10-649-016GENERAL H.V.A.C. NOTES 1. 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 2. 2.1 2.2 2.3 2.4 2.5 2.6 3. 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4. 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 5. 5.1 5.2 5.3 5.4 5.5 5.6 5.7 6. 6.1 6.2 7. 7.1 7.2 r1J*0IH1q1x11fIV U4 GENERAL ALL WORK TO BE PERFORMED UNDER THESE DOCUMENTS SHALL CONFORM WITH THE FLORIDA BUILDING CODE, AS WELL AS ALL OTHER APPLICABLE STATE AND LOCAL REGULATIONS AND ORDINANCES. ALL WORK SHALL BE PERFORMED BY A LICENSED AND INSURED MECHANICAL CONTRACTOR, IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE AFTER COMPLETION OF WORK. MECHANICAL CONTRACTOR SHALL FURNISH TO THE OWNER WRITTEN WARRANTEE THAT THE INSTALLED SYSTEM SHALL BE FREE OF MATERIALS AND WORKMANSHIP DEFECTS FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING HIS OWN PERMIT AND PAYING ALL PERMIT AND INSPECTION FEES. SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH PURCHASE OR INSTALLA11ON OF THE EQUIPMENT AND MATERIALS. THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO SHOW AS -BUILT CONDITIONS AT THE COMPLETION OF CONSTRUCTION. INTERRUPTION OF EXISTING FACILITIES AND / OR SERVICES SHALL BE KEPT TO A MINIMUM. THE CONTRACTOR SHALL FURNISH ALL MATERIALS REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICES, COORDINATE ALL INTERRUPTIONS WITH OWNER. PRECAU11ONS SHALL BE TAKEN TO PREVENT CONTAMINATION OF OWNER EQUIPMENT, FURNITURE AND CARPETING WITHIN THIS BUILDING. COVER AND WRAP EQUIPMENT, FURNITURE AND CARPETING AS NECESSARY. DUST AND DEBRIS SHALL BE STRICTLY CONTROLLED. CLOSE COORDINATION WITH OWNER WILL BE REQUIRED. DURING CONSTRUCTION CONTRACTOR SHALL FOLLOW THE "SMACNA" LATEST EDITION "INDOOR AIR QUALITY GUIDELINES FOR OCCUPIED BUILDINGS UNDER CONSTRUCTION ". ALL BUILDING CONSTRUCTION AFFECTED BY THE REMOVAL, RELOCATION OR INSTALLATION OF ANY PIECE OF EQUIPMENT SHALL BE REPAIRED AND FINISHED AS REQUIRED TO MATCH EXISTING CONDITIONS, OR AS DIRECTED BY THE ARCHITECTURAL DRAWINGS AND/ OR SPECIFICATIONS. IF ANY CONFLICT IS ENCOUNTERED WITHIN THE DESIGN DOCUMENTS, REGARDLESS OF TRADE OR RESPONSIBILITY, THE GREATER SCOPE OF WORK SHALL PREVAIL. FIELD VERIFICATION ALL WORK SHALL BE FIELD VERIFIED AND COORDINATED BEFORE INSTALLATION WITH ALL OTHER TRADES. WHERE INTERFERENCES OCCUR AND DEPARTURES FROM INDICATED DESIGN WILL BE REQUIRED TO DETERMINE CHANGES ON LOCATIONS, SIZES AND ELEVATIONS OF PIPING, DUCTWORK, ETC. THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR THE CHANGE ACCOMPANIED BY A DETAILED DRAWING FOR APPROVAL FROM ARCHITECT/ ENGINEER PRIOR TO PROCEEDING WITH ANY CHANGE OR DEPARTURES FROM EXISTING CONTRACT. COORDINATE LOCATION OF DUCTWORK WITH OTHER TRADES, PARTICULARLY WHERE DUCTS RUN THROUGH STRUCTURAL ELEMENTS. PROVIDE ALL NECESSARY SLEEVES BEFORE CONCRETE IS POURED. CONTRACTOR SHALL VERIFY EXISTING DUCTWORK SIZES, IF APPLICABLE, WHICH CONNECT TO NE DUCTWORK BEFORE FABRICATION AND INSTALLATION. CONTRACTOR SHALL VERIFY EXISTING PIPING SIZES, IF APPLICABLE, WHICH CONNECT TO NEW PIPING BEFORE FABRICATION AND INSTALLATION. BEFORE CUTTING OR MAKING OPENINGS IN ANY BUILDING COMPONENT, CONTRACTOR SHALL VERIFY USING ANY REQUIRED MEANS THAT ITS LOAD BEARING CAPABILITY IS NOT COMPROMISED IN ANY MATTER. EXISTING SYSTEMS NOT USED. CONTRACTOR SHALL VERIFY THE COOLING AND HEATING CAPACITIES AND AIR SUPPLY VOLUMES OF ALL EXISTING HVAC SYSTEMS TO REMAIN. THE CONTRACTOR SHALL ADVISE THE ARCHITECT AND ENGINEER OF ANY DEVIATION FROM WHAT IS INDICATED ON PLANS, BEFORE PROCEEDING WITH WORK. NOT USED. CONTRACTOR SHALL INSPECT ALL EXISTING DUCTWORK TO BE REUSED AND MAKE ANY NECESSARY REPAIRS TO ENSURE AN AIRTIGHT SYSTEM. AIR LEAKAGE RATES SHALL BE IN CONFORMANCE WITH THE SMACNA'S STANDARDS. DUCTWORK INSULATION SHALL BE INSPECTED AND REPLACED IN AREAS WHERE THE INSULATION IS DETERIORATED, DAMAGED, OR NOT CONTINUOUS. ALL WORK AND MATERIALS SHALL BE IN CONFORMANCE WITH THE CONTRACT DOCUMENTS. INSPECT AND REPAIR IF REQUIRED DUCT SUPPORTS TO ENSURE SECURE MOUNTING OF THE DUCT SYSTEM. CONTRACTOR SHALL ADVISE THE OWNER OF THE GENERAL CONDITIONS OF THE EXISTING SYSTEMS TO REMAIN. NOT USED. ANY EQUIPMENT OR DEVICES TO REMAIN THAT MIGHT HAVE TO BE DISCONNECTED BECAUSE OF THE REMOVAL OF ANY OTHER DEVICE MUST BE RECONNECTED AND TIED BACK TO THE EXISTING BUILDING SYSTEMS AND TESTED FOR CORRECT OPERATION. NEW EQUIPMENT NOT USED. MECHANICAL EQUIPMENT SHALL BE SUPPORTED PER MANUFACTURER RECOMMENDATIONS AND AS REQUIRED FOR APPLICABLE CODES AND STANDARDS, USING INDUSTRY STANDARD PRACTICES. STRUCTURAL ENGINEER DESIGN AND RECOMMENDATIONS SHALL BE FOLLOWED. SUBMIT SHOP DRAWINGS OF ALL SUPPORTING STRUCTURES THAT CLEARLY INDICATE SIZES, MATERIAL, DESIGN AND PRODUCT APPROVAL NUMBERS. VIBRATION ISOLATORS SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT WITH MOVING AND /OR ROTARY PARTS. SUBMIT SHOP DRAWINGS SHOWING, BUT NOT LIMITED, ISOLATION PERFORMANCE AND ALLOWABLE SUPPORTING LOADS. FOR ALL OUTDOOR MOUNTED EQUIPMENT PROVIDE SURFACE AND COIL PROTECTION AGAINST CORROSION DUE TO PROXIMITY TO MARINE AND /OR CORROSIVE ENVIRONMENT. CONTROL WIRING SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. THE CONTRACTOR SHALL FURNISH ALL MOTORS, STARTERS AND RELAYS, ETC., TO CONFORM A FULLY OPERATING SYSTEM. COORDINATE WITH THE ELECTRICAL DIVISION ALL WORK RELATED TO THE MECHANICAL SYSTEMS. NOT USED. NOT USED. NOT USED. PROVIDE EQUIPMENT MAINTENANCE AND INSTRUCTION MANUALS. THE MANUAL SHALL ESTABLISH ALL REQUIRED SCHEDULED MAINTENANCE THAT SHALL BE PERFORMED DURING THE LIFE OF THE BUILDING TO GUARANTEE THE WORKING CONDITION OF THE INSTALLED SYSTEM AND THE MAINTENANCE OF A PROPER I.A.Q. IN THE BUILDING. MANUALS SHALL BE SUBMITTED TO THE ENGINEER FOR ACCEPTANCE. EQUIPMENT DATA SHOWN IN THE EQUIPMENT SCHEDULES IS BASED ON MANUFACTURER'S ACTUAL CATALOG. VERIFY THIS INFORMATION WITH MANUFACTURERS PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT. MANUFACTURER'S NAMES SHALL BE INTERPRETED AS ESTABLISHMENT OF REQUIRED TYPE CLASS AND QUALITY. ALL SUBSTITUTIONS SHALL BE APPROVED BY THE PROJECT ENGINEER. PROVIDE ALL NECESSARY INSTRUCTIONS TO THE OWNER IN THE OPERATION OF THE MECHANICAL SYSTEM. SEE EQUIPMENT SCHEDULES ON DRAWINGS FOR INFORMATION ON ALL SPECIFIED EQUIPMENT FOR THIS JOB. DUCTWORK PROVIDE ALL NECESSARY ACCESS PANELS TO CONTROL VALVES, DAMPERS, SENSORS, AND ANY OTHER DEVICES NON- ACCESSIBLE OTHERWISE. ALL SIZES SHOWN FOR LINED AND UNLINED DUCTS ARE CLEAR INSIDE DUCT DIMENSIONS. CONDITIONED AIR DUCTWORK SHALL BE CLASS "ONE" FIBER GLASS DUCT BOARD IN ACCORDANCE WITH SMACNA'S FIBROUS DUCTS STANDARDS, Unless specified otherwise on the Mechanical Floor Plans. INSULATION SHALL HAVE THE REQUIRED DENSITY AND THICKNESS TO PROVIDE A MINIMUM INSULATION VALUE OF R -6 FRO SUPPLY DUCTWORK RUNNING THROUGH UNCONDITIONED SPACE AND R -4.2 FOR DUCTWORK RUNNING THROUGH CONDITIONED SPACE. PROVIDE VOLUME DAMPERS, TURNING VANES, ETC., IN DUCTWORK FOR PROPER AIR FLOW AND BALANCE. PROVIDE MULTIPLE VANE EXTRACTORS OR SPUTTERS WITH CONTROL RODS AT ALL OUTLETS CONNECTED CLOSER THAN TWO DUCT DIAMETERS TO MAIN SUPPLY DUCT AND WHERE SHOWN. NOT USED. NOT USED. NOT USED. TEST AND BALANCING BALANCE ALL SYSTEMS TO PROVIDE FLOW QUANTITIES AND CAPACITIES AS INDICATED ON DRAWINGS. PERFORM A COMPLETE OPERATING AND BALANCING TEST OF THE FINISHED SYSTEM. PROVIDE WRITTEN REPORT OF THE RESULT OF THIS TEST STATING THE ACCEPTABILITY OF THE SYSTEM AND COMPLIANCE WITH THE DESIGN DOCUMENTS. TEST AND BALANCE AGENCY SHALL BE AN INDEPENDENT, AABC OR NEBB CERTIFIED AGENCY, AND SHALL BE RETAINED BY THE OWNER. CONTRACTOR SHALL COORDINATE WITH OWNER AND TESTING AND COMMISSIONING AGENCY ALL WORK FOR FINAL CERTIFICATION OF THE HVAC SYSTEM. OTHER ALL WORK SHALL BE COORDINATED WITH OWNER /TENANT. THE CONTRACTOR SHALL PROTECT ALL EXISTING SYSTEMS /DEVICES WHILE PERFORMING THE SCOPE OF WORK. SHOULD ANY EXISTING SYSTEMS NEED TO BE MODIFIED DUE TO UNFORESEEN CONDITIONS, THE CONTRACTOR SHALL PRIOR MAKING ANY DETERMINATION INFORM THE HVAC LEGEND SYMBOL DESCRIPTION A.H.U. AIR HANDLER UNIT ER EXISTING TO BE RELOCATED N NEW BDD BACK DRAFT DAMPER 0/A OUTSIDE AIR CFM CUBIC FEET PER MINUTE E.F. EXHAUST FAN E.R. EXISTING TO REMAIN R/A RETURN AIR RG RETURN GRILLE S/A SUPPLY AIR SR SIDEWALL REGISTER TG TRANSFER GRILLE MVD MANUAL VOLUME DAMPER COND. CONDENSATE ® THERMOSTAT, PROGRAMABLE (k) ® AIR DISTRIBUTION SEE PLAN SP* SPRINKLER HEAD (DOWNWARD) ® SUPPLY DUCT SECTION m EXHAUST, RETURN, OR OUTSIDE AIR p{� MANUAL VOLUME DAMPER uvo MVD AT TAKE OFF FIRE DAMPER SUPPLY AIR DUCT RECTANGULAR DUALL DUCT ACCESSORIES SHALL HAVE TURNING VANES ALTHOUGH NOT SHOWN FLEXIBLE ROUND DUCT FLEXIBLE ROUND DUCT DOWN TO GRILLE ? DUCT MOUNTED SMOKE DETECTOR TO GRILLE REMOTE TEST STATION/ AUDIBLE ALARM CEILING SUPPLY DIFFUSER ® LINEAR SUPPLY DIFFUSER AIM CEILING RETURN DIFFUSER STANDARD BRANCH SUPPLY OR RETURN, NO SPUTTER (45• TAP) WITH MVD AT TAKE OFF POINT OF CHANGE IN DUCT CONSTRUCTION STATIC PRESSURE CLASS. RETURN AIR (R /A) GRILLE. SIDEWALL, CEILING GRILLE /REGISTER. _U_ ONE INCH (1 ") DOOR UNDERCUT. EXHAUST FAN (CEILING MOUNTED), Xl}� OUTSIDE AIR INTAKE WALL CAP. ,�A' LLII��JJ �� WALL MOUNTED EXHAUST FAN (PROPELLER / CENTRIFUGAL). WALL MOUNTED LOUVER. CONNECT TO EXISTING NOTE NOT ALL SYMBOLS MAY BE USED HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR ** NOMINAL MAXIMUM FIRE DAMPER(S) 0 SMOKE DAMPER(S) TRANE VCE06 FIRE RATED ENCLOSURE �* 277/1/60 FIRE RATED ROOF /FLOOR STATE OF FLORIDA NOTES: FIRE STOPPING AS SPECIFIED IN THE PROJECT SPECIFICATIONS. 2. UNITS SHALL HAVE ELECTRONIC (DDC), PROPORTIONAL CONTROLS. SMOKE CONTROL 4. SUPPORT UNITS FROM STRUCTURE ABOVE. 5. UNITS SHALL HAVE ACCESS PANELS FOR DAMPER ACTUATORS. * * EXISTING VARIABLE AIR VOLUME BOX SCHEDULE i SYMBOLS MANUFACTURER MODEL No. UNIT SIZE NOMINAL MAXIMUM ELECTRICAL HEATER (Kw) O TRANE VCE06 6 500 277/1/60 3.0';!. STATE OF FLORIDA NOTES: 1. ALL UNITS SHALL BE PROVIDE WITH A FACTORY INSTALLED DDC CONTROL AS SPECIFIED IN THE PROJECT SPECIFICATIONS. 2. UNITS SHALL HAVE ELECTRONIC (DDC), PROPORTIONAL CONTROLS. 3. UNITS SHALL BE CONTROLLED IN RESPONSE TO ROOM TEMPERATURE SENSORS AND CO2 SENSOR WHERE REQUIRED. 4. SUPPORT UNITS FROM STRUCTURE ABOVE. 5. UNITS SHALL HAVE ACCESS PANELS FOR DAMPER ACTUATORS. 6. ALL DIFFUSER RUNOUTS SHALL BE EQUIPPED WITH A MANUAL BALANCING DAMPER. 7. CONTROL UNITS SHALL BE PROVIDED COMPLETE WITH A 208/24 VOLT AC TRANSFORMER AND A FUSED DISCONNECT SWITCH. DISCONNECT SWITCHES SHALL BE PROVIDED FOR CONTROL POWER AND FOR HEATER POWER. PROVIDE POWER LINE FUSES TO MATCH LOAD. j 8. CONTRACTOR SHALL PROVIDE ALL REQUIRED FITTINGS TO CONNECT BOXES TO DUCTWORK SIZED AS PER MANUFACTURER RECOMENDATIONS. 9. ALL NEW UNITS SHALL BE CONNECTED TO EXISTING BUILDING CONTROLS. 151 SEVILLA AVENUE, SUITE 200 CORAL GABLES, FL 33134 OFFICE: (305) 442 -1188 FAX: (305) 445 -1509 WWW. ADCINTERNATIONAL.NET Issue Date & Issue Description Drawn By Checked By 01 12/04/09 AC AR y, STATE OF FLORIDA AR 0010536 RAYMUNDO FEITO, R.A. _ _.0001315 Architect • Seal /Signature Construction Documents for: a �� t: ONE 7000 PLACE SUITE: 545 5th FLOOR 7000 SW 62nd AVENUE SOUTH MIAMI, FL 33143 Issue Date & Issue Description Drawn By Checked By 01 12/04/09 AC AR PERMIT ISSUE (� Date & Delta Description Drawn By Checked By 07/07.10 P &G P &G ! REVISION PER CLIENT REQUEST Fc-rient Information HEALTHCARE REALTY 2601 SW 37th AVENUE SUITE 805 MIAMI, FL 33133 OFFICE: (305) 446 -3666 Project Number 09127 CAD File Name ONE 7000 PLACE - SUITE 545 - DR.PEREZ Description MECHANICAL SCHEDULE, & NOTES Scale AS NOTED Consultant Seal/Signature �I 1 1 1 •.