10-649-015w? PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE FLOOR ASSEMBLY BASED ON UL SYSTEM #C —AJ -1001 X410 METAL PIPE OR CONDUIT CP -25 S/L CAULK 4 1/2" LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE (MIN.) DAMMING MATERIAL (FIBERGLASS INSULATION BACKER ROD OR MINERAL WOOL) STEEL SLEEVE (OPTIONAL) PENETRATION FIRESTOP FOR METAL PIPE /CONDUIT THROUGH GYP. WALLBOARD PARTITION. ASSEMBLY BASED ON UL SYSTEM #W —L -1001 INWA ONE OR TWO HOUR FIRE RATED GYPSUM WALLBOARD ASSEMBLY WOOD STUDS AT 16" O.C. OR METAL STUDS AT 24" O.C. MAX. CAULK MATERIAL FORCED INTO ANNULAR SPACE TO MAX EXTEND POSSIBLE AND VATH 1/4" DIAM. BEAD APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM WALL. 12" DIAM. OR SMALLER SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR SMALLER RIGID STEEL CONDUIT, 4" DIAM. OR SMALLER STEEL E.M.T. CONDUIT OR 1" DIAM. OR SMALLER FLEXIBLE STEEL CONDUIT. P -25 N/S CAULKING BY MINNESOTA MINING TO BE 3/16" OR LESS. SED ON PRODUCT PERFORMANCE 1479) FIRE TEST AND UL FIRE STOP PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE WALL ASSEMBLY BASED ON UL SYSTEM #C —AJ -1001 SECTION PENETRATING ITEM STEEL SLEEVE (OPTIONAL) POINT OF CONTACT 2 1/2" MAX. ELEVATION ANNULAR SPACE NOTES: 1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE CAST INTO CONCRETE WALL. SLEEVE TO BE FLUSH OR PROJECT 2" MAX FROM BOTH SURFACES OF WALL 2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS TYPE "L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM. OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH SPACE TO BE 0" (POINT OF CONTACT). 3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 4. USE 1/2- MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE IS 1" OR LESS. USE CP -25 N/S CAULK. 5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE IS i" OR MORE. USE CP -25 N/S CAULK. 6. INSTALL FILL MATERIAL (CAULK) FLUSH WITH AND ON BOTH SIDES OF WALL ASSEMBLY SURFACE. 7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER INSTALLATION. FIRE RATING BASED ON WET INSTALLATION DEPTH. B. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION, BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER BLANKET TIGHTLY PACKED ARE ACCEPTABLE. RECESS PACKING MATERIAL FROM WALL SURFACE AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF CAULK. 9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP SYSTEM #49. METAL PIPE OR CONDUIT CP -25 N/S CAULK DAMMING MATERIAL (FIBERGLASS INSULATION BACKER ROD OR MINERAL WOOL) STEEL SLEEVE (OPTIONAL) FIRE RATED SOLID CONCRETE OR CONCRETE BLOCK WALL PENETRATION FIRESTOP FOR 6" MAX. PVC PIPE THROUGH FIRE -RATED -CONC. FLT R ASSEMBLY BASED ON UL SYSTEM #C —AJ -2001 D e �Ll D D I D 4" DEEP STEEL COLLAR W/ 1 1/4" W X 2" L ANCHOR TABS OR FIELD FABRICATED 0.016" THICK (30 GAUGE) GALV. SHEET STEEL IN ACCORDANCE WITH INST. SHEET SUPPLIED BY WRAP SHEET MANUFACTURER USE MIN. 2 - 1/2" WIDE BY 0.028" THICK STAINLESS STEEL BAND CLAMPS WITH WORM GEAR TIGHTENING MECHANISM. LOCATE CLAMP NEAR MID OF EACH STRIP STACK - SECTION PENETRATION FIRESTOP DETAIL TYP. UL ASSEMBLY F —A 1021 FOR CAST IRON PENETRATION THRU CONCRETE SLAB SECTION ELEVATION 6" (152 MM) MAX. PVC PIPE FIRE RATED CONC. FLOOR 2 1/2" MIN. 1/4" ANNULAR SPACE FS -195 R/R WRAP STRIP 2 STACKS (NOM. 4" STACK HEIGHT) TIGHTLY WRAPPED TOP EDGES BUTTED AGAINST THE UNDERSIDE OF CONK. a o a a a Qo A 1/4' X 1 1/2" MIN. STEEL EXP. BOLTS W/ 1 1/4" DIAM. STEEL FENDER WASHERS AT EA. ANCHOR TAB CP -25 S/L OR CP -25 N/S CAULK AT OUTER PERIMETER ALUMINUM FOIL WRAP AROUND PIPE 2" MIN. MAT WRAP - 6' WIDE STRIP OF FLEXIBLE SHEET MATERIAL FACED ON ONE SIDE W/ ALUM. FOIL (FOIL FACE EXPOSED) OVERLAP 1/2" AT SEAM SECURE IN PLACE W/ WIRE TIES 4" O.C. ALTERNATE: USE NOM. 1" THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN. 3.5 PFC) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH FOIL - SCRIM— KRAFT. MIN. 6" LENGTH OF PIPE COVERING INSTALLED AROUND PIPE AT IT'S EGRESS FROM STEEL COLLAR ON UNDERSIDE OF FLOOR. SECURE COVERING TO PIPE WITH STEEL WIRE TIES 0 4" O.C. H611 �► 1. FLOOR OR WALL ASSEMBLY -MIN 4 -1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100- 150pcf) CONCRETE.MAX DIAM OF OPENING IS 10 -1/2 IN. 2. THROUGH — PENETRANT— ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERPHIERY OF OPENING OR SLEEVE SHALL BE MIN. OF 0 IN. (POINT CONTACT) TO MAX. 1 -7/8 IN. PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF PIPES, CONDUITS OR TUBING MAY BE USED: A. STEEL PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE, B. IRON PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SERVICE WIEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM. 8 IN. DIAM. (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE. C. CONDUIT- NOM. 6 IN. DIAM. (OR SMALLER) STEEL CONDUIT OR NOM. 4 IN. DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING. D. COPPER TUBING- NOM. 4 IN. DIAM. (OR SMALLER) TYPE M (OR HEAVIER) COPPER TUBING. E. COPP R PIPE- NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER COPPER PIPE. 3. FIRESTOP SYSTEM -THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE A. PACKING MATERIAL -MIN 3 -3/4 IN. THICKNESS OF MIN. 4 pcf MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM BOTTOM SURFACE OF FLOOR AS REQUIRED TO ACCOMODATE THE REQUIRED THICKENESS OF FILL MATERIAL- B. FILL.-VOID OR CAVITY MATERIALS - SEALANT -MIN. 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM SURFACE OR FLOOR. MIN. 1/4 IN. DIAM. BEAD OF CAULK APPLIED TO THE PENETRANT/ CONCRETE INTERFACE AT THE POINT CONTACT LOCATION ON THE BOTTOM SURFACE OF FLOOR. 151 SEVILLA AVENUE, SUITE 200 CORAL GABLES, FL 33134 1. FLOOR OR WALL ASSEMBLY -MIN 4 -1/2 IN. (114mm) THICK LIGHTWEIGHT OR NORMAL WEIGHT (10D -150 pcf OR 1600 -2400 kg /m3) CONCRETE WALL MAY ALSO BE CONSTRUCTED OF ANY UL CALSSIFIED CONCRETE OFFICE: (305)442 - 1188►0 BLOCKS. MAX DIAM. OF CIRCULAR THROUGH OPENING IS 32 -1/2 IN (826mm). SEE CONCRETE BLOCKS (CAZT) n CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS FAX: (305) 445 -15090 IA. STEEL SLEEVE- (OPTIONAL NOT SHOWN)-NOM. 12 IN. (305mm) DIAM. (OR SMALLER) SCHEDULE 40 (OR SECTION HEAVIER) STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL SLEEVE TO BE FLUSHED WITH OR WWW. ADCINTERNATIONAL.NET PROJECT MAX 2 IN. (51mm) FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL 2. THROUGH- PENETRANT -ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE 6RESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN. OF O IN. (Omm, POINT CONTACT) TO MAX 1 -3/8 IN. (35mm). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING PENETRATING ITEM ANNULAR TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED: SPACE A. STEEL PIPE -NOM. 30 IN. (762mm) DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE Al. IRON PIPE -NOM. 30 IN. (762mm) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. STEEL SLEEVE B. CONDUIT -NOM. 6 IN, (152mm) DIAM (OR SMALLER) RIGID STEEL CONDUIT. (OPTIONAL) C. CONDUIT -NOM. 4 M. (152mm) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING. 3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM. 1 IN. (25mm) THICKNESS OF TIGHTLY - PACKED STATE OF FLORIDA CERAMIC (ALUMINA SILICA) FIBER BLANKET, MINERAL WOO. BATT OR GLASS FIBER INSULATION MATERIAL 0010536 USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM RAYMUNDO FEITO, R.A. BOTH SURFACES OF SOLID OR CONCRETE BLOCK WALL AS REQUIRED TO ACCDMODATE THE REQUIRED CO01315 THICKNESS OF CAULK FILL MATERIAL (ITEM 4). AS AN ALTERNATE WHEN MAX PIPE SIZE IS 10 IN. (254mm) FArchitect • Seal/Signature DIAM. AND WHEN MAX ANNULAR SPACE IS 1 IN. (25mm), A MIN. 1 IN. (25mm) THICKNESS OF TIGHTLY - PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN 34 IIN (13mm) FROM BOTH SURFACE OF FLOOR OR FROM EITHER SIDE OF SOLO CONCRETE WALL POINT OF CONTACT 4. FILL, VOID OR CAVITY MATERIALS- CAULK - APPUED TO FILL THE ANNULAR SPACE TO THE MIN. THICKNESS SHOWN IN THE FOLLOWING TABLE. MAX PIPE MAX ANNULAR PACKING MTL MIN CAULK 2 1/2" MAX. DIAM_ IN. SPACE IN. TYPE (a) THKNS IN. 10(254) 1(25) BR,CF,GF,or MW x(13) (b) 10(254) 1(25) CF or MW YA13) (c) 30(762) 2- 1/2(64) BR,CF,GF,or MW 1(25) (b) (a)BR= POLYETHYLENE BACKER ROD. CF =CERAMIC FIBER BLANKET. GF =GLASS FIBER INSULATION. PLAN ()CAUL.KRI STALLLLEDBFL SHE WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL (c)CAULK INSTALLED FLUSH WITH BOTTOM SURFACE OF FLOOR OR ONE SURFACE OF SOLID (NON- CONORETE BLOCK) WALL 3MCOMPANY -TYPE CP 25WB+ or FB- 3000WT (NOTE -W RATING APPLIES ONLY WHEN FB -3000 WT IS USED.) •BEARING THE UL CLASSIFICATION MARK* PENETRATION FIRESTOP FOR METAL PIPE /CONDUIT THROUGH GYP. WALLBOARD PARTITION. ASSEMBLY BASED ON UL SYSTEM #W —L -1001 INWA ONE OR TWO HOUR FIRE RATED GYPSUM WALLBOARD ASSEMBLY WOOD STUDS AT 16" O.C. OR METAL STUDS AT 24" O.C. MAX. CAULK MATERIAL FORCED INTO ANNULAR SPACE TO MAX EXTEND POSSIBLE AND VATH 1/4" DIAM. BEAD APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM WALL. 12" DIAM. OR SMALLER SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR SMALLER RIGID STEEL CONDUIT, 4" DIAM. OR SMALLER STEEL E.M.T. CONDUIT OR 1" DIAM. OR SMALLER FLEXIBLE STEEL CONDUIT. P -25 N/S CAULKING BY MINNESOTA MINING TO BE 3/16" OR LESS. SED ON PRODUCT PERFORMANCE 1479) FIRE TEST AND UL FIRE STOP PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE WALL ASSEMBLY BASED ON UL SYSTEM #C —AJ -1001 SECTION PENETRATING ITEM STEEL SLEEVE (OPTIONAL) POINT OF CONTACT 2 1/2" MAX. ELEVATION ANNULAR SPACE NOTES: 1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE CAST INTO CONCRETE WALL. SLEEVE TO BE FLUSH OR PROJECT 2" MAX FROM BOTH SURFACES OF WALL 2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS TYPE "L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM. OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH SPACE TO BE 0" (POINT OF CONTACT). 3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 4. USE 1/2- MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE IS 1" OR LESS. USE CP -25 N/S CAULK. 5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE IS i" OR MORE. USE CP -25 N/S CAULK. 6. INSTALL FILL MATERIAL (CAULK) FLUSH WITH AND ON BOTH SIDES OF WALL ASSEMBLY SURFACE. 7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER INSTALLATION. FIRE RATING BASED ON WET INSTALLATION DEPTH. B. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION, BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER BLANKET TIGHTLY PACKED ARE ACCEPTABLE. RECESS PACKING MATERIAL FROM WALL SURFACE AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF CAULK. 9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP SYSTEM #49. METAL PIPE OR CONDUIT CP -25 N/S CAULK DAMMING MATERIAL (FIBERGLASS INSULATION BACKER ROD OR MINERAL WOOL) STEEL SLEEVE (OPTIONAL) FIRE RATED SOLID CONCRETE OR CONCRETE BLOCK WALL PENETRATION FIRESTOP FOR 6" MAX. PVC PIPE THROUGH FIRE -RATED -CONC. FLT R ASSEMBLY BASED ON UL SYSTEM #C —AJ -2001 D e �Ll D D I D 4" DEEP STEEL COLLAR W/ 1 1/4" W X 2" L ANCHOR TABS OR FIELD FABRICATED 0.016" THICK (30 GAUGE) GALV. SHEET STEEL IN ACCORDANCE WITH INST. SHEET SUPPLIED BY WRAP SHEET MANUFACTURER USE MIN. 2 - 1/2" WIDE BY 0.028" THICK STAINLESS STEEL BAND CLAMPS WITH WORM GEAR TIGHTENING MECHANISM. LOCATE CLAMP NEAR MID OF EACH STRIP STACK - SECTION PENETRATION FIRESTOP DETAIL TYP. UL ASSEMBLY F —A 1021 FOR CAST IRON PENETRATION THRU CONCRETE SLAB SECTION ELEVATION 6" (152 MM) MAX. PVC PIPE FIRE RATED CONC. FLOOR 2 1/2" MIN. 1/4" ANNULAR SPACE FS -195 R/R WRAP STRIP 2 STACKS (NOM. 4" STACK HEIGHT) TIGHTLY WRAPPED TOP EDGES BUTTED AGAINST THE UNDERSIDE OF CONK. a o a a a Qo A 1/4' X 1 1/2" MIN. STEEL EXP. BOLTS W/ 1 1/4" DIAM. STEEL FENDER WASHERS AT EA. ANCHOR TAB CP -25 S/L OR CP -25 N/S CAULK AT OUTER PERIMETER ALUMINUM FOIL WRAP AROUND PIPE 2" MIN. MAT WRAP - 6' WIDE STRIP OF FLEXIBLE SHEET MATERIAL FACED ON ONE SIDE W/ ALUM. FOIL (FOIL FACE EXPOSED) OVERLAP 1/2" AT SEAM SECURE IN PLACE W/ WIRE TIES 4" O.C. ALTERNATE: USE NOM. 1" THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN. 3.5 PFC) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH FOIL - SCRIM— KRAFT. MIN. 6" LENGTH OF PIPE COVERING INSTALLED AROUND PIPE AT IT'S EGRESS FROM STEEL COLLAR ON UNDERSIDE OF FLOOR. SECURE COVERING TO PIPE WITH STEEL WIRE TIES 0 4" O.C. H611 �► 1. FLOOR OR WALL ASSEMBLY -MIN 4 -1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100- 150pcf) CONCRETE.MAX DIAM OF OPENING IS 10 -1/2 IN. 2. THROUGH — PENETRANT— ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERPHIERY OF OPENING OR SLEEVE SHALL BE MIN. OF 0 IN. (POINT CONTACT) TO MAX. 1 -7/8 IN. PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF PIPES, CONDUITS OR TUBING MAY BE USED: A. STEEL PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE, B. IRON PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SERVICE WIEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM. 8 IN. DIAM. (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE. C. CONDUIT- NOM. 6 IN. DIAM. (OR SMALLER) STEEL CONDUIT OR NOM. 4 IN. DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING. D. COPPER TUBING- NOM. 4 IN. DIAM. (OR SMALLER) TYPE M (OR HEAVIER) COPPER TUBING. E. COPP R PIPE- NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER COPPER PIPE. 3. FIRESTOP SYSTEM -THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE A. PACKING MATERIAL -MIN 3 -3/4 IN. THICKNESS OF MIN. 4 pcf MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM BOTTOM SURFACE OF FLOOR AS REQUIRED TO ACCOMODATE THE REQUIRED THICKENESS OF FILL MATERIAL- B. FILL.-VOID OR CAVITY MATERIALS - SEALANT -MIN. 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM SURFACE OR FLOOR. MIN. 1/4 IN. DIAM. BEAD OF CAULK APPLIED TO THE PENETRANT/ CONCRETE INTERFACE AT THE POINT CONTACT LOCATION ON THE BOTTOM SURFACE OF FLOOR. 151 SEVILLA AVENUE, SUITE 200 CORAL GABLES, FL 33134 OFFICE: (305)442 - 1188►0 n FAX: (305) 445 -15090 WWW. ADCINTERNATIONAL.NET ji 4Fe y, f y4eq STATE OF FLORIDA ,_ AR- 0010536 RAYMUNDO FEITO, R.A. AA- CO01315 FArchitect • Seal/Signature Construction Documents for: SIM 9�5 - DIL at: ONE 7000 PLACE SUITE: 545 5th FLOOR 7000 SW 62nd AVENUE SOUTH MIAMI, FL 33143 Issue Date & Issue Description Drawn By Checked By 01 12 04 09 AC AR ­­­1_1 . _ . . ..... PERMIT.... I S 5 U E ............... ............................... ...... .................................................... ... Date & Delta Description Drawn By Checked By i i .._ ............................ ._........._........_._....._...._.....___.................................._............... ....._..._......._I- .._._. -. - -- .............. .1 Client Information HEALTHCARE REALTY 2601 SW 37th AVENUE SUITE 805 MIAMI, FL 33133 OFFICE: (305) 446 -3666 Project Number 09127 CAD File Name ONE 7000 PLACE - SUITE 545 - DR.PEREZ Description TYPICAL FIRE PENETRATION DETAILS Scale 1/2" =V -0" Consultant • Seal/Signature I' �