Nom 1/2 or 518 in. thick, 4 ft wide with square or tapered edges.
The gypsum wallboard type, thickness, number of layers and sheet orientation shall be
as specified in the individual Wall or Partition Design. Diam of circular through opening
to be 3/8 in. to 518 in. larger than outside diam of cable or cable bundle.
C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached
to studs with cement coated nails as specified in the - individual Wall or Partition Design.
When steel channel stud framing is employed, gypsum wallboard attached to studs with
Type S self - drilling, self - tapping bugle -head steel screws as specified in the individuat
Wall or Partition Design.
The hourly F Rating of Owfirestop system is equal to the hourly fire rating of the wall
assembly in which it is installed.
2, Cables. - Individual cable or max I in, diam cable bundle installed . in through opening
with an annular space of min 0 in. (pant contact) to max 314 in. Cable to be rigidly
supported on both sides of wall assembly. The following types and sizes of cables may
be used:
A. Max. 150 pair Nor 24 AWG copper conductor telephone cable with polyvinyt chloride.
PVC insulation acid jacket materials. When max 25 pair telephone cable is used,
T Rating is 2 hr.When 50 to 150 pair telephone cable is used in 1 hr fine rated wall,
T Rating is 314 hr.When 50 to 150 pair telephone cable is used in 2 hr fire rated wall,
T Rating is 1 hr.
B. Max No. 10 AM multiple copper conductor Type IWVh ("Ronal") nonmetallic
sheathed cable with PVC insulation and jacket materials. When Type NM cable is used,
max T Rating is 1 -112 hr.
C. Multiple fiber optical communication cable jacketed with PVC and having a max
outside-diem of 518. in.. When fiber optic cable is used, max T Rating is 2 hr-
O: Max 12 AWG multi conductor (mac seven conductors) power /control cable with
cross- linked polyethylene tXLPE) insulation and XLPE or PVC jacket materials. When►
mutti corxWor power/control cable is used, max T Rating is 2 hr.
E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with
polyvinyl chloride insulation and jacket materials.
3_ Ful,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material
installed to completely fill annular space between cable and gypsum wallboard on both
sides of wall and with a nun 1/4 in. darn band of caulk or putty applied to perimeter of
cable(s) at its egress from each side of the wall.
3M COMPANY - MP+ Stix putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap
putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is
*Bearing the UL Classification Mark
P22 CURRENT PER DEVICE
STANDBY
r
BPSiOA
70 mA
270 mA
A
NOTIFICATION DEVICES x
,WJSTR 75cd
13
239 mA
4 mA
3107 mA
STR 75W
22
255 mA
0 mA
5610 mA
TOT. CURP, RATINGS ALL DEV. IirwA,B,C
70mA
8987 mA
D
TOTAL CURR. CONVERTED TO AMPS line D x .001
0.07 A
8.987 A
E
F
G
NUMBER OF STANDBY HOURS (24 or 60 for-NFPA)
24 Hr
Multiply lines E & F Total standby AH
1.68 AH
ALARM SOUNDING PERIODIHOURS
15 MIN= 0.250 HRS
I-
0.2520 Hr
H
I
MULTIPLY LINES E & H
mom=
ADD LINES G & 1
3.944724 AH
W_M�
J
K
MULTIPLY LINE J BY 1.20 (2016 EXTRA FOR
DESIRED PERFORMANCE (1.2 Derating Factor)
4.733669 AH
On
soon
it
mom
r, • • •
••
y
son�
1111iffAll Dial _ •
10
ME--
•.an.nt•*
■0
•
mom
Ell 4 . •4Z 1kcaA
vrig s ' F.� FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS
0 o LABORATORIES, INCAD FOR USE IN THROUGH - PENETRATION
FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FiRE
RESISTANCE DIRECTORY 501.6,90G9
SECTION
AA
System No. WIL-3001
September 07, 2004
F Ratings -1 and 2 Hr. (San items 1)
T Rating- 314,1.1-1/2 and 2 Hr. (See item 2)
L Rating at ambient -15 CFM/sq. R (See item 3)
L Rating at 400-F - less than 1 CFM/sq_ fL (See item 3)
1. Waft Assembly - The 1 or 2 hr fire -rated gypsum waflboardfstud wall assembly shall
be constructed of the materials and in the manner described in the indnidual U300 or
U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features:
A. Studs - Wall framing may consist of either woad studs or steel channel studs. Wood
studs to consist of nom 2 by 4 in. lumber spaced 16-in. OC with nom 2 by 4 in. lumber
4 end plates and cross braces. Steel studs to be min 3-5/8 in. wide by 1-3/8 in, deep
channels spaced max 24 in OC.
B. Gypsum Board* - Nom 1/2 or 518 in. thick, 4 ft wide with square or tapered edges.
The gypsum wallboard type, thickness, number of layers and sheet orientation shall be
as specified in the individual Wall or Partition Design. Diam of circular through opening
to be 3/8 in. to 518 in. larger than outside diam of cable or cable bundle.
C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached
to studs with cement coated nails as specified in the - individual Wall or Partition Design.
When steel channel stud framing is employed, gypsum wallboard attached to studs with
Type S self - drilling, self - tapping bugle -head steel screws as specified in the individuat
Wall or Partition Design.
The hourly F Rating of Owfirestop system is equal to the hourly fire rating of the wall
assembly in which it is installed.
2, Cables. - Individual cable or max I in, diam cable bundle installed . in through opening
with an annular space of min 0 in. (pant contact) to max 314 in. Cable to be rigidly
supported on both sides of wall assembly. The following types and sizes of cables may
be used:
A. Max. 150 pair Nor 24 AWG copper conductor telephone cable with polyvinyt chloride.
PVC insulation acid jacket materials. When max 25 pair telephone cable is used,
T Rating is 2 hr.When 50 to 150 pair telephone cable is used in 1 hr fine rated wall,
T Rating is 314 hr.When 50 to 150 pair telephone cable is used in 2 hr fire rated wall,
T Rating is 1 hr.
B. Max No. 10 AM multiple copper conductor Type IWVh ("Ronal") nonmetallic
sheathed cable with PVC insulation and jacket materials. When Type NM cable is used,
max T Rating is 1 -112 hr.
C. Multiple fiber optical communication cable jacketed with PVC and having a max
outside-diem of 518. in.. When fiber optic cable is used, max T Rating is 2 hr-
O: Max 12 AWG multi conductor (mac seven conductors) power /control cable with
cross- linked polyethylene tXLPE) insulation and XLPE or PVC jacket materials. When►
mutti corxWor power/control cable is used, max T Rating is 2 hr.
E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with
polyvinyl chloride insulation and jacket materials.
3_ Ful,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material
installed to completely fill annular space between cable and gypsum wallboard on both
sides of wall and with a nun 1/4 in. darn band of caulk or putty applied to perimeter of
cable(s) at its egress from each side of the wall.
3M COMPANY - MP+ Stix putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap
putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is
*Bearing the UL Classification Mark
P22 CURRENT PER DEVICE
STANDBY
JALARM
BPSiOA
70 mA
270 mA
A
NOTIFICATION DEVICES x
,WJSTR 75cd
13
239 mA
4 mA
3107 mA
STR 75W
22
255 mA
0 mA
5610 mA
TOT. CURP, RATINGS ALL DEV. IirwA,B,C
70mA
8987 mA
D
TOTAL CURR. CONVERTED TO AMPS line D x .001
0.07 A
8.987 A
E
F
G
NUMBER OF STANDBY HOURS (24 or 60 for-NFPA)
24 Hr
Multiply lines E & F Total standby AH
1.68 AH
ALARM SOUNDING PERIODIHOURS
15 MIN= 0.250 HRS
0.2520 Hr
H
I
MULTIPLY LINES E & H
2.264724 A14
ADD LINES G & 1
3.944724 AH
12 A/H PROVIDED
J
K
MULTIPLY LINE J BY 1.20 (2016 EXTRA FOR
DESIRED PERFORMANCE (1.2 Derating Factor)
4.733669 AH
4"SQUARE BOX TO
ADAPTER
•• NO RING IF 4-0
:• USED)
DETECTOR
.rr■�� BASE
NOTE: MIN PIPE FLEX 1/2"
FREE WIRE IN CEILING DETECTOR HEAD
BOX MOUNTING OUT OR INTERLOCKING-TYP
CEILINGS WITH SYSTEMS • IN t. •
THIS DIAGRAM •- REPRESENTATIVE PURPOSES ONLY,
AND IS NOT AN EXACT SPECIFICATION.
FROM iNTFC BOARD t
AT FACP `=
NOTE: I
•, •,
■ r■ - r rr
WIRING FOR ADB-FL BASE (STYLE 4
• NOTE: 3
TO NEXT DEVICE
(WHERE APPLICABLE)
NOTE 2: DO NOT LOOP WIRE UNDER1`ERMINALS I & 2-
BREAK WIRE RUN TO PROVIDE SUPERVISION
NOTE 3. OBSERVE. POLARITY. rr NOT GROUND CONTROL WIRES ••
SHIELDS. r., TOGETHER AT EACH DETECTOR.
NOTE ROTARY DIALS ON OF DETECTOR HEAD TO
CORRESPOND TO THE LAST TWO DIGITS OF DEVICE LOOP ADDRESS.
REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE
NOTE 5r RECORD TW LOOP ADDRESS & DEVICE TYPE IN THE SPACES PROVIDED ON
ADA HEIGHT• REQUIRMENT3'
WITH DEEP
19W Box
STROBE OR _
SPEAKER/STROBE .
80" A.F.F. OR loot
6• BELOW CEILING —9,00
(WHICHEVER IS LOWER)
PULL STATION
48* A.F.F.0 00
0
NOT TO SCALE
• r.s • •
.t
ME ATAW #
1 r IN ACCORDANCE
N'FPA72,70,-
OF • �..: k • ♦ : •
O
a
1
i
REVISIONS,
PER CITY COMMENTS
1 BY: TF 09/28112
0 �tt41et.rtrr®
c,
to
ztx
' `1 `• ` l( 4%d • evj
•
l �p � + + • r,�r
+�„ +xs• tt�4;
.cc) w vo�°i
•ZJ �� `-=Co� Q
C0 "Z5ccSC31q'
crlrgj�Q CO) J
I
Z LL q
ui � Cn wqa
a-- aav[L_
(D
'2QWaj�� W
�t- �
4 U wQ ® U
Z 2 vo t j
aw� emu'
PROJECT NUMBER:
000000
DATE: SCALE:
09/06/12 1/8
.