PROJECT NOTES
—ALL DISCONNECTED PLUMBING LINES FOR EXISTING FIXTURES SHALL BE CAPPED.NO LINES SHALL REMAIN
OPEN TO THE ATMOSPHERE
— INSTALL A WATER HAMMER ARRESTER FOR EACH PLUMBING FIXTURE SUPPLY BRANCH USING TABLE (2/P -2)
— INSTALL A SHUTOFF VALVE ON THE FIXTURE SUPPLY TO EACH PLUMBING FIXTURE.
—THE INSTALLATION OF ANY PART OF PLUMBING SYSTEM SHALL BE ACCORDING TO FBC —P SECTION 307
—ANY PLUMBING LINES WHICH REQUIRE REMOVAL AND /OR ALTERATION, G.C. SHALL CAP AND FILL SLAB
WITH SAME FIRE RATED INTEGRITY.
— PROVIDE METAL SLEEVE AT ALL WALL AND SLAB PENETRATIONS.
—ALL HORIZONTAL DRAIN PIPE 2 "M OR SMALLER SHALL BE SLOPED AT 1 /4 " /FT
—ALL HORIZONTAL DRAIN PIPE FROM 3" TO 6" SHALL. BE SLOPED AT 1 /8 " /FT MIN.
—ALL HORIZONTAL DRAIN PIPE 8" OR LARGER SHALL BE SLOPED AT 1 /16 "/FT MIN
— PROVIDE AUTOMATIC TRAP RESEAL FOR ALL FLOOR DRAINS
CONNECT NEW LINES TO EXISTING, VERIFY EXACT LOCATION,SIZE & CAPACITY IN FIELD PRIOR TO BID THE
PROJECT. NOTIFY ARCHITECT & ENGINEER OF ANY DISCREPANCIES.
CONTRACTOR IS STRONGLY ENCOURAGE TO PERFORM A VISIT TO VERIFY ALL CONDITIONS THAT MAY AFFECT THE
SCOPE OF WORK.CONTRACTOR NOT PERFORMING A SITE VISIT ARE ACKNOWLEDGING AND ACCEPTING ALL SITE
CONDITIONS AS THEY EXIST. VERIFY: POINTS OF CONNECTIONS; EXISTING LINES ( SIZE, CAPACITY, MATERIALS, ....)
—ALL PLUMBING WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH LOCAL CODES AND ORDINANCES
AND ALL STANDARDS OF CONSTRUCTION ESTABLISHED BY THE LANDLORD.
— SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH
THE PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. NO FACSIMILES OR FACSIMILE COPIES
SHALL BE ACCEPTED.
—IF ANY CONFLICT IS ENCOUNTERED WITHIN THE DESIGN DOCUMENTS, REGARDLESS OF TRADE OR RESPONSIBILITY,
THE GREATER SCOPE OF WORK SHALL PREVAIL
—THESE PLANS ARE FOR BUILDING DEPARTMENT REVIEW ONLY. THEY ARE NOT TO CONSTRUED AS
CONSTRUCTION DOCUMENTS UNTIL ALL BUILDING DEPARTMENT APPROVALS ARE OBTAINED.
— CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS BEFORE PROCEEDING WITH WORK.IF ANY
DISCREPANCIES, ERRORS OR OMISSIONS ARE ENCOUNTERED ON PLANS, CONTRACTOR SHALL NOTIFY ARCHITECT/
ENGINEER BEFORE ANY PART OF THE WORK IS STARTED SO THAT PROPER CORRECTIONS BE MADE. IF
ARCHITECTS/ENGINEER IS NOT NOTIFIED PRIOR TO COMMENCING OF THE WORK, THE CONTRACTOR SHALL.
BEAR FULL RESPONSIBILITY FOR ANY DISCREPANCIES , ERROR OR OMISSIONS.
� p
SANITARY RISER
WATER HAMMER. THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER HAMMER. A
WATER — HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK — CLOSING
VALVES ARE UTILIZED. WATER — HAMMER ARRESTORS SHALL BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. WATER — HAMMER
ARRESTORS SHALL CONFORM TO ASSE 1010
. Q ®�ESnG
EXISING
2
�
?4
INSTANT WATER HEATER
CHRONOMITE
MODEL M -20L
5.54 KW , 277 VOLTS
EXISTING 4" WASTE STACK
EXISTING 2" DOMESTIC WATER
EXISTING 3" VENT STACK
4� S.S. SINGLE COMPARTMENT SINK W/ GOOSENECK FAUCET (LEVER HANDLES)
PLUMBING
Scale: Y40 = 1'-0w +
1
ENGINEERING b''ESIGN
21 SW ■
tl 786.E363-7091
■ ■
:D P=1 00
.j ERGUIN CAPOTE PE No. 62487
Luis CL "• ■ GUTIERREZ PE No. 66391
151 SEVILLA AVENUE, SUITE 200
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
STATE OF FLORIDA AR- 0010536
RAYMUNDO FEITO, R.A. AA— CO01315
Architect • Seal/Signature
Construction Documents for:
HE"c111111111 1
S
,& 3M
at:
ONE 7000 PLACE
3rd FLOOR
7000 SW 62nd AVENUE
SOUTH MIAMI, FL 33143
Consultant • Seal/Signature