10-650-0211. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,AND ALL
APPLICABLE LOCAL ORDINANCES.
2. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE
AFTER COMPLETION OF WORK.
3. PLUMBING CONTRACTOR SHALL FURNISH WRITTEN GUARANTEE THAT ALL PLUMBING WORK
SHALL BE FREE OF DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE
YEAR FROM FINAL ACCEPTANCE.
4. CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY FAMILIARIZE THEMSELVES WITH
EXISTING CONDITIONS. FIELD VERIFY LOCATION OF EXISTING POINTS OF CONNECTIONS
BEFORE SUBMITTING BID. OBTAIN ANY REQUIRED CLARIFICATION BEFORE COMMENCING
WORK.
5. WHERE INDICATED OR REQUIRED, EXISTING SYSTEM COMPONENTS SHALL BE CAREFULLY
REMOVED OR RELOCATED. EACH RESULTING OPENING IN THE BUILDING CONSTRUCTION
SHALL BE PROPERLY PATCHED AND FINISHED WITH THE SAME MATERIALS AS THOSE
ADJACENT TO THE OPENING.
6. COORDINATE NEW PLUMBING WORK WITH LIGHTING, ELECTRICAL, DUCTWORK,STRUCTURAL
FRAMING AND CEILING SYSTEMS.
7. CONTRACTOR SHALL BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND NOTIFY
ARCHITECT /ENGINEER OF ANY DEVIATION DUE TO FIELD CONDITIONS BEFORE
COMMENCING WORK.
8. CONTRACTOR SHALL COORDINATE LOCATION AND SIZE OF ALL PENETRATIONS THROUGH
WALLS, CEILINGS, FLOORS AND ROOFS WITH OTHER TRADES AND REPORT ANY DISCRE-
PANCIES TO ARCHITECT /ENGINEER.NO STRUCTURAL MEMBER SHALL BE CUT OR MODIFIED
WITHOUT WRITTEN AUTHORIZATION.
9. DRAWING ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR EXACT LOCATION OF
FIXTURES AND PIPING.
10. CONTRACTORS SHALL BE RESPONSIBLE FOR ALL PERMITS, TAXES, INSPECTIONS AND
TEST FEES.
11. ALL MATERIALS TO BE PROVIDED UNDER THIS DOCUMENTS SHALL MEET ALL THE
REQUIREMENTS OF THE F.P.C, AND ALL OTHER LOCAL STANDARDS AND REGULATIONS.
MATERIALS SHALL BE NEW, FREE OF DEFECTS AND OF AMERICAN MANUFACTURER,
INDELIBLY MARKED WITH MANUFACTURER NAME, WEIGHT AND /OR CLASS. MANUFACTURER
NAMES SHALL BE INTERPRETED AS ESTABLISHMENT OF REQUIRED TYPE, CLASS
AND QUALITY. MATERIAL SHALL BE PROVIDED AS FOLLOWS:
A. ALL WASTE, VENT, AND STORM PIPING BELOW GRADE SHALL BE ONE OF THE
FOLLOWING TYPES (AS PER TABLE - 702.2, F.P.C.) :
A.1 SERVICE WEIGHT CAST IRON, SOIL PIPE. PIPING AND FITTINGS SHALL CONFORM
TO THE REQUIREMENTS OF CISPI STANDARD 301, ASTM A -888 OR ASTM A -74,
LATEST ISSUE.
A.2 BELL AND SPIGOT SERVICE WEIGHT CAST IRON, WITH LEAD AND OAKUM, OR
GASKETED JOINTS. PIPING AND FITTINGS SHALL CONFORM TO THE REQUIREMENTS
OF CISPI STANDARD 301, ASTM A -888 OR ASTM A -74, LATEST ISSUE.
A.3 SCHEDULE 40 ABS OR (DWV) PCV PIPING. FOR BUILDINGS EXCEEDING 3- STORIES
IN HEIGHT, UNDERGROUND DRAINAGE PIPING SHALL BE SERVICE WEIGHT CAST IRON
AS PER SECTION A.1.
B. ALL WASTE, VENT, AND STORM PIPING ABOVE GRADE SHALL BE ONE OF THE
FOLLOWING TYPES (AS PER TABLE - 702.1, F.P.C.) :
B.1 SERVICE WEIGHT CAST IRON SOIL PIPE. PIPING AND FITTINGS SHALL CONFORM WITH
THE REQUIREMENTS OF CISPI STANDARD 301, ASTM A -888 OR ASTM A -74.
B.2 BELL AND SPIGOT, 'NO HUB' SERVICE WEIGHT CAST IRON, OR WROUGHT IRON, WITH
SEALING SLEEVES AND STAINLESS STEEL COUPLING JOINTS, CLAMPS AND BOLTS.
PIPING AND FITTINGS SHALL CONFORM WITH THE REQUIREMENTS OF CISPI STANDARD
301, ASTM A -888 OR ASTM A -74, LATEST ISSUE.
B.3 SCHEDULE 40 ABS OR (DWV) PCV PIPING. NO COMBUSTIBLE PIPING SHALL BE
LOCATED IN RETURN AIR PLENUM.
C. SANITARY PIPE FITTINGS:
CA JOINTS FOR HUBLESS PIPE AND FITTING SHALL CONFORM EITH THE F.P.C. AND THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS AND LOCAL CODE REQUIREMENTS.
HUBLESS COUPLINGS SHALL CONFORM TO CISPI 301. JOINTS FOR HUB AND SPIGOT
PIPE SHALL BE INSTALLED WITH COMPRESSION GASKETS CONFORMING TO THE
REQUIREMENTS OF ASTM STANDARD C -564 OR SHALL BE INSTALLED WITH LEAD
AND OAKUM.
D. DOMESTIC WATER PIPING AND FITTINGS SHALL CONFORM WITH TABLES 605.4 through
605.8. OF THE F.P.C. AND SHALL BE ONE OF THE FOLLOWING TYPES:
DA COPPER TYPE 'L' ABOVE GROUND AND COPPER TYPE 'K' BELOW GROUND
CONFORMING WITH ASME B -88, AND ASTM B -16, LEAD - FREE SOLDER.
DOMESTIC WATER PIPING SHALL NO BE INSTALLED BELOW SLAB, UNLESS
INDICATED OTHERWISE ON THESE DRAWINGS
HANG PIPE LARGER THAN 4" FROM TOP
OF JOISTS ONLY AT PANEL POINT
PIPE
SIZE
C- CLAMP, CONNECT TO TOP
VALVE WATER CLOSET
OF BEAM OR STEEL BAR JOIST
mm®
ADJUSTABLE BAND HANGER FOR PIPE 3-1/2"
AND SMALLER AND CAST IRON PIPE 2"
AND
SMALLER
1/4" NPT STANDARD PIPE THREAD
ca c�
LAVATORY/SINK
z z
=no
•-
5.54 KW
MAXIMUM OPERATING TEMPERATURE
140 F
r +
mmm
w a.cn a cn
0.35 GPM
_N ww di
wcwa -,0
D.2 PROVIDE WATER HAMMER ARRESTOR 18" HIGH, NEXT LARGE SIZE THAN PIPE
SERVING FIXTURE.
D.3 INSULATE ALL HOT WATER PIPING WITH 1" RIGID FIBERGLASS OR 1/2" THICK
FLEXIBLE FOAM INSULATION (ARMAFLEX). FLEXIBLE FOAM INSULATION
SHALL NOT BE SPLIT, AND SHALL BE TAPED AT BUTT JOINTS.
E. WALL CLEANOUTS.
EA JOSAM SERIES 58750 WITH ACCESS COVER OR EQUAL
E.2 PROVIDE CHROME PLATED BRASS ESCUTCHEONS WITH LOCKING SCREWS WHERE
PIPE PASS THROUGH FINISHED WALLS.
E.3 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH SOIL AND WASTE STACK.
F. VALVES.
F.1 QUATER TURN BALL VALVES, RATED FOR 125 PSI. MANUFACTURED BY NIBCO, SCOTT,
STOCKHAM OR EQUAL
F.2 PROVIDES STOPS AT ALL PLUMBING FIXTURES. EXPOSED STOPS SHALL BE CHROME
PLATED.
G. PLUMBING FIXTURES.
GA SEE PLUMBING FIXTURE SCHEDULE FOR FIXTURE SPECIFICATIONS.
G.2 PLUMBING FIXTURES SHALL COMPLY WITH WATER CONSERVATION REGULATION
FS.553.14.
G.3 EXPOSED HOT WATER PIPING SERVING PLUMBING FIXTURES SHALL BE
PROPERLY INSULATED.
12. PERFORM THE FOLLOWING TEST:
A. NEW DOMESTIC WATER PIPING SHALL BE HYDROSTATICALLY TESTED AT 100
PSIG FOR A PERIOD OF NO LESS THAN ONE HOUR.
B. WASTE AND VENT PIPING SHALL BE F -ILLED WITH WATER TO A 10 FOOT HEAD
AND ALLOWED TO STAND UNTIL THE WATER LEVEL REMAINS CONSTANT.
C. CORRECT ALL DEFECTS DISCLOSED BY ABOVE TESTING.
D. NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE PURGED OF DELETERIOUS MATTER
AND, WHERE REQUIRED BY THE ADMINISTRATIVE AUTHORITY, DISINFECTED PRIOR TO
UTILIZATION.THE METHOD TO BE FOLLOWED SHALL BE THAT PRESCRIBED BE THE HEALTH
AUTHORITY OR WATER PURVEYOR HAVING JURISDICTION OR, IN THE ABSENCE OF A
PRESCRIBED METHOD , THE PROCEDURE DESCRIBED IN EITHER AWWA C651 OR AWWA 652.
OR AS DESCRIBED IN SECTION 610 FPC 2004.
13. WASTE PIPING 2 1/2" AND SMALLER SHALL BE SLOPED AT 1/4° PER FOOT MINIMUM.
PIPES LARGER THAN 2 1/2" SHALL BE SLOPED AT 1/8" PER FOOT MINIMUM FALL
14. INSULATE ALL AIR CONDITIONING AND REFRIGERATION CONDENSATE DRAIN WITH 3/4"
INCOAFLEX PIPE INSULATION OR EQUAL FINISHED, WHERE EXPOSED, WITH 2 COATS
OF WHITE LATEX PAINT AS PER MANUFACTURER'S INSTRUCTION.
15. PIPING PENETRATION AT ROOFS, CEILINGS, FLOORS AND WALLS SHALL BE SEALED AIR
AND WATER TIGHT. WHERE PENETRATING FIRE RATED CONSTRUCTION, FIRE SAFE TO
PROVIDE PROTECTION MATCHING REQUIRED FIRE RESISTANCE RATING.
16. ALL HORIZONTAL VENT PIPING SHALL SLOPE TO DRAW TO STACKS. NO POCKETS OR
LOW POINTS SHALL BE CREATED IN THE VENT LINES WHICH MAY PREVENT VENTING IF
FILLED WITH CONDENSATION.
17. CEILING ACCESS PANELS SHALL BE PROVIDED FOR VALVES INSTALLED ABOVE OTHERWISE
NON- ACCESSIBLE CEILINGS.
18. NO EQUIPMENT OR MATERIALS SHALL BE PURCHASED OR INSTALLED PRIOR TO FINAL
APPROVAL OF SHOP DRAWINGS.
19. THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO SHOW
AS -BUILT CONDITIONS AT THE COMPLETION OF CONSTRUCTION.
20. FURNISH AND INSTALL DIELECTRIC COUPLINGS AT ALL CONNECTIONS BETWEEN
DISSIMILAR METALS.
21. THE EXISTING PLUMBING LINES INDICATED OR NOTED ON THESE DRAWINGS, ARE
SHOWN AS OBTAINED FROM EXISTING INFORMATION OR SITE OBSERVATIONS, AND
ARE ONLY APPROXIMATE IN LOCATION. THE CONTRACTOR SHALL VERIFY THESE
LOCATIONS, CONNECTION POINTS AND SIZES BEFORE PROCEEDING WITH WORK.
22. PRECAUTIONS SHALL BE TAKEN TO PREVENT CONTAMINATION OF OWNER EQUIPMENT,
FURNITURE AND CARPETING WITHIN THIS BUILDING. COVER AND WRAP EQUIPMENT.
FURNITURE AND CARPETING AS NECESSARY. DUST AND DEBRIS SHALL BE STRICTLY
CONTROLLED. CLOSE COORDINATION WITH OWNER WILL BE REQUIRED.
23. WHERE REQUIRED, EXISTING CEILINGS SHALL BE REMOVED TO MODIFY THE EXISTING
PLUMBING SYSTEMS. THESE CEILINGS SHALL BE REPLACED TO MATCH ADJACENT
SURFACES.
24. ALL DISCONNECTED PLUMBING LINES SHALL BE EITHER RECONNECTED OR CAPPED.
NO LINES SHALL REMAIN OPEN TO THE ATMOSPHERE.
25. IF CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS ", ALL MATERIALS
INSIDE THE R/A PLENUM SHALL HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A
MAX SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A.
"NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM."
INSTALL REINFORCING WIRE TO INSERT IN
NEW CONCRETE CONSTRUCTION.
STEEL DECK -- CONCRETE SLAB
` ' DRILLED -IN THREADED INSERT FOR EXISTING
ALL- THREAD ROD CONCRETE SLAB OR CAST IN PLACE FOR NEW
CONCRETE CONSTRUCTION. DO NOT USE SHOT -IN
INSERTS.
PROVIDE COPPER
COATED HANGERS
WHERE HANGERS CLEVIS HANGER FOR PIPE 4" AND LARGER
CONTACT BARE AND CAST IRON PIPE 3" AND LARGER
COPPER PIPE (l
INSULATION < Wz PROVIDE GALVANIZED STEEL SHEILD FOR ALL INSULATED PIPE. VERIFY
r SHIELDS.
mm®
-r
�t
PIPE
SIZE
mm®
VALVE WATER CLOSET
M -20L MICROPROCESSOR MODEL
mm®
TANK WATER CLOSET
WEIGHT
mmn;
PIPE FITTING
1/4" NPT STANDARD PIPE THREAD
mn'n
LAVATORY/SINK
VOLTAGE
=no
•-
5.54 KW
MAXIMUM OPERATING TEMPERATURE
140 F
r +
mmm
FLOW SWITCH DE- ACTIVATION
0.35 GPM
m
PIPE HANGERS
Tr/
aw.«
PROVIDE UPPER ATTACHMENT AS REQUIRED FOR CASES NOT SHOWN
HERE. DO NOT INSTALL HANGER INSIDE INSULATION OR OTHERWISE
PENETRATE VAPOR BARRIER. DO NOT HANG ONE PIPE FROM ANOTHER
EXCEPT IN CHASES. SLOPEALL WATER PIPING SLIGHTLY TOWARD
DRAINABLE LOCATIONS. HANGER SPACING FOR PIPE SIZE: AS
INDICATED ON TABLE. CAST IRON: 10' AND WITHIN 1' -0" OF ALL JOINTS.
ROD SIZES FOR PIPE SIZE: 2" AND SMALLER =3/8 ", 2 1/2" TO 3 " =1/2 ",
4 " =5f8% 6 " =3/4 ". 8" AND LARGER =7/8 ". LOCATE HANGERS WITHIN
1' -0 OF VALVES AND FITTINGS. PROVIDE SUPPLEMENTARY STEEL
STRUTS BETWEEN JOISTS IF REQUIRED. LOCATE HANGERS WITHIN 1' -0"
OF EQUIPMENT CONNECTIONS. ANCHOR WATER PIPE AGAINST SWAYING
DUE TO CHANGES IN WATER VELOCITY. CHAINS AND PERFORATED STRAP
IRON AND STEEL ARE NOT ACCEPTABLE. DO NOT SUSPEND PIPE FROM
JOIST BRACING MEMBERS. REFER TO CODES AND SPECS FOR FURTHER
INFORMATION. PROVIDE SEISMIC BRACING IF /AS REQUIRED BY LOCAL
AUTHORITIES. TRAPEZE HANGERS MAY BE USED FOR MULTIPLE PARRALLEL
PIPES, SEE "TRAPEZE PIPE HANGER DETAIL"
MAKE 1/2" BRANCH TO TRAP
PRIMER OFF TOP OF DOMESTIC
COLD WATER BRANCH PIPE TO
FIXTURE(S). INSULATE PIPE
UPSTREAM OF TRAP PRIMER, BUT
NOT DOWNSTREAM.
LOCATE TRAP PRIMER WHERE AN
ACCESS DOOR (REFER TO
SPECIFICATIONS) CAN BE PLACED
IN FRONT OF IT IN AN ACCESSIBLE
LOCATION. INSTALL PRIMER
MINIMUM 6" ABOVE FLOOD RIM OF
FIXTURE BEING SERVED.
PROVIDE FLOOR DRAIN BODY OR
P -TRAP WITH THREADED TRAP
PRIMER CONNECTION. PROVIDE-
FITTINGS AND ADAPTERS AS
REQUIRED TO MAKE WATER -TIGHT
CONNECTION TO DRAIN.
PROJECT NOTES
-ALL DISCONNECTED PLUMBING LINES FOR EXISTING FIXTURES SHALL BE CAPPED.NO LINES SHALL REMAIN
OPEN TO THE ATMOSPHERE
- INSTALL A WATER HAMMER ARRESTER FOR EACH PLUMBING FIXTURE SUPPLY BRANCH USING TABLE (2/P -2)
- INSTALL A SHUTOFF VALVE ON THE FIXTURE SUPPLY TO EACH PLUMBING FIXTURE.
-THE INSTALLATION OF ANY PART OF PLUMBING SYSTEM SHALL BE ACCORDING TO FBC -P SECTION 307
-ANY PLUMBING LINES WHICH REQUIRE REMOVAL AND /OR ALTERATION. G.C. SHALL CAP AND FILL SLAB
WITH SAME FIRE RATED INTEGRITY.
- PROVIDE METAL SLEEVE AT ALL WALL AND SLAB PENETRATIONS.
-ALL HORIZONTAL DRAIN PIPE 2 "- OR SMALLER SHALL BE SLOPED AT 1 /4 " /FT
=ALL HORIZONTAL DRAIN PIPE FROM 3" TO 6" SHALL BE SLOPED AT 1 /8 " /FT MIN.
-ALL HORIZONTAL DRAIN PIPE 8" OR LARGER SHALL BE SLOPED AT 1/16 " /FT MIN
- PROVIDE AUTOMATIC TRAP RESEAL FOR ALL FLOOR DRAINS
CONNECT NEW LINES TO EXISTING, VERIFY EXACT LOCATION,SIZE & CAPACITY IN FIELD PRIOR TO BID THE
PROJECT. NOTIFY ARCHITECT & ENGINEER OF ANY DISCREPANCIES.
CONTRACTOR IS STRONGLY ENCOURAGE TO PERFORM A VISIT TO VERIFY ALL CONDITIONS THAT MAY AFFECT THE
SCOPE OF WORK.CONTRACTOR NOT PERFORMING A SITE VISIT ARE ACKNOWLEDGING AND ACCEPTING ALL SITE
CONDITIONS AS THEY EXIST. VERIFY: POINTS OF CONNECTIONS; EXISTING LINES ( SIZE, CAPACITY,MATERIALS, ....)
-ALL PLUMBING WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH LOCAL CODES AND ORDINANCES
AND ALL STANDARDS OF CONSTRUCTION ESTABLISHED BY THE LANDLORD.
- SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH
THE PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. NO FACSIMILES OR FACSIMILE COPIES
SHALL BE ACCEPTED.
--IF ANY CONFLICT IS ENCOUNTERED WITHIN THE DESIGN DOCUMENTS, REGARDLESS OF TRADE OR RESPONSIBILITY,
THE GREATER SCOPE OF WORK SHALL PREVAIL
THESE PLANS ARE FOR BUILDING DEPARTMENT REVIEW ONLY. THEY ARE NOT TO CONSTRUED AS
CONSTRUCTION DOCUMENTS UNTIL ALL BUILDING DEPARTMENT APPROVALS ARE OBTAINED.
- CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS BEFORE PROCEEDING WITH WORK.IF ANY
DISCREPANCIES,ERRORS OR OMISSIONS ARE ENCOUNTERED ON PLANS, CONTRACTOR SHALL NOTIFY ARCHITECT/
ENGINEER BEFORE ANY PART OF THE WORK IS STARTED SO THAT PROPER CORRECTIONS BE MADE. IF
ARCHITECTS/ENGINEER IS NOT NOTIFIED PRIOR TO COMMENCING OF THE WORK, THE CONTRACTOR SHALL
BEAR FULL RESPONSIBILITY FOR ANY DISCREPANCIES , ERROR OR OMISSIONS.
INSTALL PER PDI STANDARDS AND
MANUFACTURER'S INSTRUCTIONS.
PROVIDE A WHA AT ALL QUICK
CLOSING VALVES,
SINGLE/DOUBLE FDCrURE
r•• •r
-r
�t
PIPE
SIZE
FIXTURE
UNIT LOAD
VALVE WATER CLOSET
M -20L MICROPROCESSOR MODEL
DIMENSIONS
TANK WATER CLOSET
WEIGHT
4 POUNDS
PIPE FITTING
1/4" NPT STANDARD PIPE THREAD
PRESSURE REQUIREMENTS
LAVATORY/SINK
VOLTAGE
277 V
•-
5.54 KW
MAXIMUM OPERATING TEMPERATURE
140 F
r +
0.4 GPM
FLOW SWITCH DE- ACTIVATION
0.35 GPM
• OR • r E. SUPPLY
IF HORIZONTAL r M .S r LONG,
PROVIDE ONE END OF
IF BRANCH IS GREATER THAN 20' LONG, PROVIDE
ANOTHER WHA IN MIDDLE, EACH IZ r FOR HALF THE
FIXTURE UNITS.
FIXTURE UNIT r
11
•+ i
•�
VALVE WATER CLOSET
M -20L MICROPROCESSOR MODEL
DIMENSIONS
TANK WATER CLOSET
WEIGHT
4 POUNDS
PIPE FITTING
1/4" NPT STANDARD PIPE THREAD
PRESSURE REQUIREMENTS
LAVATORY/SINK
VOLTAGE
277 V
•-
5.54 KW
MAXIMUM OPERATING TEMPERATURE
140 F
FLOW SWITCH ACTIVATION
0.4 GPM
FOR BATTERIES OF FIXTURES , PROVIDE WATER HAMMER ARRESTERS BY SIOUX CHIEF, PRECISION PLUMBING
PRODUCTS, O. APPROVED EQUIVALENT WITH PISTON AND O-RING CONSTRUCTION .r +r
ASSE 11010 AND ANSI I A11112.26.11611 CERTIFICATION , INSTALL IN HORIZONTAL OR VER11CAL POSITION , BUT
-YMA-
WHERE REQUIRED BY LOCAL CODE
�i1�t�►
AUTOMATIC TRAP PRIMER VALVE
WITH INTEGRAL AIR GAP.
PROVIDE DISTRIBUTION UNIT(S)
WHERE MORE THAN ONE TRAP IS
SERVED BY ONE TRAP PRIMER
VALVE.
INSTALL TRAP PRIMER LINES
DOWNSTREAM OF TRAP PRIMER
OR DISTRIBUTION UNIT USING 1/2"
TYPE "K" SOFT COPPER TUBING.
INSTALL WITHOUT KINKS, AND
SLOPE CONTINUOUSLY TOWARDS
FLOOR DRAIN.
CONCRETE FLOOR
IF PIPE IS BELOW FLOOR SLAB
a ON GRADE, PROVIDE 1/2-
ELASTOMERIC INSULATION FROM
RIMER CONNECTION TO 1" ABOVE
FLOOR SLAB.
GTRAP PRIMER IN WET WALL
)
CHRONOMITE
ELECT WATER HTR (INSTANTANEOUS)
UNIT DESIGNATION
TANKLESS WATER HEATER
MODEL
M -20L MICROPROCESSOR MODEL
DIMENSIONS
6 -1/4" X 9 -5/8" X 2 -3/4"
WEIGHT
4 POUNDS
PIPE FITTING
1/4" NPT STANDARD PIPE THREAD
PRESSURE REQUIREMENTS
25 PSI MIN /150 PSI MAX
VOLTAGE
277 V
KW RATING
5.54 KW
MAXIMUM OPERATING TEMPERATURE
140 F
FLOW SWITCH ACTIVATION
0.4 GPM
FLOW SWITCH DE- ACTIVATION
0.35 GPM
FDCTURE CONNECTION SCHEDULE
KITCHEN SINK
CD
FW
VA
CA
�j
J
N co
FD
FU
FAUCET FLOW CONTROL
HOT WATER OUTLET
H HEATAERR
ELECTRICAL
SUPPLY
HOT' VALVE I
"COLD" VALVE
SINK
MAIN PIPE
COLD WATER INLET
- SOV
COPPER
TUBING
�� �I ar•- •• �I� -r
+ �+
r a � alr •.
rem, 84=11111111 kllil!i!1111 moke:010
1 10 11
4 12
5 6
n .... o.... .: d:: 13
a;
7 _._ 6 14
WALL =- 15
FADE CLEANOUT (G.C.O.)
8 5
1/8" C.I. BEND
7� BALANCE OF PIPING SAME AS CLEANOUT TO GRADE.
9 $� CLEANOUT & ACCESS. COVER TO BE
FLUSH W/TOP OF FLOOR.
FLOOR TO BE OC TED I .1 /� BALANCE OF PIPING SAME AS CLEANOUT TO GRADE.
C.O. NOT TO BE LOCATED IN �/
CARPETED AREA 10 BRASS CLEANOUT PLUG W /COUNTER SUNK HEAD.
11
MAY EXTEND AS A WASTE FINISH GRADE
OR VENT. REFER TO PLANS. 12 16" SQUARE CONC. PAD TROWEL SMOOTH AND EDGE.
(/ CHROME WALLCOVER & SCREW.
13 C.E. WASTE LINE. LENGTH TO SUITE.
WALL
t4 WASTE LINE
PLUGGED TEE W /CXEANOUT.
15 1/8 BEND IF CLEANOUT OCCURS AT END OF LINE,
FLOOR LINE
CLEANOUT DETAILS
N.T.S.
DESCRIPTION
SANITARY PIPE
VENT PIPE
COLD WATER PIPE
HOT WATER PIPE
CONDENSATE DRAIN PIPE
FILTERED WATER
VACUUM SYSTEM PIPING
COMPRESSOR SYSTEM PIPING
GATE -VALVE
P -TRAP
WATER HAMMER (SHOCK)
ARRESTOR.
WALL CLEAN OUTS
FLOOR DRAIN
FIXTURE UNITS
SYMBOL
CW
HW
UG
DCV
0
F.F.
S.F.
VI
=C
DESCRIPTION
COLD WATER PIPE
HOT WATER PIPE
CONNECT TO EXISTING
r•
FLOOR CLEAN-OUT
FIRST •O-
SECOND FLOOR
VENT THRU .••
PIPING TURNING UP
PIPING TURNING i•
151 SEVILLA AVENUE, SUITE 200
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WNWW. ADCINTERNATIONAL.NET
Consultant w