10-649-018O L= 0.25xW(4" MIN.).
Q VOLUME CONTROL DAMPER WITH LOCKING NUT. PROVIDE
INSULATION STAND OFF BRACKET FOR ALL INSULATED DUCTS.
2� OVER 12" HIGH USE MULTIPLE BLADES.
NOTE: EXHAUST AND RETURN TAKE OFF IS SIMILAR.
BRANCH TAKE OFF DETAIL.
SCALE: N.T.S.
1/8 "0 HANGER ROD SUPPORT
fFROM EXISTING STRUCTURE
WITH A 1/4" BOLT, 1" EMBEDMENT.
HANGER
BAND OF SAME SIZE
AS HANGER STRAP
SHEET METAL � 36" (914 MM)
SADDLE MINIMUM DIA. MAX.
5' -0" ON CENTER 6" MIN. FIBROUS ROUND
AND FLEXIBLE
DUCT
NOTE:
HANGERS SHALL BE LOCATED AT
DUCT JOINTS OR AS CLOSE AS
POSSIBLE AS PER SMACNA DUCT
CONSTRUCTION STANDARDS
(Existing/New ROUND DUCT SUPPORT DETAIL.
SCALE: N.T.S.
STRUCTURE ABOVE.
AR- 0010536
AA- CO01315
C.B. UNIVERSAL CONCRETE
SUPPLY AIR DUCT
Architect • Seal/Signature
INSERTS GRINNELL FIG. 282
SEE PLAN FOR SIZES.
OR EQUAL.
-•- THREADED 1/4-
Construction Documents for:
\S-Qullr�11'14 P. AV
at:
ONE 7000 PLACE
SUITE: 545
5th FLOOR
7000 SW 62nd AVENUE
SOUTH MIAMI, FL 33143
STEEL ROD
LOW
PRESSURE DUCT
AC AR
PERMIT ISSUE
0
DOUBLE LOCK NUT
AIR VOLUME CONTROL
FLEXIBLE MEDIUM
PRESSURE DUCT
ACCESS DOOR
NOTE:
TERMINAL UNITS SHALL
BE MOUNTED
SO ACCESS
DOOR AND
DIAL CAN BE
EASILY REACHED FROM
BELOW
NOTES
a
1D EXISTING SUPPLY AIR DUCTWORK UPSTREAM OF VAV BOXES)
0
VAV CONTROLLERS AND ELECTRONIC THERMOSTATS
CONNECTION SHALL BE IN ACCORDANCE WITH THE LATEST
U
a
TO BE INSTALLED AS PER MANUFACTURER RECOMMENDATION
EDITION OF SMACNA LOW PRESSURE DUCT MANUAL
IL
CO)
AND TO MATCH EXISTING BLDG SYSTEM. LOCATION SHALL
SUPPLY DUCTWORK SHALL BE INSULATED WITH 1"
Z
BE AS INDICATED.
THICK FIBERGLASS BLANKET INSULATION WITH FOIL
®
ALL SUPPLY AIR DIFFUSER OR RETURN AIR GRILLE WITH MANUAL
KRAFT VAPOR BARRIER (R -4.2).
N
w
0 ALL SUPPLY AIR DUCTWORK DOWNSTREAM OF VAV BOXES
O
DAMPER, TO MATCH EXISTING.
SHALL BE OF FIBERGLASS DUCTBOARD CONSTRUCTION, 1"
Q5
SPACE OCCUPANCY REMAINS THE SAME (OFFICE). OUTSIDE AIR
IN THICH (R -4.2) AND SHALL BE FABRICATED AND INSTALLED
w
REQUIREMENTS DO NOT VARY.
AS PER LATEST EDITION OF SMACNA "FIBROUS DUCT MANUAL"
®
SEAL ANY AIR LEAKS IN SUPPLY MAINS AND REPAIR ANY INSULATION.
TYPICAL VARIABLE AIR VOLUME
VAV BOX DETAIL.
SCALE: N.T.S.
Z
Z
IPRINTFO ON:07 -11 -2010
TURNING VAP
SHEET METAL 5cREW FA5TENER5
OTES:
ALL VANED ELBOWS SHALL BE CONSTRUCTED AND
INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2 VANE SHALL BE SINGLE
VANE TYPE REGARDLESS OF W DIMENSION.
ALL SINGLE VANES SHALL HAVE A 2" RADIUS,
1 1/2" MAXIMUM SPACE BETWEEN VANES AND A
3/4" TRAILING EDGE.
WHEN WI EQUALS WZ AND W IS GREATER THAN 20"
VANES SHALL BE DOUBLE VANE TYPE.
90 ELBOW WITH TURNING VANES DETAIL.
SCALE: N.T.S.
12 GAGE MINIMi
SIZE SUPPORT
EXISTING STRU(
DUCT WORK
6 "x2 "x1/8" GALVANIZED
STEEL CHANNEL.
RIGID DUCT SUPPORT DETAIL.
SCALE: N.T.S.
SEAL JOINT
WITH DUCT
SEALER AND
TAPE
MANUAL VOLUME
DAMPER
DRAW
BAND
AIR
LOW VELOCITY SUPPLY
AIR DUCT (SEE PLAN VIEW)
MANUAL VOLUME
DAMPER
INSTALL FLEXIBLE DUCT
SUPPORT AS REQUIRED
FOR NO SAG.
SPIN COLLAR WITH INSULATED AND VAPOR SEALED
DAMPER AND COLLAR AND DIFFUSER BACK
EXTRACTOR PANEL
DIFFUSER
DETAIL $$AP'
N.T.S.
NOTE:
SUPPORTS SHALL BE PLACED
AT 5' -0" ON CENTER FOR DUCTS
UP TO 35" AND 6' -0" FOR DUCTS
UP TO 59 ", PER SMACNA RECOMENDATIONS.
NOTE: /
FOLLOW SMACNA DUCT f
CONSTRUCTION STANDARDS
(Existing/New) /New FLEXIBLE DUCT CONNECTION DETAIL.
SCALE: N.T.S.
DETAIL "A"
AIR FLOW
SPIN COLLAR FITTING WITH
EXTRACTOR AND DAMPER.
QUADRANT OPERATOR TO BE
OUTSIDE INSULATION. PROVIDE
INSULATION GUARD WHERE
NECESSARY.
` SEAL JOINT WITH DUCT
�C SEALER AND TAPE
FIGURE 1 FIGURE 2
ITEM. DESCRIPTION
1. PICTURE FRAME MOUNTING ANGLE
(2 PER DAMPER /1 PER SIDE)
2. DAMPER /SLEEVE ASSEMBLY
3. FIRE RATED WALL OR FLOOR
4. FASTENER
FIRE DAMPER - DUCTMATE DETAIL.
SCALE: N.T.S.
MASONARY
FIRE DAMPER -MODEL RUSKIN IBD2 - DETAIL.
SCALE: N.T.S.
3 �n
4
MULTI BLADE OR
CURTAIN TYPE
DAMPER
SLEEVE
1
151 SEVILLA AVENUE, SUITE 200
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
VVVVW. ADCINTERNATIONAL.NET
STATE OF FLORIDA
RAYMUNDO FEITO, R.A.
AR- 0010536
AA- CO01315
Architect • Seal/Signature
Construction Documents for:
\S-Qullr�11'14 P. AV
at:
ONE 7000 PLACE
SUITE: 545
5th FLOOR
7000 SW 62nd AVENUE
SOUTH MIAMI, FL 33143
Issue Date & Issue Description Drawn By Checked By
01 12/04/09
AC AR
PERMIT ISSUE
c�
Z
Z
a
w
U
a
IL
CO)
Z
0
N
w
O
O
w
Date & Delta Description Drawn By Checked By
I
Z
07 07 10
P &G P &G
t9
REVISION PER CLIENT REQUEST
Z
Z
Z
a
•
W
t—
V
w
H
a
Client Information
HEALTHCARE REALTY
2601 SW 37th AVENUE
SUITE 805
MIAMI, FL 33133
OFFICE: (305) 446 -3666
Project Number
09127
CAD File Name
ONE 7000 PLACE - SUITE 545 - DR.PEREZ
Description
MECHANICAL DETAILS
Scale
AS NOTED
■
♦ ^ Consultant . Seal/Signature
7P N00MME00ffwq�
U 21 SW 102 Ct. Miami, Fl. 33
Office: (786) 863 -7091
z Fax: (305) 220 -5196
Qpgengineerdesign@bellsouth.net
U
M=3mO
W STATE OF FLORIDA
ERGUIN CAPOTE P.E. No. 62487
LUIS O. PEREZ, PE P.E. No. 62586