GENERAL NOTES
1- INSTALLATION SHALL BE DONE IN STRICT ACCORDANCE WITH THE FLORIDA BUILDING CODE 2007
WITH 2009 SUPPLEMENTS AND NEC 2008.
2- ALL CONDUCTORS SHALL BE COPPER, THWN TYPE RATED AT 750C.
3- ALL CONDUITS SHALL BE E.M.T. UNLESS INDICATED OTHERWISE.
4- ALL RECEPTACLES AND LIGHT SWITCHES SHALL HAVE AN ENGRAVED BRANCH CIRCUIT IDENTIFICATION
PLATE INDICATING PANEL AND CIRCUIT NUMBER.
5- PROVIDE TYPED CIRCUIT INDEX FOR ALL NEW AND EXISTING PANELBOARDS.
6- PROVIDE ALL REQUIRED PERMITS AND PAY ALL FEES.
7- ALL BOXES SHALL BE METALLIC.
8- ALL RECEPTACLES SHALL BE 18" A.F.F. UNLESS INDICATED OTHERWISE.
9- PROVIDE A GREEN GRID. WIRE TO ALL RECEPTACLES, AND FIXED EQUIPMENT.
10- CONTRACTOR MUST VISIT SITE TO BECOME FAMILIAR WITH EXISTING CONDITIONS BEFORE
BIDDING THIS JOB.
11- CONTRACTOR SHALL INSTALL ALL ELECTRICAL EQUIPMENT FURNISHED BY THE OWNER OR
OTHER CONTRACTOR.
12- ALL CONDUITS SHALL RUN CONCEALED U.I.O.
13- PROVIDE COVER PLATES FOR ALL OUTLETS.
14- ALL CONDUIT PENETRATIONS OF FIRE -RATED WALLS, FLOORS, AND CEILINGS SHALL BE SEALED IN
ACCORDANCE WITH REQUIREMENTS OF NEC ARTICLE 300 -21 AND DETAILS I AND 11 ON THIS SHEET.
15- PROVIDE ALL THE REQUIRED WIRING AND CONDUIT.
16- FOR ALL DISCONNECTS PROVIDE NEMA 1 ENCLOSURE INDOORS AND NEMA 3R
ENCLOSURE OUTDOOR.
17- ALL ELECTRICAL SWITCHES SHALL BE 48" A.F.F. UNLESS INDICATED OTHERWISE.
18- ALL LIGHT SWITCHES SHALL HAVE AN ENGRAVED BRANCH CIRCUIT IDENTIFICATION PLATE
INDICATING PANEL AND CIRCUIT NUMBER.
19- COORDINATE MOUNTING HEIGHT OF ALL LIGHTING FIXTURES WITH ARCHITECT.
20- SHEETS WITH NOTES IN HEXAGON ARE FOR SPECIFIC LOCATIONS. NOTES WITHOUT HEXAGON
ARE GENERAL NOTES FOR THAT SHEET.
21- ALL FLUORESCENT FIXTURES SHALL USE ENERGY CONSERVATION BALLAST AND LAMPS
LAMPS (GE OR SYLVANIA)
22- ALL CONDUITS RUNNING UNDERGROUND BE PVC SCHEDULE 40 1" MINIMUM.
23- ALL CONDUITS RUNNING EXPOSED IN EXTERIOR AREAS UP TO 8' -0" HIGH TO BE RIGID METALLIC CONDUIT.
24- ALL CONDUITS RUNNING CONCELEAD TO BE EMT TYPE.
SYMBOL LEGEND
I SYMBOL I DESCRIPTION I
FLUORESCENT LIGHTING FIXTURE CEILING r IN NORMAL -•
TYPE AS SPECIFIED
FLUORESCENT DOWNLIGHT CEILING MTD. TYPE AS SPECIFIED.
(Z} CEILING /WALL MTD. EXIT LIGHT.
CEILING /WALL MTD. EMERGENCY LIGHT.
it TELEPHONE OUTLET MTD 18" AFF.,U.1.0
DATA OUTLET MTD. 18" A.F.F.,U.I.O
n FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR ADDRESSABLE TYPE.
FIRE MTD. AT 8 r FROM FINISHED FLOOR TO BOTTON
OF
STROBE FIRE ALARM SYSTEM r AT .• r
FROM FINISHED FLOOR TO BOTTON F DEVICE.
20A, 120/277VAC SINGLE POLE TOGGLE SWITCH, SPECIFICATION GRADE
4' -0" A.FF.F.
$3 THREE WAY SWITCH, SAME AS ABOVE
20A, 125V, 3 WIRE GROUNDING TYPE SPECIFICATION GRADE DUPLEX
RECEPTACLE, MTD. 18" A.F.F., U.I.O.
20 A. 125V. 3 WIRES GROUND TYPE SPECIFICATION GRADE
QUADRUPLEX RECEPT. MTD. 18" A.F.F., U.I.O.
20A, 125V, 3 WIRE GROUND FAULT INTERRUPTER DUPLEX
RECEPTACLE, 6" ABOVE COUNTERS OR 42" A.F.F., U.I.O.
(2) MOTOR, NUMBER IN CIRCLE DENOTES HORSE POWER RATING
Q�r® CEILING OR WALL MTD. JUNCTION BOX
SURFACE WALL MTD. PANELBOARD
FLUSH MTD. PANELBOARD
330 SAFETY DISCONNECT • OF POLES,
15 15=FUSE SIZE, • r
-140TE: ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED FOR THIS PROJECT-
151 SEVILLE` AVENUE c'..'IT2 2GG ~ " "
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
Date & Delta Description Drawn By Checked By
a
1 04/15/2011 P &G LP
I BLDG DEPT. COMM.
Client Information
HEALTHCARE REALTY
ONE 7000 Place
SUITE PHN
MIAMI, FL 33133
OFFICE: (305) 446 -3666
Project Number
09126
CAD File Name
ONE 7000 PLACE - HEALTH SOUTH SUITE330 - DR. BONNER
Description
ELECTRICAL NOTES AND OVERALL PLAN
Scale
AS NOTED