10-649-015w?
PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE FLOOR
ASSEMBLY BASED ON UL SYSTEM #C —AJ -1001
X410
METAL PIPE OR CONDUIT
CP -25 S/L CAULK
4 1/2" LIGHTWEIGHT OR NORMAL WEIGHT
CONCRETE (MIN.)
DAMMING MATERIAL (FIBERGLASS INSULATION
BACKER ROD OR MINERAL WOOL)
STEEL SLEEVE (OPTIONAL)
PENETRATION FIRESTOP FOR METAL PIPE /CONDUIT THROUGH GYP. WALLBOARD PARTITION.
ASSEMBLY BASED ON UL SYSTEM #W —L -1001
INWA
ONE OR TWO HOUR FIRE RATED
GYPSUM WALLBOARD ASSEMBLY
WOOD STUDS AT 16" O.C. OR
METAL STUDS AT 24" O.C. MAX.
CAULK MATERIAL FORCED INTO ANNULAR
SPACE TO MAX EXTEND POSSIBLE AND
VATH 1/4" DIAM. BEAD APPLIED TO
PERIMETER OF PIPE OR CONDUIT AT ITS
EGRESS FROM WALL.
12" DIAM. OR SMALLER SCHEDULE 10S
OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR SMALLER RIGID STEEL CONDUIT, 4"
DIAM. OR SMALLER STEEL E.M.T. CONDUIT
OR 1" DIAM. OR SMALLER FLEXIBLE STEEL
CONDUIT.
P -25 N/S CAULKING BY MINNESOTA MINING
TO BE 3/16" OR LESS.
SED ON PRODUCT PERFORMANCE
1479) FIRE TEST AND UL FIRE STOP
PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE WALL
ASSEMBLY BASED ON UL SYSTEM #C —AJ -1001
SECTION
PENETRATING ITEM
STEEL SLEEVE
(OPTIONAL)
POINT OF CONTACT
2 1/2" MAX.
ELEVATION
ANNULAR
SPACE
NOTES:
1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER
SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE
CAST INTO CONCRETE WALL. SLEEVE TO BE FLUSH
OR PROJECT 2" MAX FROM BOTH SURFACES OF WALL
2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS
SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS
TYPE "L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM.
OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
SPACE TO BE 0" (POINT OF CONTACT).
3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF WALL ASSEMBLY.
4. USE 1/2- MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE
IS 1" OR LESS. USE CP -25 N/S CAULK.
5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE
IS i" OR MORE. USE CP -25 N/S CAULK.
6. INSTALL FILL MATERIAL (CAULK) FLUSH WITH AND
ON BOTH SIDES OF WALL ASSEMBLY SURFACE.
7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER
INSTALLATION. FIRE RATING BASED ON WET INSTALLATION
DEPTH.
B. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION,
BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER
BLANKET TIGHTLY PACKED ARE ACCEPTABLE.
RECESS PACKING MATERIAL FROM WALL SURFACE
AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS
OF CAULK.
9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP
SYSTEM #49.
METAL PIPE OR CONDUIT
CP -25 N/S CAULK
DAMMING MATERIAL (FIBERGLASS INSULATION
BACKER ROD OR MINERAL WOOL)
STEEL SLEEVE (OPTIONAL)
FIRE RATED SOLID CONCRETE
OR CONCRETE BLOCK WALL
PENETRATION FIRESTOP FOR 6" MAX. PVC PIPE THROUGH FIRE -RATED -CONC. FLT R
ASSEMBLY BASED ON UL SYSTEM #C —AJ -2001
D e �Ll
D D I D
4" DEEP STEEL COLLAR
W/ 1 1/4" W X 2" L ANCHOR
TABS OR FIELD FABRICATED
0.016" THICK (30 GAUGE)
GALV. SHEET STEEL IN
ACCORDANCE WITH INST.
SHEET SUPPLIED BY
WRAP SHEET MANUFACTURER
USE MIN. 2 - 1/2" WIDE BY
0.028" THICK STAINLESS
STEEL BAND CLAMPS
WITH WORM GEAR
TIGHTENING MECHANISM.
LOCATE CLAMP NEAR
MID OF EACH STRIP STACK -
SECTION
PENETRATION FIRESTOP DETAIL TYP.
UL ASSEMBLY F —A 1021 FOR CAST IRON
PENETRATION THRU CONCRETE SLAB
SECTION
ELEVATION
6" (152 MM) MAX. PVC PIPE
FIRE RATED CONC. FLOOR 2 1/2" MIN.
1/4" ANNULAR SPACE
FS -195 R/R WRAP STRIP
2 STACKS (NOM. 4" STACK
HEIGHT) TIGHTLY WRAPPED
TOP EDGES BUTTED AGAINST
THE UNDERSIDE OF CONK.
a o a a
a Qo A
1/4' X 1 1/2" MIN. STEEL EXP. BOLTS
W/ 1 1/4" DIAM. STEEL FENDER
WASHERS AT EA. ANCHOR TAB
CP -25 S/L OR CP -25 N/S
CAULK AT OUTER PERIMETER
ALUMINUM FOIL WRAP AROUND PIPE
2" MIN.
MAT WRAP - 6' WIDE STRIP
OF FLEXIBLE SHEET MATERIAL
FACED ON ONE SIDE W/
ALUM. FOIL (FOIL FACE EXPOSED)
OVERLAP 1/2" AT SEAM
SECURE IN PLACE W/ WIRE
TIES 4" O.C.
ALTERNATE: USE NOM. 1"
THICK HOLLOW CYLINDRICAL
HEAVY DENSITY (MIN. 3.5 PFC)
GLASS FIBER UNITS JACKETED
ON THE OUTSIDE WITH FOIL -
SCRIM— KRAFT. MIN. 6" LENGTH
OF PIPE COVERING INSTALLED
AROUND PIPE AT IT'S EGRESS
FROM STEEL COLLAR ON
UNDERSIDE OF FLOOR. SECURE
COVERING TO PIPE WITH STEEL
WIRE TIES 0 4" O.C.
H611 �►
1. FLOOR OR WALL ASSEMBLY -MIN 4 -1/2 IN. THICK REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT (100- 150pcf) CONCRETE.MAX
DIAM OF OPENING IS 10 -1/2 IN.
2. THROUGH — PENETRANT— ONE METALLIC PIPE, CONDUIT OR
TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY
WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN
PIPE, CONDUIT OR TUBING AND PERPHIERY OF OPENING OR SLEEVE
SHALL BE MIN. OF 0 IN. (POINT CONTACT) TO MAX. 1 -7/8 IN. PIPE
CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SCHEDULE 10 (OR
HEAVIER) STEEL PIPE,
B. IRON PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SERVICE WIEIGHT (OR
HEAVIER) CAST IRON SOIL PIPE, NOM. 8 IN. DIAM. (OR SMALLER) OR
CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT- NOM. 6 IN. DIAM. (OR SMALLER) STEEL CONDUIT OR NOM.
4 IN. DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
D. COPPER TUBING- NOM. 4 IN. DIAM. (OR SMALLER) TYPE M (OR
HEAVIER) COPPER TUBING.
E. COPP R PIPE- NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR
HEAVIER COPPER PIPE.
3. FIRESTOP SYSTEM -THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE
A. PACKING MATERIAL -MIN 3 -3/4 IN. THICKNESS OF MIN. 4 pcf
MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A
PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM
BOTTOM SURFACE OF FLOOR AS REQUIRED TO ACCOMODATE THE
REQUIRED THICKENESS OF FILL MATERIAL-
B. FILL.-VOID OR CAVITY MATERIALS - SEALANT -MIN. 1/4 IN. THICKNESS
OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM
SURFACE OR FLOOR. MIN. 1/4 IN. DIAM. BEAD OF CAULK APPLIED TO
THE PENETRANT/ CONCRETE INTERFACE AT THE POINT CONTACT
LOCATION ON THE BOTTOM SURFACE OF FLOOR.
151 SEVILLA AVENUE, SUITE 200
CORAL GABLES, FL 33134
1. FLOOR OR WALL ASSEMBLY -MIN 4 -1/2 IN. (114mm) THICK LIGHTWEIGHT OR NORMAL WEIGHT (10D -150 pcf
OR 1600 -2400 kg /m3) CONCRETE WALL MAY ALSO BE CONSTRUCTED OF ANY UL CALSSIFIED CONCRETE
OFFICE: (305)442 - 1188►0
BLOCKS. MAX DIAM. OF CIRCULAR THROUGH OPENING IS 32 -1/2 IN (826mm). SEE CONCRETE BLOCKS (CAZT)
n
CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS
FAX: (305) 445 -15090
IA. STEEL SLEEVE- (OPTIONAL NOT SHOWN)-NOM. 12 IN. (305mm) DIAM. (OR SMALLER) SCHEDULE 40 (OR
SECTION
HEAVIER) STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL SLEEVE TO BE FLUSHED WITH OR
WWW. ADCINTERNATIONAL.NET
PROJECT MAX 2 IN. (51mm) FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL
2. THROUGH- PENETRANT -ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE 6RESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND
PERIPHERY OF OPENING SHALL BE MIN. OF O IN. (Omm, POINT CONTACT) TO MAX 1 -3/8 IN. (35mm).
PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING
PENETRATING ITEM
ANNULAR TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
SPACE A. STEEL PIPE -NOM. 30 IN. (762mm) DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE
Al. IRON PIPE -NOM. 30 IN. (762mm) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
STEEL SLEEVE
B. CONDUIT -NOM. 6 IN, (152mm) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
(OPTIONAL)
C. CONDUIT -NOM. 4 M. (152mm) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM. 1 IN. (25mm) THICKNESS OF TIGHTLY - PACKED
STATE OF FLORIDA
CERAMIC (ALUMINA SILICA) FIBER BLANKET, MINERAL WOO. BATT OR GLASS FIBER INSULATION MATERIAL
0010536
USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM
RAYMUNDO FEITO, R.A.
BOTH SURFACES OF SOLID OR CONCRETE BLOCK WALL AS REQUIRED TO ACCDMODATE THE REQUIRED
CO01315
THICKNESS OF CAULK FILL MATERIAL (ITEM 4). AS AN ALTERNATE WHEN MAX PIPE SIZE IS 10 IN. (254mm)
FArchitect • Seal/Signature
DIAM. AND WHEN MAX ANNULAR SPACE IS 1 IN. (25mm), A MIN. 1 IN. (25mm) THICKNESS OF TIGHTLY -
PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN 34 IIN
(13mm) FROM BOTH SURFACE OF FLOOR OR FROM EITHER SIDE OF SOLO CONCRETE WALL
POINT OF CONTACT
4. FILL, VOID OR CAVITY MATERIALS- CAULK - APPUED TO FILL THE ANNULAR SPACE TO THE MIN. THICKNESS
SHOWN IN THE FOLLOWING TABLE.
MAX PIPE MAX ANNULAR PACKING MTL MIN CAULK
2 1/2" MAX.
DIAM_ IN. SPACE IN. TYPE (a) THKNS IN.
10(254) 1(25) BR,CF,GF,or MW x(13) (b)
10(254) 1(25) CF or MW YA13) (c)
30(762) 2- 1/2(64) BR,CF,GF,or MW 1(25) (b)
(a)BR= POLYETHYLENE BACKER ROD.
CF =CERAMIC FIBER BLANKET.
GF =GLASS FIBER INSULATION.
PLAN
()CAUL.KRI STALLLLEDBFL SHE WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL
(c)CAULK INSTALLED FLUSH WITH BOTTOM SURFACE OF FLOOR OR ONE SURFACE OF SOLID
(NON- CONORETE BLOCK) WALL
3MCOMPANY -TYPE CP 25WB+ or FB- 3000WT
(NOTE -W RATING APPLIES ONLY WHEN FB -3000 WT IS USED.)
•BEARING THE UL CLASSIFICATION MARK*
PENETRATION FIRESTOP FOR METAL PIPE /CONDUIT THROUGH GYP. WALLBOARD PARTITION.
ASSEMBLY BASED ON UL SYSTEM #W —L -1001
INWA
ONE OR TWO HOUR FIRE RATED
GYPSUM WALLBOARD ASSEMBLY
WOOD STUDS AT 16" O.C. OR
METAL STUDS AT 24" O.C. MAX.
CAULK MATERIAL FORCED INTO ANNULAR
SPACE TO MAX EXTEND POSSIBLE AND
VATH 1/4" DIAM. BEAD APPLIED TO
PERIMETER OF PIPE OR CONDUIT AT ITS
EGRESS FROM WALL.
12" DIAM. OR SMALLER SCHEDULE 10S
OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR SMALLER RIGID STEEL CONDUIT, 4"
DIAM. OR SMALLER STEEL E.M.T. CONDUIT
OR 1" DIAM. OR SMALLER FLEXIBLE STEEL
CONDUIT.
P -25 N/S CAULKING BY MINNESOTA MINING
TO BE 3/16" OR LESS.
SED ON PRODUCT PERFORMANCE
1479) FIRE TEST AND UL FIRE STOP
PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE WALL
ASSEMBLY BASED ON UL SYSTEM #C —AJ -1001
SECTION
PENETRATING ITEM
STEEL SLEEVE
(OPTIONAL)
POINT OF CONTACT
2 1/2" MAX.
ELEVATION
ANNULAR
SPACE
NOTES:
1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER
SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE
CAST INTO CONCRETE WALL. SLEEVE TO BE FLUSH
OR PROJECT 2" MAX FROM BOTH SURFACES OF WALL
2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS
SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS
TYPE "L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM.
OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
SPACE TO BE 0" (POINT OF CONTACT).
3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF WALL ASSEMBLY.
4. USE 1/2- MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE
IS 1" OR LESS. USE CP -25 N/S CAULK.
5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE
IS i" OR MORE. USE CP -25 N/S CAULK.
6. INSTALL FILL MATERIAL (CAULK) FLUSH WITH AND
ON BOTH SIDES OF WALL ASSEMBLY SURFACE.
7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER
INSTALLATION. FIRE RATING BASED ON WET INSTALLATION
DEPTH.
B. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION,
BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER
BLANKET TIGHTLY PACKED ARE ACCEPTABLE.
RECESS PACKING MATERIAL FROM WALL SURFACE
AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS
OF CAULK.
9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP
SYSTEM #49.
METAL PIPE OR CONDUIT
CP -25 N/S CAULK
DAMMING MATERIAL (FIBERGLASS INSULATION
BACKER ROD OR MINERAL WOOL)
STEEL SLEEVE (OPTIONAL)
FIRE RATED SOLID CONCRETE
OR CONCRETE BLOCK WALL
PENETRATION FIRESTOP FOR 6" MAX. PVC PIPE THROUGH FIRE -RATED -CONC. FLT R
ASSEMBLY BASED ON UL SYSTEM #C —AJ -2001
D e �Ll
D D I D
4" DEEP STEEL COLLAR
W/ 1 1/4" W X 2" L ANCHOR
TABS OR FIELD FABRICATED
0.016" THICK (30 GAUGE)
GALV. SHEET STEEL IN
ACCORDANCE WITH INST.
SHEET SUPPLIED BY
WRAP SHEET MANUFACTURER
USE MIN. 2 - 1/2" WIDE BY
0.028" THICK STAINLESS
STEEL BAND CLAMPS
WITH WORM GEAR
TIGHTENING MECHANISM.
LOCATE CLAMP NEAR
MID OF EACH STRIP STACK -
SECTION
PENETRATION FIRESTOP DETAIL TYP.
UL ASSEMBLY F —A 1021 FOR CAST IRON
PENETRATION THRU CONCRETE SLAB
SECTION
ELEVATION
6" (152 MM) MAX. PVC PIPE
FIRE RATED CONC. FLOOR 2 1/2" MIN.
1/4" ANNULAR SPACE
FS -195 R/R WRAP STRIP
2 STACKS (NOM. 4" STACK
HEIGHT) TIGHTLY WRAPPED
TOP EDGES BUTTED AGAINST
THE UNDERSIDE OF CONK.
a o a a
a Qo A
1/4' X 1 1/2" MIN. STEEL EXP. BOLTS
W/ 1 1/4" DIAM. STEEL FENDER
WASHERS AT EA. ANCHOR TAB
CP -25 S/L OR CP -25 N/S
CAULK AT OUTER PERIMETER
ALUMINUM FOIL WRAP AROUND PIPE
2" MIN.
MAT WRAP - 6' WIDE STRIP
OF FLEXIBLE SHEET MATERIAL
FACED ON ONE SIDE W/
ALUM. FOIL (FOIL FACE EXPOSED)
OVERLAP 1/2" AT SEAM
SECURE IN PLACE W/ WIRE
TIES 4" O.C.
ALTERNATE: USE NOM. 1"
THICK HOLLOW CYLINDRICAL
HEAVY DENSITY (MIN. 3.5 PFC)
GLASS FIBER UNITS JACKETED
ON THE OUTSIDE WITH FOIL -
SCRIM— KRAFT. MIN. 6" LENGTH
OF PIPE COVERING INSTALLED
AROUND PIPE AT IT'S EGRESS
FROM STEEL COLLAR ON
UNDERSIDE OF FLOOR. SECURE
COVERING TO PIPE WITH STEEL
WIRE TIES 0 4" O.C.
H611 �►
1. FLOOR OR WALL ASSEMBLY -MIN 4 -1/2 IN. THICK REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT (100- 150pcf) CONCRETE.MAX
DIAM OF OPENING IS 10 -1/2 IN.
2. THROUGH — PENETRANT— ONE METALLIC PIPE, CONDUIT OR
TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY
WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN
PIPE, CONDUIT OR TUBING AND PERPHIERY OF OPENING OR SLEEVE
SHALL BE MIN. OF 0 IN. (POINT CONTACT) TO MAX. 1 -7/8 IN. PIPE
CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SCHEDULE 10 (OR
HEAVIER) STEEL PIPE,
B. IRON PIPE- NOM. 8 IN. DIAM. (OR SMALLER) SERVICE WIEIGHT (OR
HEAVIER) CAST IRON SOIL PIPE, NOM. 8 IN. DIAM. (OR SMALLER) OR
CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT- NOM. 6 IN. DIAM. (OR SMALLER) STEEL CONDUIT OR NOM.
4 IN. DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
D. COPPER TUBING- NOM. 4 IN. DIAM. (OR SMALLER) TYPE M (OR
HEAVIER) COPPER TUBING.
E. COPP R PIPE- NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR
HEAVIER COPPER PIPE.
3. FIRESTOP SYSTEM -THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE
A. PACKING MATERIAL -MIN 3 -3/4 IN. THICKNESS OF MIN. 4 pcf
MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A
PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM
BOTTOM SURFACE OF FLOOR AS REQUIRED TO ACCOMODATE THE
REQUIRED THICKENESS OF FILL MATERIAL-
B. FILL.-VOID OR CAVITY MATERIALS - SEALANT -MIN. 1/4 IN. THICKNESS
OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM
SURFACE OR FLOOR. MIN. 1/4 IN. DIAM. BEAD OF CAULK APPLIED TO
THE PENETRANT/ CONCRETE INTERFACE AT THE POINT CONTACT
LOCATION ON THE BOTTOM SURFACE OF FLOOR.
151 SEVILLA AVENUE, SUITE 200
CORAL GABLES, FL 33134
OFFICE: (305)442 - 1188►0
n
FAX: (305) 445 -15090
WWW. ADCINTERNATIONAL.NET
ji
4Fe
y, f
y4eq
STATE OF FLORIDA
,_ AR-
0010536
RAYMUNDO FEITO, R.A.
AA-
CO01315
FArchitect • Seal/Signature
Construction Documents for:
SIM 9�5 - DIL
at:
ONE 7000 PLACE
SUITE: 545
5th FLOOR
7000 SW 62nd AVENUE
SOUTH MIAMI, FL 33143
Issue Date & Issue Description Drawn By Checked By
01 12 04 09 AC AR
1_1 . _ . . ..... PERMIT.... I S 5 U E ............... ............................... ...... ....................................................
...
Date & Delta Description Drawn By Checked By
i
i
.._ ............................ ._........._........_._....._...._.....___.................................._............... ....._..._......._I- .._._. -. - -- ..............
.1
Client Information
HEALTHCARE REALTY
2601 SW 37th AVENUE
SUITE 805
MIAMI, FL 33133
OFFICE: (305) 446 -3666
Project Number
09127
CAD File Name
ONE 7000 PLACE - SUITE 545 - DR.PEREZ
Description
TYPICAL FIRE PENETRATION DETAILS
Scale
1/2" =V -0"
Consultant • Seal/Signature
I' �