12-1044-002FIRE ALARM INSTALLATION 8r OPERATION NOTES: FiRE ALARM SEQUENCE OF OPERATION: ACTUATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT DETECTOR OR WATER FLOW SWITCH SHALL CAUSE THE FOLLOWING OPERATIONS TO OCCUR; 1. GENERAL ALARM ACTIVATION OF ALL PROGRAMMED SIGNAL CiRCUITS, ON FLOOR OF INCIDENCE AND FLOOR ABOVE AND BELOW. (IF MULTIPLE FLOORS) i 2. LIGHT THE ASSOCIATED INDICATORS CORRESPONDING TO ACTIVE SIGNAL CIRCUITS. 3. A GENERAL ALARM SHALL BE ANNUNCCATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH & DETECTION DEVICE. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF A DETECTION OR MANUAL DEVICE. A SUPERVISORY SIGNAL SHALL ANNUNCIATE ANY TAMPER, HVAC, OR DUCT DETECTOR ACTIVATION. 4. IF MULTIPLE FLOORS, EACH ELEVATOR LOBBY, HOIST, AND MACHINE ROOM SMOKE DETECTOR SHALL INITIATE AN ALARM CONDITION IN THE BUILDING AND RETURN ALL ELEVATORS TO THE PRIMARY OR ALTERNATE FLOOR OF EGRESS IN COMPLIANCE WITH ANSi ASME A17.1. 5. WATERFLOW SWITCH SHALL ACTIVATE GENERAL ALARM. A VALVE TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY ALARM INDICATION. 6. ANNUNCIATION OF THE ACTIVE DEVICE AT THE FIRE ALARM CONTROL PANEL AND ANY ANNUCiATORS, iN MONITORED BUILDING, SEND A SIGNAL TO THE U.L. MONITORING CENTER FOR ALARM, TROUBLE, WATERFLOW AND SUPERVISORY CONDITIONS. FIRE ALARM SPECIFICATIONS: ALL EQUIPMENT TO BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE COMPATIBLE WITH THE SYSTEM BEING USED. SYSTEM iS TO BE POWER LIMITED. SYSTEM TO BE CENTRAL STATION SERVICE AS PER NFPA -72. FIRE ALARM PANEL SHALL BE LISTED FOR CENTRAL STATION SERVICE PER NFPA 72, 2002, SECTION 8.3, UNLESS OTHERWISE SPECIFIED. THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM MANUFACTURER AND ARTICLE 760 OF THE NATIONAL ELECTRICAL CODE. MINIMUM WIRE SIZE IS 12 AWG FOR GROUND CONNECTION. (NOTE: PANEL NEUTRAL OR CONDUIT GROUND IS NOT ACCEPTABLE). ALL STROBE LIGHTS SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM AND SHALL BE SYNCHRONIZED IN OPEN AREAS. ALL AUDIBLE SIGNALS SHALL HAVE THREE PULSE TEMPORAL PATTERN AND SOUND LEVEL SHALL BE AT LEAST 15 DBA ABOVE AMBIENT SOUND LEVEL AND HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FT ABOVE THE FLOOR IN OCCUPIED AREAS. FIRE ALARM CIRCUITS AND DEVICES SHALL BE CLASS "137. ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. AND N.E.G. 760. CONNECTIONS TO LIGHTS AND POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT. THE CIRCUIT AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING AND BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND BE PER N.F.P.A. 72 2002 EDITION THE FIRE ALARM PANEL iS PROVIDED WITH STANDBY BATTERY PER N.F.P.A. 72 WITH 24 HOURS OF STANDBY AND 15 MINUTES OF ALARM (AS REQUIRED). SHOULD LOSS OF NORMAL 120VAC POWER OCCUR, FIRE ALARM PANEL WILL AUTOMATICALLY TRANSFER TO BATTERY. A CERTIFICATE OF COMPLETION WILL BE PREPARED AND A COPY PROVIDED TO THE OWNER AND THE CITY FIRE RESCUE DEPARTMENT. OWNER MANUALS, INSTALLATION INSTRUCTIONS, OPERATION INSTRUCTIONS AND RECORD DRAWINGS SHALL BE AT THE SITE ON COMPLETION OF JOB AND FINAL ACCEPTANCE. INSTALLATION NOTES: ALL FIRE STOP PENETRATIONS SHALL BE MADE WiTH APPROVED N.E.C. ELECTRICAL TUBING AND SHALL BE SEALED WITH U.L. APPROVE FIRE STOP MATERIAL. COLOR CODING MAY NOT APPLY TO EXISTING WIRE. (WIRE TO BE LABELED ACCORDINGLY.) CONDUIT SHALL BE A MiNIMUM OF 1/2" AND 40 %Q FILL MAXIMUM. TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE CONTROL COMMUNICATOR. ALL FLOW, TAMPER, PIV AND BACKFLOW WILL HAVE MONITOR MODULES; FIRE PROTECTION SPRINKLER PUMP MONITORING. (3 POINTS) (A).FiRE PUMP RUN (B).FIRE PUMP FAIL (C).FIRE PUMP PHASE REVERSAL. ROUTING OF THE FiRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC. VERIFY EXACT LOCATIONS OF DEVICES AND WIRE ROUTING PRIOR TO STARTING WORK. MOUNTING REQUIREMENTS: MANUAL PULL STATIONS TO BE INSTALLED AT 48" A.F.F. MOUNT FIRE ALARM SYSTEM STROBES, SPEAKER / STROBES AT 80" A.F.F. FROM BOTTOM OF DEVICE OR 6" BELOW CEILING. (WHICH EVER IS LOWER) SMOKE DETECTOR SHALL NOT BE LOCATED WITHIN 3' OF SUPPLY AiR OUTLETS. SMOKE DETECTORS TO BE INSTALLED AS PER N.F.P.A. 72. WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 47 MINIMUM FROM CEILING WiTH 12" MAXIMUM FROM CEILING. fQ SCOPE OF WORK 1. INSTALLATION OF NEW NOTIFICATION DEVICES FOR THE SCOPE OF WORK SHOWN ON THE ATTACHED PLANS. SCOPE OF WORK HAS A TOTAL AREA OF: 3,520 SQ. FT. THE FIRE ALARM SYSTEM IS AN ADDRESSABLE INTELLIGENT SYSTEM. THE SYSTEM HAS A SLC DEVICE CAPACITY OF 102 DETECTORS, AND 94 MODULES, X2 SLC LOOPS, FOR A TOTAL OF 380 POINTS. 2. THE MAXIMUM HEIGHT OF CEILING 9'Z'. 3. SEE BATTERY CALCULATIONS FOR MAXIMUM LENGTH PER INDICATING CIRCUIT. 4. BUILDING IS FULLY SPRINKLERED. �e.S S l F/F FiLL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS U�a LABORATORIES, INC.® FOR USE IN THROUGH - PENETRATION US RES STAANCE DIRECTORY 50L6,90G9 ENT UL FIRE SECTION A -A System No. C A.14044 June 15, 2005 F Ratings - 2, 3, and 4 Hr. (See items 2A and 4) T Rating - 0 Hr. L Rating at Ambient = 2 CFM /sq. ft. L Rating at 400 F - less than 1 CFM /sq. ft. W Rating - Class i (See item 4) 1. Floor or Wall Assembly Lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units *. When floor is C onstructed of hollow core precast concrete units, packing material (Item 3) and caulk till material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow -core precast concrete units is 7 in. (178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. i A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 for heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall asserbly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall. 2. Through Penetrants - One metalric pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. (762 mm) diam (Or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit. D. Conduit - Nom 4 in. (102 mm) diam for smaller) steel electrical metallic tubing. E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Packing Material - Polyethylene backer rod or nom I in. (25 mm) thickness of tightly- packed mineral wool bait or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4). 4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetTically on both sides of wall, flush with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table: Min. Floor or Wall Thkns In. (mm) Nom. Pipe Tube or Conduit Diam in. (mm) Max Annular Space in. (mm) Min. Caulk Thkns in. (mm) F Rating Hour 2-1/2(64) 1/2-12 (13 -305) 1-3/8(35) 1/2(13) 2 2-1/2(64) 1/2-12 (13- 305) 3-1/4(83) 1 (25) 2 4-1/2(114) 1/2-6 (13 -152) 1-3/8(35) 1/4 (6) (a) 2 4-1/2(114) 1/2-12 (13 -305) 1-1/4(32) 1/2(13) 2 4-1/2(114) 1/2-20113-508) 2 (51) 1 (25) 2 4-1/2(114) 1/2-20 (13 -508) 2 (51) ) (25) 2 4-1/2(114) 1/2-12 (13- 305) 3-1/4(83) 1 (25) 2 4-1/2(114) 22 -30 (558 -762) 2 (51) 1/2(51) 2 5-1/2(140) 1/2-6 (13 -152) 1-3/8(35) 1 (25) (b) 2 (a)Min 2 in. (51 mm) thickness of mineral woo( bait insulation required in annular space. (b)Min 1 in. (25 mm) thickness Of mineral wool bait insulation required in annular space on both sides of floor or wall assembly. Min l in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wail assembly. 3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant. (Note: W Rating applies only when FB -3000 WT sealant is used.) *Bearing the UL Classification Marking *NOTE This material was extracted by 3M fire protection products from 2004 edition of the UL fire resistance directory. F /RE ALARM LEGEND COUNT SYMBOL DEVICE TYPE MODEL MANUFACTURE WIRE TYPE AND DESCRIPTION A 2 #16 FPLR ISOTEC P #- IR142SFPLI -02 WiRE FOR DATA COMMUNICATION FIRE ALARM CONTROL PANEL 2 #14 FPLR ISOTEC P #- IR142SFPL1 -02 WIRE FOR STROBES C 2 #16 FPLR ISOTEC P #- iR142SFPLi -02 WiRE FOR SPEAKERS 2 IrAM WITH (2 -LCX) SLC EXPANDER EST -2 EST Required system & (AA -50) AMPLIFIERS 0.0700 x 24,0000 1 24 rP--/-Sl FIRE ALARM POWER SUPPLY BPSiOA EST AlermTons i CAB REMOTE CABINET RACCR EST totes) OATerd WITH SIGA -APS & SIGA -AA50 (►bra's) Sateiy (AMR Hours) Ham) (AM) Hours) 8 189 M SPEAKER / STROBE G4RF S7VM EST =. 68760 X 02500 3.3490 18690 1 1.2000 2 MER SPEAKER / STROBE G4RF S7VM EST 1.6800 + 1.7885 = 3.4685 SPEAKER / STROBE (75cd) 757 -4A4S EST. - 6 S WEATHERPROOF � SPEAKER / STROBE (110cd) 757 -8A46 EST 37 {cal WEATHERPROOF 1 @STROBE ONLY GC -VM EST CEILING MOUNT 9 307 ® STROBE ONLY GiRF -VM EST 32 ® PULL STATION SIGA -278 EST 8 MC CONTROL MODULE SIGA -CCiS EST 9 182 SMOKE DETECTOR SIGA -PS EST 2 HEAT DETECTOR SIGA -HRS EST 4 7:H DUCT DETECTOR SIGA -SD EST 4 RT REMOTE TEST STATION SIGA -TRM EST 3 ® CONTROL RELAY MODULE SiGA -CR EST 6 ® MONITOR MODULE SIGA -CT1 EST (N) = NEW DEVICE (E) = EXISTING DEVICE 27 810 TOTAL DEVICES (ER) = EXISTING RELOCATE y Salk . a FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, INC.Q FOR USE IN THROUGH - PENETRATION US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE RESISTANCE DIRECTORY 50L6,90G9 SECTION A -A System No. W- L-3001 September 07, 2004 F Ratings - i and 2 Hr. (See items 1) T Rating - 3/4, 1, 1-1/2 and 2 Hr. (See item 2) L Rating at ambient = 15 CFM /sq. ft. (See item 3) L Rating at 400 F - less than I CFM /sq. ft. (See item 3) 1. Wall Assembly = The i or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner described in the individual 0300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide by 1 -3/8 in. deep channels spaced max 24 in OC. B. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be as specified in the individual Wall or Partition Design. Diam of circular through opening to be 3/8 in. to 5/8 in. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached to studs with cement coated nails as specified in the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - dolling, self - tapping bugle-head steel screws as specified in the individual Wall or Partition Design. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Cables - Individual cable or max 1 in. diam cable bundle installed in through opening with an annular space of min 0 in. (point contact) to max 3/4 in. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride PVC insulation and jacket materials. When max 25 pair telephone cable is used, T Rating is 2 hr.When 50 to 150 pair telephone cable is used in I hr fire rated wall, T Rating is 314 hr.When 50 to 150 pair telephone cable is used in 2 hr fire rated wall, T Rating is I hr. B. Max No. 10 AWG multiple copper conductor Type NM ('Romex') nonmetallic sheathed cable with PVC insulation and jacket materials. When Type NM cable is used, max T Rating is 1 -1 /2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of 5/8 in. When fiber optic cable is used, max T Rating is 2 hr. D. Max 12 AWG multi conductor (max seven conductors) power /control cable With cross - linked polyethylene (XLPE) insulation and XLPE or PVC jacket materials. When multi conductor power /control cable is used, max T Rating is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl chloride insulation and jacket materials. 3. Fill,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material installed to completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 in. diam bead of caulk or putty applied to perimeter of cable(s) at its egress from each side of the wall. 3M COMPANY - MP+ Stix putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is used.) *Beating the UL Classification Mark E ._M7TH)FLOOR - FIRE ALARM PLAN �• N S j t`.l ,i SCALE: 1/8" =1'-0' 4i w WIRE LEGEND SYMBOL WIRE TYPE AND DESCRIPTION A 2 #16 FPLR ISOTEC P #- IR142SFPLI -02 WiRE FOR DATA COMMUNICATION B 2 #14 FPLR ISOTEC P #- IR142SFPL1 -02 WIRE FOR STROBES C 2 #16 FPLR ISOTEC P #- iR142SFPLi -02 WiRE FOR SPEAKERS Project name: HEALTHSOUTH - 7TH FLOOR - BREAST HEALTH CENTER BPS 10 19 EIPS10-PomweerSu ly Loading and Voftage Drop CalcuWons Total SysbmSar,dby Cue (AMPS) BPS # 19 = 0.0700 amps 01 o. 0 OD Total System Standby Qerent Raqaed Shendby T«ne = Required Standby (AMPS) W (haaa) Regmred Capecky (AM PLH rs) Required Alarm X Required system optiorlai 0.0700 x 24,0000 = 1.6800 Current = Alarm x AlermTons x Capacly (AMPS) _ (AMPS) totes) OATerd (AMP- (►bra's) Sateiy (AMR Hours) Ham) (AM) Hours) Hans) ) 6.4860 + 0 -1900 =. 68760 X 02500 3.3490 18690 1 1.2000 = 4.0186 7.00 1.6800 + 1.7885 = 3.4685 1 X 1 1.2000 - 4.1622 7.00 . _. Total SysbmSar,dby Cue (AMPS) BPS # 19 = 0.0700 amps 01 o. 0 OD Total System Standby Qerent Raqaed Shendby T«ne = Required Standby (AMPS) W (haaa) Regmred Capecky (AM PLH rs) Required Alarm X Required system optiorlai 0.0700 x 24,0000 = 1.6800 SyslemAlarm Qarent(AMPS) M#19- 0.1900artps 01 o. 0 OD Ciwis Panel W Total (ALPS} W (hors) Regmred Alarm Required Alarm Alarm Required system optiorlai Re%irod Required Battery Alarm Current -1- Current = Alarm x AlermTons x Capacly (AMPS) _ (AMPS) totes) OATerd (AMP- (►bra's) Sateiy (AMR Hours) Ham) (AM) Hours) Hans) ) 6.4860 + 0 -1900 =. 68760 X 02500 3.3490 18690 MONITOR SYSTEM BATTERY «« CALCULATIONS AT 24 HOURS BACK - UP WITH 15 MINUTE ALARM 1 1 - Povuer Supply Loading andyolt�p CalcuWons Ckmd AtarmCu eri(AMPS) WS#20 =6.%4 ToW SystemmS Wby Ctsrem(ALPS) BPS# 20- 0.0700 arrps 01 o. 0 OD Toff SysbmSangby cun-em TOW W Ragraed Standby (ALPS} W (hors) Required Slam Cap Y Qpwky (ALP-Fbcn) Required Alarm X Required Required optiorlai 0.0700 Required Battery Battery Supplied ((AMP-Hours) + Capacity (AMP- = Capacity x Factorof x Capacity (AMP- _ City (AMP- totes) (AMP- Hans) Sateiy (AMP - Hours) Ham) Holes) Hours) Hans) Hans) 1 2.6800 + 1.6690 = 3.3490 1 x 1 1.2000 = 4.0186 7.00 MONITOR SYSTEM BATTERY «« CALCULATIONS AT 24 HOURS BACK - UP WITH 15 MINUTE ALARM 1 1 - Povuer Supply Loading andyolt�p CalcuWons Ckmd AtarmCu eri(AMPS) WS#20 =6.%4 ToW SystemmS Wby Ctsrem(ALPS) BPS# 20- 0.0700 arrps 01 o. 0 OD Toff SysbmSangby cun-em Sergi Tire W Ragraed Standby (ALPS} W (hors) = Qpwky (ALP-Fbcn) X Required 0.0700 x 1 24.0000 = 1.6800 P + CW-ty (AMP- - �BY x Factor of _ City (AMP- died Hans) (AMP - Safety Holes) Hours) Hans) 1.6800 + 1.7885 = 3.4685 1 X 1 1.2000 - 4.1622 7.00 Ckmd AtarmCu eri(AMPS) WS#20 =6.%4 ToW SystemmS Wby Ctsrem(ALPS) BPS# 20- 0.0700 arrps 01 o. 0 OD Toff SysbmSangby cun-em Sergi Tire W Ragraed Standby (ALPS} W (hors) = Qpwky (ALP-Fbcn) X Required 0.0700 x 1 24.0000 = 1.6800 MONITOR SYSTEM. BATTERY «« CALCULATIONS AT 24 HOURS BACK- UP WITH 15 MINUTE ALARM MFRr 6` AREA, M r Il•1l, VI YYV1 %IN E 7TH FLOOR - SITE PLAN N s SCALE: N.T.S. ♦ rr BOX MOUNTING • . SQUARE . BOX SUPPORT1 • • '11 N'SQUARE CEILING a»� yiiiiiiiiiiiiiitt��>• iiiiiiiiiiiiiii 4" SQUARE BOX TO 3-0 ADAPTER RING - (OR NO RING IF 4-0 BOX IS USED) 11 j PLUG - IN DETECTOR BASE NOTE: MIN PiPE FLEX 1/2' --- FREE WIRE IN CEILING DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. DETECTOR BASE NOTE:3 CABLE NOTE: 3 FROM INTFC BOARD -) TO NEXT DEVICE AT FACPC + ](WHERE APPLICABLE) NOTE:1 °. �. 0 LOOP ADI WIRING FOR ADB-FL BASE (STYLE 4) NOTE 1: DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE NOTE 2: DO NOT LOOP WIRE UNDER TERMINALS 1 & 2. BREAK WIRE RUN TO PROVIDE SUPERVISION NOTE 3: OBSERVE POLARITY. DO NOT GROUND CONTROL WIRES OR SHIELDS. TiE SHIELDS TOGETHER AT EACH DETECTOR. NOTE 4: SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE NOTE 5: RECORD THE LOOP ADDRESS Sr DEVICE TYPE IN THE SPACES PROVIDED ON 8(7' A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER) WiTH DEEP 1900 BOX STROBE OR SPEAKER /STROBE PULL STATION �O 48" A.F.F. a NOT TO SCALE BOX MOUNTING REQUIRMENTS 1900 BOX PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING OOK= t t t t CEILING 1 t PLUG - IN 1 t DETECTOR BASE DETECTOR HEAD BIG MOUNTING IN SHEET ROCK OR PLASTER TYPE CEILINGS (MUST BE INSTALLED WiTH CONDUIT) THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. NOT TO SCALE f .1 1 • 2 2 d 01 o. 0 OD « Tats W 1- 301 OWt'9 W a�aW wo 0O6��N Required Stal&y Refired Atom Required optional I Required Battery e� P + CW-ty (AMP- - �BY x Factor of _ City (AMP- died Hans) (AMP - Safety Holes) Hours) Hans) MONITOR SYSTEM. BATTERY «« CALCULATIONS AT 24 HOURS BACK- UP WITH 15 MINUTE ALARM MFRr 6` AREA, M r Il•1l, VI YYV1 %IN E 7TH FLOOR - SITE PLAN N s SCALE: N.T.S. ♦ rr BOX MOUNTING • . SQUARE . BOX SUPPORT1 • • '11 N'SQUARE CEILING a»� yiiiiiiiiiiiiiitt��>• iiiiiiiiiiiiiii 4" SQUARE BOX TO 3-0 ADAPTER RING - (OR NO RING IF 4-0 BOX IS USED) 11 j PLUG - IN DETECTOR BASE NOTE: MIN PiPE FLEX 1/2' --- FREE WIRE IN CEILING DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. DETECTOR BASE NOTE:3 CABLE NOTE: 3 FROM INTFC BOARD -) TO NEXT DEVICE AT FACPC + ](WHERE APPLICABLE) NOTE:1 °. �. 0 LOOP ADI WIRING FOR ADB-FL BASE (STYLE 4) NOTE 1: DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE NOTE 2: DO NOT LOOP WIRE UNDER TERMINALS 1 & 2. BREAK WIRE RUN TO PROVIDE SUPERVISION NOTE 3: OBSERVE POLARITY. DO NOT GROUND CONTROL WIRES OR SHIELDS. TiE SHIELDS TOGETHER AT EACH DETECTOR. NOTE 4: SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE NOTE 5: RECORD THE LOOP ADDRESS Sr DEVICE TYPE IN THE SPACES PROVIDED ON 8(7' A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER) WiTH DEEP 1900 BOX STROBE OR SPEAKER /STROBE PULL STATION �O 48" A.F.F. a NOT TO SCALE BOX MOUNTING REQUIRMENTS 1900 BOX PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING OOK= t t t t CEILING 1 t PLUG - IN 1 t DETECTOR BASE DETECTOR HEAD BIG MOUNTING IN SHEET ROCK OR PLASTER TYPE CEILINGS (MUST BE INSTALLED WiTH CONDUIT) THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. NOT TO SCALE f .1 1 • 2 2 d 01 o. 0 OD Tats W 1- 301 OWt'9 W a�aW wo 0O6��N Required Stal&y Refired Atom Required optional : lm Required Battery e� P + CW-ty (AMP- - �BY x Factor of _ City (AMP- died Hans) (AMP - Safety Holes) Hours) Hans) 1.6800 + 1.7885 = 3.4685 1 X 1 1.2000 - 4.1622 7.00 MONITOR SYSTEM. BATTERY «« CALCULATIONS AT 24 HOURS BACK- UP WITH 15 MINUTE ALARM MFRr 6` AREA, M r Il•1l, VI YYV1 %IN E 7TH FLOOR - SITE PLAN N s SCALE: N.T.S. ♦ rr BOX MOUNTING • . SQUARE . BOX SUPPORT1 • • '11 N'SQUARE CEILING a»� yiiiiiiiiiiiiiitt��>• iiiiiiiiiiiiiii 4" SQUARE BOX TO 3-0 ADAPTER RING - (OR NO RING IF 4-0 BOX IS USED) 11 j PLUG - IN DETECTOR BASE NOTE: MIN PiPE FLEX 1/2' --- FREE WIRE IN CEILING DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. DETECTOR BASE NOTE:3 CABLE NOTE: 3 FROM INTFC BOARD -) TO NEXT DEVICE AT FACPC + ](WHERE APPLICABLE) NOTE:1 °. �. 0 LOOP ADI WIRING FOR ADB-FL BASE (STYLE 4) NOTE 1: DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE NOTE 2: DO NOT LOOP WIRE UNDER TERMINALS 1 & 2. BREAK WIRE RUN TO PROVIDE SUPERVISION NOTE 3: OBSERVE POLARITY. DO NOT GROUND CONTROL WIRES OR SHIELDS. TiE SHIELDS TOGETHER AT EACH DETECTOR. NOTE 4: SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE NOTE 5: RECORD THE LOOP ADDRESS Sr DEVICE TYPE IN THE SPACES PROVIDED ON 8(7' A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER) WiTH DEEP 1900 BOX STROBE OR SPEAKER /STROBE PULL STATION �O 48" A.F.F. a NOT TO SCALE BOX MOUNTING REQUIRMENTS 1900 BOX PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING OOK= t t t t CEILING 1 t PLUG - IN 1 t DETECTOR BASE DETECTOR HEAD BIG MOUNTING IN SHEET ROCK OR PLASTER TYPE CEILINGS (MUST BE INSTALLED WiTH CONDUIT) THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. NOT TO SCALE f .1 1 • 2 2 d 01 o. 0 OD W W 1- 301 OWt'9 W a�aW wo 0O6��N t"1MMA OF 5 3 Iti t9 iMr : lm e� �Q M Q Q 0 ftomi C4 vii g °oQ oog REVISIONS:�� f p • � t a y; Y 4 La «p• . tr w 4 • C\L 00 ., 'Vil- 00 U F�. CL 0 W M tom- �Q°YUj4: �gW�0Ur LLU )Z,. �UZZLLCi }q- WZ(Dl -Z ~�'WQQ rc cc Z'7Zf_ UJZ3IW- Q;icw_J4 :t Q� ��O)'¢ -s u. 2 U rn W 3w.x a t- w W ca U PROJECT NUMBER: 000000 DATE: SCALE: 09/05/12 1/8 DRAWN BY: CHECKED BY- T.F. D.N. 1 OF 3