10-650-019BE ,T NOTES: 1. DIMENSIONS A, B, AND C AS INDICATED ON THE DRAWINGS. 2• PROVIDE INSULATED FLEXIBLE DUCT UNLESS OTHERWISE NOTED. ROUTE TO DIFFUSER, REGISTER, GRILLE, OR HEPA/ULPA FILTER WITH MINIMUM BENDS AND DISTANCE. 3. TAP MUST BE A MINIMUM OF 2 INCHES SMALLER THAN MAIN DUCT. SIDE TAP SHOWN, BOTTOM TAP SIMILAR. 4. EXTEND SHEET METAL DUCT TO LIMIT FLEXIBLE DUCT LENGTH TO 10 FEET OR LESS, AS INDICATED. 5. USE CONICAL TEE FITTING WHENEVER POSSIBLE OR UNLESS OTHERWISE INDICATED. FLEXIBLE DUCT CONNECTION DETAIL. SCALE: 3 4 4 MULTI BLADE OR CURTAIN TYPE DAMPER 1 2 SLEEVE 3 1 FIGURE 1 FIGURE 2 jTEM• DESCRIPTION 1. PICTURE FRAME MOUNTING ANGLE (2 PER DAMPER /1 PER SIDE) 2. DAMPER /SLEEVE ASSEMBLY 3. FIRE RATED WALL OR FLOOR 4. FASTENER FIRE DAMPER - DUCTMATE DETAIL. SCALE: N.T.S. r1RINT TURNING SHEET METAL SC;KLW hA51LNLK5 NOTES: 1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA. 2. WHEN W1 DOES NOT EQUAL W2 VANE SHALL BE SINGLE VANE TYPE REGARDLESS OF W DIMENSION. VANE TYPE REGARDLESS OF W DIMENSION. 3. ALL SINGLE VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE BETWEEN VANES AND A 1 1/2" MAXIMUM SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE. 4. WHEN W1 EQUALS W2 AND W2 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE. •0 ELBOW WITH TURNING 12 GAGE MINIM SIZE SUPPORT EXISTING STRU( FlTlbq f. 6 "x2 "x1/8" GALVANIZED STEEL CHANNEL RIGID DUCT SUPPORT DETAIL. NOTE: SUPPORTS SHALL BE PLACED AT 5' -0" ON CENTER FOR DUCTS UP TO 35" AND 6' -0" FOR DUCTS UP TO 59% PER SMACNA RECOMENDATIONS. MASONARY FIRE DAMPER-MODEL DAMPER-MODEL RUSKIN 1BD2 DETAIL. HANGER SUPPORT FROM EXISTING STRUCTURE `' 1 SHEET METAL —' SADDLE MINIMUM 5' -0" ON CENTER M. r NOTE: HANGERS SHALL BE LOCATED AT DUCT JOINTS OR AS CLOSE AS POSSIBLE AS PER SMACNA DUCT CONSTRUCTION STANDARDS ROUND DUCT- '•• . . BAND OF SAME SIZ AS HANGER STRAP u ewr;ER L= 0.25xW(4" MIN.). VOLUME CONTROL DAMPER WITH LOCKING NUT. PROVIDE INSULATION STAND OFF BRACKET FOR ALL INSULATED DUCTS. Q OVER 12" HIGH USE MULTIPLE BLADES. NOTE: EXHAUST AND RETURN TAKE OFF IS SIMILAR. ,'BRANCH TAKE OFF DETAIL. SCALE: (914 MM) I MAX. DESIGN 151 SEVILLA AVENUE, SUITE 200 CORAL GABLES, FL 33134 OFFICE: (305) 442 -1188 FAX: (305) 445 -1509 WWW. ADCINTERNATIONAL.NET STATE OF FLORIDA AR- 0010536 RAYMUNDO FEITO, R.A. AA- 0001315 Architect • Seal/Slgnature Construction Documents for: Ifflill SW 0� at: ONE 7000 PLACE 3rd FLOOR 7000 SW 62nd AVENUE SOUTH MIAMI, FL 33143 Issue Date S Issue Description Drawn By Checked By 01 12 0909 JP AR REVIEW Date & Delta Description Drawn By Checked By Client Information HEALTHCARE REALTY ONE 7000 Place SUITE PHN MIAMI, FL 33133 OFFICE: (305) 446 -3666 Project Number 09126 CAD File Name ONE 7000 PLACE - HEALTH SOUTH SUITE330 - DR. BONNER Description MECHANICAL DETAILS Scale AS NOTED