10-650-022.r sueA I. V) • i w M r rr : r s rr rr rr • • r� r • PRINT System No. C -AJ -2419 F Rating - 3 Hr T Rating - 0 Hr 1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete floor or min 5 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening shall be 6 in. See Concrete Blocks (CAZi) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants -- One nonmetallic penetrant centered within the firestop system. The annular space between pipe and periphery of opening shall be nom 3/4 in. Pipe to be rigidly supported on both sides of the floor assembly. The following types and sizes of non - metallic pipe may be used: A Polyvinyl Chloride (PVC) Pipe -- Nom 4 in dam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (proms or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 4 in. diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe -- Nom 4 in, diam (or smaller) Schedule 40 solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3. Firestop System -- The details of the firestop system shall be as follows: A Fill, Void or Cavity Material* - Wrap Strip -- Nom 3/16 in. thick by 1 -3/4 in. wide intumescent wrap strip. The wrap strip is continuously wrapped around the outer circumference of the pipe covering two times and slid into the annular space. When multiple wrap strips are used to achieve the required total length, the ends are to be butted end to end and held in place with tape. The bottom edge of the wrap strip shall be recessed 1/2 in. from the bottom surface of the concrete floor. In walls, the ,wrap shall be installed on both surfaces of the wall such that the exposed edge of the wrap strip is recessed 1/2 in. from each side of the wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 648 -E- W45/1 -3/4- Wrap Strip B. Fill, Void or Cavity Materials* - Sealant -- Mein 1/2 in. thickness of fill material applied within the annulus, flush with bottom surface of floor or both surfaces of wall. HILT) CONSTRUCTION CHEMICALS, DIV OF HILTi INC - FS ONE Sealant *Bearing the UL Classification Mark ® ®e Reproduced by HILTI, Ilex. Courtesy of ��,SS fF� Underwriters Laboratories, Inc FiRESTOP SYSTEMS April 27, 2005 C US System No. C -AJ -2271 N F Rating - 2 Hr T Rating -1 Hr A W Rating -Class 1(See Item 3) O 2 1 O 4 3 �A SECTION A -A 1. Floor or Wall Assembly - Min 2 -1/2 in. (64 mm) thick reinforced lightweight or nomal weight (100 -150 pd or 1600 -2400 kg1m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks`. Max diam of opening is 7 in. (178 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory fa names of manufacturers. 2. Through Penetrants - One nonmetallic pipe or conduit to be installed concentrically or eccentrically within the firestop system. Annular space between pipe or conduit and edge of opening to be min 0 in. (0 mm, point contact) and max 112 in. (13 mm). Pipe or conduit to be rigidly supported on both sides of floor-ceiling assembly. The following types and sizes of nonmetalfic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nan 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nan 6 in. (152 mm) diam (or smaller) SDR13.5 CPVC pipe for use in dosed (process or supply) piping systems. C. Aaylonitrile Butadiene Styrene (ABS) Pipe - Nam 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core ABS pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping systems. D. Flame Retardant Polypropylene (FRPP) Pipe - Nan 6 in. (152 mm) diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping systems. 3. Fill, Vold or Cavity Materials' - Sealant - Required for systems with W Rating, but otherwise optional. Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top or bottom surface of floor. W Rating applies only when CP601 S or CP 604 Sealant is used. HILTI CONSTRUCTION CHEMICALS, DiV OF HILTI INC - FS-ONE Sealant, CP 601S Sealant or CP 604 Sealant 3A, Packing Material (not shown) - Min 112 in. (13 mm) thick iess of 4 pd (64 kg/m3) mineral wool batt insulation firmly packed into annular space and recessed from the top surface of floor to accommodate the required thickness of fill material. Required only when CP 604 Sealant is used. 4. Firestop Device'--Firestop Collar - Firestop collar shall be installed in accordance with the accompanying installation instructions. Collar to be installed and latched around the pipe and secured to underside of floor or both sides of wall using anchor hooks provided with the collar. Minimum two anchor hooks required for nom 1.1/2 and 2 in. (38 and 51 mm) diam pipes. Minimum three anchor hooks required for worn 3 and 4 in. (76 and 102 mm) diam pipes. Minimum four anchor hooks required for 6 in. (152 mm) dram pipes. The anchor hooks are to be secured with min 114 in. (6 mm) diam by min 1 -1/4 in. (32 mm) lag steel expansion bons or min 0.145 in. (3.7 mm) diam by 1 -1/4 in. (32 mm) kxg powder actuated fasteners utilizing a 1 -7116 in. (37 mm) diam by 1116 in. (1.6 mm) thick steel washer. As altemates to the anchors specified above, Hilti 1/4 in. (6 mm) diam by 1 -1/4 in, (32 mm) lag KWIK -CON II+ concrete screw anchor, Hilti 114 In. (6 mm) diam by 1-3/4 in. (45 mm) log KWIK -BOLT 3 steel expansion anchor or Hilti X-DNI 27 P8 S15 powder actuated floor pin with integral nom 9116 in. (15 mm) diam washer may be used. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTi INC - CP 643 5011.5 -N, CP 643 63r^, CP 643 93/3 -N, CP 643 90/4 -N and CP643 16016"N, Firestop Collar 'Bearing the UL Classification Mark !J IOU Reproduced by HILTI, Ira Courtesy of V Underwriters Laboratories, Ira, V Hilts Firestop Systems November 18,2006 System No. W -L -2284 X F Rating -1 Hr T Rating -1 Hr 3 1 F` A 3 �A 3 2 SECTION A -A 1. Wall Assembly -- The 1 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A Studs -- Wall framing shall consist of wood studs or steel channel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Stec studs to be min 3-1/2 in. wide and spaced max 24 in. OC. B. Gypsum Board* -- Min 5/8 in. thick, 4 ft wide with ware or tapered edges. The gypsum wallboard type, thidTom number of laym and orientation shall be as specified in the individual U300 or 0400 Wall and Partition Design. Max dam of opening is 4 in. Z Through Penetrants -- One nonmetallic pipe to be centered within the firestop system. M annular space of 3/16 to 1/4 in. is required within the firestop system. Ripe to be rigidly supported on both sides of wall ossermbly« The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe -- Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Non 3 in. diam (or smaller) SDR 13.5 CPVC pipe for use in dosed (process or supply) Piping systems. 3. Fill, Void or Cavity Material* -- Wrap Strip - Layers of intumescent wrap strip are continuously wrapped around the pipe with ends held in place with tape. Wrap strip installed such that ends protrude ram. 1/8 in. beyond both surfaces of wall. Size of wrap strip and number of layers are shorn in table below. HILTi CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP648 -E W25/1' or CP648 -E W45/1 -3/4' Firestop Wrap Strip A. Fill, Void or Cavity Material* - Wrap Strip -- (As an aftemate to the wrap strip in item 3) - One layer of intumescent wrap strip is tightly wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip installed such that ends protrude ram. 1/8 in. beyond bath surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DN OF HILTI INC -- CP648- S -1,5' US, CP648 -S -2' US, CP648 -S -3' US *Bearing the UL Classification Mark ® 1 er Reproduced U erwrrtters Laboratories, Inc, of FIRESTOP SYSTEMS April 22,2M C US System No. W -L -1290 F Rating -1 and 2 Hr (See gem 1) T Rating - 0 Hr L Rating at Ambient - Less than 1 CFMISq Ft L Rati System No. F -A -2089 cc cm CNI F Rating - 3 Hr T Rating - 0 Hr W Rating - Class 1(See Item 3B) 2 1 3B A. A A 3A SECTION A -A 1. Floor Assembly- Min 2 -112 In. thick reinforced lightweight or normal weight (100 -150 pd) concrete. Max diameter of opening is 5 in. 1 A, Floor AssemblygOptional - Not Shown) - The fire rated unprotected concrete and steel floor assembly shall be ca�tructed of the materials and in the manner specified in the individual D900 Series designs in the Fire Resistance Directory and as summarizes below: A. Concrete - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pd) concrete. B. Steel Floor and Form Units' - Composite or not- cortkposite max 3 in. deep gale steel fluted units as specified in the individual Floor- Ceiling Design. n. 9 2. Through Penetrants - One nonmetallic pipe to be installed concentrically or eccettrically within ftte firestop system. Annular space within the firestop system is dependent upon the diam and type of penetrant used as tabulated in Item 3A Pipe to be rigidly supported ale both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nan 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (pmcess or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nan 3 in. diam (or smaller) SDR13.5 CPVC for use to dosed (process a supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nan 3 in, diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or supply) or vetted (drain, waste or vent) piping systems. D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 3 in. diam (or smaller) Schedule 40 FRPP Pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping system. 3. Firestop System - The firestop system shag consist of the following: A Fill, Vold or Cavity Material' -Wrap Strip - Nan 3116 in. thick by 1 -3/4 in. wide intumescent wrap strip. The layers of wrap strip are continuously wrapped tightly around pipe with ends held in place with tape. Wrap strip installed recessed %in. from bottom surface of concrete cover. The max diam of opening, max diam and type of penetrant, annular space within the firestop system and layers of wrap strip required are tabulated below: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTi INC - CP648 -E W45fl -N4" Wrap Strip B. Fill, Void or Cavity Materials'- Sealant - Min 1/4 in. thickness of fill material applied within the annulus directly on top of wrap strip, flush with top surface of floor. W Rating applies only when CP 601S Sealant is used. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTi INC - FS-ONE Sealant or CP 601S Sealant 'Bearing the UL Classification Mark I . I I !J 1� 1 C Reproduced by HILTI, Inc. Courtesy ofS Underwriters Laboratories, Inc. V Hilts Firestop Systems October 06,2W5 System No. C -AJ -1226 co F RATING = 3-HR. T RATING = MR. � L Rating At Ambient- Less than 1 MVSq R L Rating At W F - 4 CFMISq Ft 3 A 2 4B � 48 e.�r� I:� •:� 3 A 4A SECTION A -A 1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete Wan may also be constructed of any UL Classified Concrete Blocks*. Max dam of opening is 32 in. 2. Metallic Sleeve -- (Optional) Flom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cost or grouted into floor or wan assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wan. 3. Through - Penetrant -- One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in. (point contact) to mac 1 -7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be used: A. Steel Ripe -- Flom 30 in. dam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Ripe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Copper Ripe - Nom 6 in, diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing -- Flom 6 in. dam (or smaller) Type L (or heavier) copper tubing. E, Conduit -- Nom 6 in. diem (or smaller) steel conduit F. Conduit -- Nom 4 in. dam (or smaller) steel electrical metallic tubing (EMT). 4. Finestop System -- The firestop system shall consist of the following: A Packing Material -- Min 4 in. thickness of min 4 pcf mineral wool butt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Mataiot* -- Sealant -- Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and Crete or sleeve, a min 1/4 in. dam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, - . gassti HILTI INC • -- FS-One Sealant ftprodicaf b m� Underwrlam FlRESroP sYWM b t �, �c C us _ . F�oga 1 of t CM System No. C- AJ- 2342 cm Cn F Rating - 3 Hr _ w r Q T Rating - 0 Hr W Rating - Class 1(See Item 3B) f 2 3B 1 A A 3A . y .�.., .. SECTIOMA -A 1. Floor a Wall Assembly- Min 2-1/2 in. (64 mm) thick reinforced lightweight a normal weight (100 -150 pd or 1600 -2400 kg/m3) concrete floor or wall. Wall may also be constructed of any UL Classified Concrete Blocks'. Max diam of opening is 6 in. See Concrete Blacks (CAZi') category in ft Fire Resistance Directory for names of manufacturers. 2. Through Penehrts - One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the firestop system is dependent upon the max diam and type of penetrant used as tabulated in Item 3A. Pipe to be rigidly supported err both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes may be used: A Polyvinyl Chloride (PVC) Pipe - Nan 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for lose in dosed (process or supply) or vented (drain, waste a vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nark 4 in. (102 mm) diam (or smaller) SDR73.5 CPVC for lose in dosed (process or supply) piping systems. C. Aaylonibile Butadiene Styrene (ABS) Pipe - Nan 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in dosed (process or supply) or vented (drain, waste or vent) piping systems. D. Flame Retardant Polypropyle a (FRPP) Pipe - Nom 4 in. (102 mm) dram (or smaller) Schedule 40 FRPP pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping system. 3. Firestop System - The firestop system shall consist of the following: A Fill, Void or Cavity Material` - Wrap Strip - Layers of intumescent wrap strip are continuously mapped around the pipe with ends held in place with tape. Wrap strip installed recessed max 1/4 in. (6 mm) from bottom surface of floor or from both surfaces of wall. Size of map ship and number of layers for a given size penetrant are shown in table below: HILTi CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP648 -E W2511" or CP648 -E W4511 -314' Firestop Wrap Strip S ipP' rig Reproduced by HILTI, Inc. Courtesy of �� Underwriters Laboratories, Iwo Hilts Firestop Systems August 29, 2007 Page:1 aft FA�ir� t C System No. C -AJ -2342 F Rating - 3 Hr T Rating - 0 Hr W Rating -Class 1(See Item 3B) ng at 400° F -Less than 1 CFMISq Ft C m US Product Designation Pipe Size in. Max Opening Annular Space Annular Space Number of Nan Wrap Strip (mm) Diam (in.) Min in.(mm) Max in. (mm) Layers width in, (mm) CP648 -E W25J1" 1 1!2 (3$) 3 (T6) 3116 (4.8) 15116 (24) 1 1(25) CP648 -E W45t1 -3(4" 11/2(38) 3 (76) 3/16(4.8) 15J16 (24) 1 13/4(45) CP648 -E W2511' 2 (51) 3112 (89) 3116 (4.8) 15116 (24) 1 1 (25) CP648 -E W4511 -3/4" 2 (51) 3112 (89) 3116 (4.8) 15/16(24) 1 1314 (45) CP648 -E W45/1.3/4" 3(76)_ 4 (102) 3/16(4.8) 15 /t6 (24) 1 13/4 (45) CP648 -E W4511 -314' 3(76) 5 (127) 318 (10) 1 1/16(27) 2 1314 (45) CP648 -E W4511 -314' 4 (102) 6 (152) 3!8 (10} 1 1!8 (29) 2 1314 (45) 3 sECT%N A -A ' 1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specified in the individual 0300 or 0400 Series Wan and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features. A. Studs The 1 or 2 hr fire rioted gypsum board /stud wall amerr►bly shop be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall induce the following corhstmuction features. B. Gypsum Board*- -- Nom 5/8 in. thndc, 4 ft wide with square or tapered edges. The gypsum board type. thickness. numbs of loges, fastener type and sheet orientation shall be as specified in the individual 0300 or U400 Series Design in the Fire Resistance Directory. Max dam of opening is 5 in. The hoary F and T Ratings of the Firestop system are equal to the hoary fire rating of the wall assembly in which it is installed. 2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the Firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or cube to be rigidly supported on both sides of wolf assembly. The annular space between the pipe or tube and periphery of the opening stall be min 0 in (point contact) to max 1/2 in. The following types and yes of metallic pipes, conduit or tube may be used: A Steel Pipe -- Nom 4 in. dam (or smaller) Schedule 40 (or heavier) steel pipe. B. Iron Ripe -- Nan 4 in. dam (or smaller) cast or ductile iron pipe. C. Conduit -- Nan 4 in. dram (or smaller) steel electrical metallic tubing (E11T) or steel conduit D. Capper Tube -- Nan 4 in. dam (or smeller) Type L (err heavier) copper tube. E. Copper Ripe -- Nom 4 Tn. dam (or smaller) Regular (or heavier) copper pipe. 3. FiII, Void or Catty Material*- Sealant -- Mein 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contest location between pipe and wall, a min % in dam bead of fill material shall be applied at the'Pipe /wall interioce, HILTI CONSTRUCTION CHE1u1CW.S, DN OF HILTI INC -- CP606 Flexible Firestop Sealant *Barring the UL Classification Mark • ®� ®er Reproduced by HILTI, Inc. Courtesy of V Q Underwriters Laboratories, Inc. x FiRESTOP SYSTEMS June 03,2M5 W 0: W ° Date 8 Delta Description Drawn By. Checked By E-• Z _. V W e• V .:•a W h Q Client Information i HEALTHCARE REALTY N ONE 7000 Place SUiTE PHN . MiAMI, FL 33133 OFFICE: (305) 446.3666 � Project Number 09126 CAD File Name ONE 7000 Spa , _ // / / ///mom AM/// / //!//���j� 151 SEVILLA AVENUE, SUITE 26O m. CORAL GABLES, GABLES, FL 33134 OFFICE: (305) 442 -1188 _ it FAX: (305) 445 -1509 MiV11W. ADCINTERNATIONAL.NET , I t STATE OF� FLORIDA t AR- 0010536 ., , • RAYWIUNDO FEITO, RA. AA- 0001315 Architect • Sea1/Signature Construction Documents for; 10%.01%1diS�o�a�i NEW Jju at; ONE 7000 PLACE 3rd FLOOR 7000 SW 62nd AVENUE SOUTH MIAMI, FL 33143 • Issue Date &Issue Description d Drawn By Checked By 01 12_L09_L09 JP AR REVIEW Z_ Z CL . . a- t3 ' - W Al. Fill, Void or Cavity Material` -Wrap Strip - (As an aftemate to the wrap strip in Item 3A) One layer of intumhescent wrap strip is catti nuauusly _ ,wrapped around the pipe with ends butted and held in place with integrated tape. Wrap slip installed recessed matt 114 in. (6 mm) from top surface a of floor or from both surfaces of wag. Size of wrap strip for a given size penetrant are shown in the table below. HILTI CONSTRUCTION CHEMICALS, DIY OF HILTI INC - CP648- S-1.5" US, CP648�S -Z' US, CP64&S -3° US a CP64$ -S•4' US Wrap Stri p Product Designation Pipe N Number of N Nom. Wrap Strip ProductDesigration P Diameter (in.) L Layers W Width (in.) CP648- E- W2511' 1 1 -1/2 and 2 1 1 1 1 CP648- E -W45N -314' 1 1 -112, 2 and 3 1 1 1 1-3/4 System No. F -A -2089 cc cm CNI F Rating - 3 Hr T Rating - 0 Hr W Rating - Class 1(See Item 3B) 2 1 3B A. A A 3A SECTION A -A 1. Floor Assembly- Min 2 -112 In. thick reinforced lightweight or normal weight (100 -150 pd) concrete. Max diameter of opening is 5 in. 1 A, Floor AssemblygOptional - Not Shown) - The fire rated unprotected concrete and steel floor assembly shall be ca�tructed of the materials and in the manner specified in the individual D900 Series designs in the Fire Resistance Directory and as summarizes below: A. Concrete - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pd) concrete. B. Steel Floor and Form Units' - Composite or not- cortkposite max 3 in. deep gale steel fluted units as specified in the individual Floor- Ceiling Design. n. 9 2. Through Penetrants - One nonmetallic pipe to be installed concentrically or eccettrically within ftte firestop system. Annular space within the firestop system is dependent upon the diam and type of penetrant used as tabulated in Item 3A Pipe to be rigidly supported ale both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nan 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (pmcess or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nan 3 in. diam (or smaller) SDR13.5 CPVC for use to dosed (process a supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nan 3 in, diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or supply) or vetted (drain, waste or vent) piping systems. D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 3 in. diam (or smaller) Schedule 40 FRPP Pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping system. 3. Firestop System - The firestop system shag consist of the following: A Fill, Vold or Cavity Material' -Wrap Strip - Nan 3116 in. thick by 1 -3/4 in. wide intumescent wrap strip. The layers of wrap strip are continuously wrapped tightly around pipe with ends held in place with tape. Wrap strip installed recessed %in. from bottom surface of concrete cover. The max diam of opening, max diam and type of penetrant, annular space within the firestop system and layers of wrap strip required are tabulated below: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTi INC - CP648 -E W45fl -N4" Wrap Strip B. Fill, Void or Cavity Materials'- Sealant - Min 1/4 in. thickness of fill material applied within the annulus directly on top of wrap strip, flush with top surface of floor. W Rating applies only when CP 601S Sealant is used. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTi INC - FS-ONE Sealant or CP 601S Sealant 'Bearing the UL Classification Mark I . I I !J 1� 1 C Reproduced by HILTI, Inc. Courtesy ofS Underwriters Laboratories, Inc. V Hilts Firestop Systems October 06,2W5 System No. C -AJ -1226 co F RATING = 3-HR. T RATING = MR. � L Rating At Ambient- Less than 1 MVSq R L Rating At W F - 4 CFMISq Ft 3 A 2 4B � 48 e.�r� I:� •:� 3 A 4A SECTION A -A 1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete Wan may also be constructed of any UL Classified Concrete Blocks*. Max dam of opening is 32 in. 2. Metallic Sleeve -- (Optional) Flom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cost or grouted into floor or wan assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wan. 3. Through - Penetrant -- One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in. (point contact) to mac 1 -7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be used: A. Steel Ripe -- Flom 30 in. dam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Ripe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Copper Ripe - Nom 6 in, diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing -- Flom 6 in. dam (or smaller) Type L (or heavier) copper tubing. E, Conduit -- Nom 6 in. diem (or smaller) steel conduit F. Conduit -- Nom 4 in. dam (or smaller) steel electrical metallic tubing (EMT). 4. Finestop System -- The firestop system shall consist of the following: A Packing Material -- Min 4 in. thickness of min 4 pcf mineral wool butt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Mataiot* -- Sealant -- Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and Crete or sleeve, a min 1/4 in. dam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, - . gassti HILTI INC • -- FS-One Sealant ftprodicaf b m� Underwrlam FlRESroP sYWM b t �, �c C us _ . F�oga 1 of t CM System No. C- AJ- 2342 cm Cn F Rating - 3 Hr _ w r Q T Rating - 0 Hr W Rating - Class 1(See Item 3B) f 2 3B 1 A A 3A . y .�.., .. SECTIOMA -A 1. Floor a Wall Assembly- Min 2-1/2 in. (64 mm) thick reinforced lightweight a normal weight (100 -150 pd or 1600 -2400 kg/m3) concrete floor or wall. Wall may also be constructed of any UL Classified Concrete Blocks'. Max diam of opening is 6 in. See Concrete Blacks (CAZi') category in ft Fire Resistance Directory for names of manufacturers. 2. Through Penehrts - One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the firestop system is dependent upon the max diam and type of penetrant used as tabulated in Item 3A. Pipe to be rigidly supported err both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes may be used: A Polyvinyl Chloride (PVC) Pipe - Nan 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for lose in dosed (process or supply) or vented (drain, waste a vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nark 4 in. (102 mm) diam (or smaller) SDR73.5 CPVC for lose in dosed (process or supply) piping systems. C. Aaylonibile Butadiene Styrene (ABS) Pipe - Nan 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in dosed (process or supply) or vented (drain, waste or vent) piping systems. D. Flame Retardant Polypropyle a (FRPP) Pipe - Nom 4 in. (102 mm) dram (or smaller) Schedule 40 FRPP pipe for use in dosed (process or supply) or vented (drain, waste or vent) piping system. 3. Firestop System - The firestop system shall consist of the following: A Fill, Void or Cavity Material` - Wrap Strip - Layers of intumescent wrap strip are continuously mapped around the pipe with ends held in place with tape. Wrap strip installed recessed max 1/4 in. (6 mm) from bottom surface of floor or from both surfaces of wall. Size of map ship and number of layers for a given size penetrant are shown in table below: HILTi CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP648 -E W2511" or CP648 -E W4511 -314' Firestop Wrap Strip S ipP' rig Reproduced by HILTI, Inc. Courtesy of �� Underwriters Laboratories, Iwo Hilts Firestop Systems August 29, 2007 Page:1 aft FA�ir� t C System No. C -AJ -2342 F Rating - 3 Hr T Rating - 0 Hr W Rating -Class 1(See Item 3B) ng at 400° F -Less than 1 CFMISq Ft C m US Product Designation Pipe Size in. Max Opening Annular Space Annular Space Number of Nan Wrap Strip (mm) Diam (in.) Min in.(mm) Max in. (mm) Layers width in, (mm) CP648 -E W25J1" 1 1!2 (3$) 3 (T6) 3116 (4.8) 15116 (24) 1 1(25) CP648 -E W45t1 -3(4" 11/2(38) 3 (76) 3/16(4.8) 15J16 (24) 1 13/4(45) CP648 -E W2511' 2 (51) 3112 (89) 3116 (4.8) 15116 (24) 1 1 (25) CP648 -E W4511 -3/4" 2 (51) 3112 (89) 3116 (4.8) 15/16(24) 1 1314 (45) CP648 -E W45/1.3/4" 3(76)_ 4 (102) 3/16(4.8) 15 /t6 (24) 1 13/4 (45) CP648 -E W4511 -314' 3(76) 5 (127) 318 (10) 1 1/16(27) 2 1314 (45) CP648 -E W4511 -314' 4 (102) 6 (152) 3!8 (10} 1 1!8 (29) 2 1314 (45) 3 sECT%N A -A ' 1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specified in the individual 0300 or 0400 Series Wan and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features. A. Studs The 1 or 2 hr fire rioted gypsum board /stud wall amerr►bly shop be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall induce the following corhstmuction features. B. Gypsum Board*- -- Nom 5/8 in. thndc, 4 ft wide with square or tapered edges. The gypsum board type. thickness. numbs of loges, fastener type and sheet orientation shall be as specified in the individual 0300 or U400 Series Design in the Fire Resistance Directory. Max dam of opening is 5 in. The hoary F and T Ratings of the Firestop system are equal to the hoary fire rating of the wall assembly in which it is installed. 2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the Firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or cube to be rigidly supported on both sides of wolf assembly. The annular space between the pipe or tube and periphery of the opening stall be min 0 in (point contact) to max 1/2 in. The following types and yes of metallic pipes, conduit or tube may be used: A Steel Pipe -- Nom 4 in. dam (or smaller) Schedule 40 (or heavier) steel pipe. B. Iron Ripe -- Nan 4 in. dam (or smaller) cast or ductile iron pipe. C. Conduit -- Nan 4 in. dram (or smaller) steel electrical metallic tubing (E11T) or steel conduit D. Capper Tube -- Nan 4 in. dam (or smeller) Type L (err heavier) copper tube. E. Copper Ripe -- Nom 4 Tn. dam (or smaller) Regular (or heavier) copper pipe. 3. FiII, Void or Catty Material*- Sealant -- Mein 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contest location between pipe and wall, a min % in dam bead of fill material shall be applied at the'Pipe /wall interioce, HILTI CONSTRUCTION CHE1u1CW.S, DN OF HILTI INC -- CP606 Flexible Firestop Sealant *Barring the UL Classification Mark • ®� ®er Reproduced by HILTI, Inc. Courtesy of V Q Underwriters Laboratories, Inc. x FiRESTOP SYSTEMS June 03,2M5 W 0: W ° Date 8 Delta Description Drawn By. Checked By E-• Z _. V W e• V .:•a W h Q Client Information i HEALTHCARE REALTY N ONE 7000 Place SUiTE PHN . MiAMI, FL 33133 OFFICE: (305) 446.3666 � Project Number 09126 CAD File Name ONE 7000 Spa , _ // / / ///mom AM/// / //!//���j� 151 SEVILLA AVENUE, SUITE 26O m. CORAL GABLES, GABLES, FL 33134 OFFICE: (305) 442 -1188 _ it FAX: (305) 445 -1509 MiV11W. ADCINTERNATIONAL.NET , I t STATE OF� FLORIDA t AR- 0010536 ., , • RAYWIUNDO FEITO, RA. AA- 0001315 Architect • Sea1/Signature Construction Documents for; 10%.01%1diS�o�a�i NEW Jju at; ONE 7000 PLACE 3rd FLOOR 7000 SW 62nd AVENUE SOUTH MIAMI, FL 33143 • Issue Date &Issue Description d Drawn By Checked By 01 12_L09_L09 JP AR REVIEW Z_ Z CL . . a- t3 ' - W Al. Fill, Void or Cavity Material` -Wrap Strip - (As an aftemate to the wrap strip in Item 3A) One layer of intumhescent wrap strip is catti nuauusly _ ,wrapped around the pipe with ends butted and held in place with integrated tape. Wrap slip installed recessed matt 114 in. (6 mm) from top surface a of floor or from both surfaces of wag. Size of wrap strip for a given size penetrant are shown in the table below. HILTI CONSTRUCTION CHEMICALS, DIY OF HILTI INC - CP648- S-1.5" US, CP648�S -Z' US, CP64&S -3° US a CP64$ -S•4' US Wrap Stri p Product Designation Pipe Size th•(mm) Max Opening D`am (in.) Annular Space Min in. (mm) Annular Space Max in. (mm) Nom Wrap Strip Length in. (mm) Nary Wrap Strip Thick in. (mm) Nan Wrap Strip Width in. (mm) CP648- S-1,5• US 11/2(38) 3 (76) 3116 (4.8) 15/16(24) 6.5(165) 0.18 (4.6) 1(25) CP648S -2" US 2(51), 31/2(89), 3116 (4.8) 15/16(24) 8 (203) 0.18 (4.6) 1(25} CP648S•3" US 3(76) 4 (102) 3116 (4,8) 5116 (8) 11.5 (292) Al. Fill, Void or Cavity Material` -Wrap Strip - (As an aftemate to the wrap strip in Item 3A) One layer of intumhescent wrap strip is catti nuauusly _ ,wrapped around the pipe with ends butted and held in place with integrated tape. Wrap slip installed recessed matt 114 in. (6 mm) from top surface a of floor or from both surfaces of wag. Size of wrap strip for a given size penetrant are shown in the table below. HILTI CONSTRUCTION CHEMICALS, DIY OF HILTI INC - CP648- S-1.5" US, CP648�S -Z' US, CP64&S -3° US a CP64$ -S•4' US Wrap Stri p Product Designation Pipe Size th•(mm) Max Opening D`am (in.) Annular Space Min in. (mm) Annular Space Max in. (mm) Nom Wrap Strip Length in. (mm) Nary Wrap Strip Thick in. (mm) Nan Wrap Strip Width in. (mm) CP648- S-1,5• US 11/2(38) 3 (76) 3116 (4.8) 15/16(24) 6.5(165) 0.18 (4.6) 1(25) CP648S -2" US 2(51), 31/2(89), 3116 (4.8) 15/16(24) 8 (203) 0.18 (4.6) 1(25} CP648S•3" US 3(76) 4 (102) 3116 (4,8) 5116 (8) 11.5 (292) 0.18 (4.6) 13/4(45) CP648 -W US 4 (102) 6 (152) 318 (10) 11/8(29)1 15.1(384) 0.36(9)1 1314 (45) p Product Designation Pipe Size th•(mm) Max Opening D`am (in.) Annular Space Min in. (mm) Annular Space Max in. (mm) Nom Wrap Strip Length in. (mm) Nary Wrap Strip Thick in. (mm) Nan Wrap Strip Width in. (mm) CP648- S-1,5• US 11/2(38) 3 (76) 3116 (4.8) 15/16(24) 6.5(165) 0.18 (4.6) 1(25) CP648S -2" US 2(51), 31/2(89), 3116 (4.8) 15/16(24) 8 (203) 0.18 (4.6) 1(25} CP648S•3" US 3(76) 4 (102) 3116 (4,8) 5116 (8) 11.5 (292) 0.18 (4.6) 13/4(45) CP648 -W US 4 (102) Product Designation Pipe Size th•(mm) Max Opening D`am (in.) Annular Space Min in. (mm) Annular Space Max in. (mm) Nom Wrap Strip Length in. (mm) Nary Wrap Strip Thick in. (mm) Nan Wrap Strip Width in. (mm) CP648- S-1,5• US 11/2(38) 3 (76) 3116 (4.8) 15/16(24) 6.5(165) 0.18 (4.6) 1(25) CP648S -2" US 2(51), 31/2(89), 3116 (4.8) 15/16(24) 8 (203) 0.18 (4.6) 1(25} CP648S•3" US 3(76) 4 (102) 3116 (4,8) 5116 (8) 11.5 (292) 0.18 (4.6) 13/4(45) CP648 -W US 4 (102) 6 (152) 318 (10) 11/8(29)1 15.1(384) 0.36(9)1 1314 (45) Al • Fig, Void or Cavity Material' - Wrap Strip - (As an alternate to the wrap strip in Item 3A) - One layer of intumescent wrap strip is continuously mapped around the pipe with ends tufted and held in place with integrated tape. Wrap strip installed recessed max 114 in. (6 mm) iron top surface of floor or from both surfaces of wad. Size of wrap strip for a given size penetrant are shown in the table below. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP648S -1.5' US, CP648S -2' US, CP648S -3" US or CP648•S•4• US Wrap Strip B. Fin, Void a Cavity Material' - Sealant - Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor of both surfaces of wall. W Rating applies only when CP 601S or CP 604 sealant is used. HILTI CONSTRUCTION CHEMICALS, DIV OF HiLTi INC- FS-ONE Sealant, GP 601S Sealant or CP 604 Sealant C. Packing Material (rot shown) -Min 1/2 in, (13 mm) thickness of 4 pd (64 kg1m3) mineral wool batt insulation firmly packed into annular space and recessed from the top surface of floor to accommodate the required th'idQhess of fin material. Required only when CP 604 Sealant is used. 'Bearing the UL Clas9mbon Mark �I I Reproduced by HILTi, Ira. Courtesy of Underwriters Laboratories, Inc, August 29, 2007 Hilti Firestop Systems Page :2of2 PLACE - HEALTH SOUTH SUITE330 - DR. BONNER Description PLUMBING FIRE PENETRATION DETAILS Scale AS NOTED GUTIERREZ PE Consultant SeaUSIgnature All CL ENGINEERING DES I N Z GROUP CORP. PH. 786.863-7091 FAX. 305. 220.5196 :D P=3mO .J ERGUIN CAPOTE PE No. 62487, Luis 0. PEREZ PE No. 62586 YANDRO ■ - ■ -