10-323-019System No. C -AJ -2419
F Rating - 3 Hr
T Rating - 0 Hr
1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete floor or min
5 in. thick reinforced lightweight or normal weight 100 -150 concrete wall. Wall m also be constructed of a UL
9 ( P� may any
Classed Concrete Blocks*. Max diam of opening shall be 6 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants -- One nonmetallic penetrant centered within the firestop system. The annular space between pipe and
periphery of opening shall be nom 3/4 in. Pipe to be rigidly supported on both sides of the floor assembly. The following
types and saes of non - metallic pipe may be used:
A Polyvinyl Chloride (PVC) Pipe -- Nom 4 in. dam (or smaller) Schedule 40 solid core or cellular core PVC pipe for
use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) pipe - Nom 4 in. diam (or smaller) SDR 13.5 CPVC pipe for use in closed
(process or supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe -- Nom 4 in. diam (or smaller) Schedule 40 solid core or cellular core
ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
3. Firestop System -- The details of the firestop system shall be as follows:
A. Fill, Void or Cavity Material* - Wrap Strip -- Nom 3/16 in. thick by 1 -3/4 in. wide intumescent wrap strip. The
wrap strip is continuously wrapped around the outer circumference of the pipe covering two times and slid into the
annular space. When multiple wrap strips are used to achieve the required total length, the ends are to be butted
end to end and held in place with tape. The bottom edge of the wrap strip shall be recessed 1/2 in. from the
bottom surface of the concrete floor. In walls, the wrap shall be installed on both surfaces of the wall such that
the exposed edge of the wrap strip is recessed 1/2 in. from each side of the wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 648 -E- W45/1 -3/4' Wrap Strip
B. FIT, Void or Cavity Materials* - Sealant -- Min 1/2 in. thickness of fill material applied within the annulus, flush
with bottom surface of floor or both surfaces of wall.
HILT] CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS ONE Sealant
*Bearing the UL Classification Mark
P � ®m Reproduced by HILTI, Inc Courtesy of V�'SS lF�ec�
Underwriters Laboratories, Inc. �?
FIRESTOP SYSTEMS Apn127, 2005 C m US
r
System No. C -AJ -2271 r
F Rating - 2 Hr
T Rating -1 Hr
A W Rating - Class 1(See Item 3)
1. Floor or Wall Assembly - Min 2 -1/2 in. (64 mm) thick reinforced lightweight or normal weight (100 -150 pd or 1600 -2400 kgtm3) concrete. Wall
may also be constructed of any UL Classified Concrete Blocks'. Max diam of opening is 7 in. (178 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants - One nonmetallic pipe or conduit to be installed concentrically or eccentrically within the firestop system. Annular space
between pipe or conduit and edge of opening to be min 0 in. (0 mm, point contact) and max 1/2 in. (13 mm). Pipe or conduit to be rigidly
supported on both sides of floor - ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used:
A Polyvinyl Chloride (PVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in dosed (process
or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) SDR13.5 CPVC pipe for use in dosed (process or
supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core ABS pipe for use in
dosed (process or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or
supply) or vented (drain, waste or vent) piping systems.
3. Fill, Void or Cavity Materials* - Sealant- Required for systems with W Rating, but otherwise optional. Min 1/2 in. (13 mm) thickness of fill
material applied within the annulus, flush with top or bottom surface of floor. W Rating applies only when CP601 S or CP 604 Sealant is used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC- FS-ONE Sealant, CP 601S Sealant or CP 604 Sealant
3A Packing Material (not shown) - Min 1/2 in. (13 mm) thickness of 4 pcf (64 kglm3) mineral wool batt insulation firmly packed into annular space
and recessed from the top surface of floor to accommodate the required thickness of fill material. Required only when CP 604 Sealant is used.
4. Firestop Device*- Firestop Collar- Firestop collar shall be installed in accordance with the accompanying installation instructions. Collar to be
installed and latched around the pipe and secured to underside of floor or both sides of wall using anchor hooks provided with the collar. Minimum
two anchor hooks required for non 1 -1/2 and 2 in. (38 and 51 mm) diam pipes. Minimum three anchor hooks required for nom 3 and 4 in. (76 and
102 mm) diam pipes. Minimum four anchor hooks required for 6 in. (152 mm) diam pipes. The anchor hooks are to be secured with min 114 in. (6
mm) diam by min 1 -1/4 in. (32 mm) long steel expansion bolts or min 0.145 in. (3.7 mm) diam by 1 -1/4 in. (32 mm) long powder actuated
fasteners utilizing a 1 -7/16 in. (37 mm) diam by 1/16 in. (1.6 mm) thick steel washer. As alternates to the anchors specified above, Hilt! 1/4 in. (6
mm) diam by 1 -1/4 in. (32 mm) long KWIK -CON II+ concrete screw anchor, Hilt 1/4 in. (6 mm) diam by 1 -3/4 in. (45 mm) long KWIK -BOLT 3 steel
expansion anchor or Hilti X-DNI 27 P8 S15 powder actuated floor pin with integral nom 9/16 in. (15 mm) diam washer may be used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP 643 50/1.5 -N, CP 643 63aW, CP 643 9313'N, CP 643 9014% and CP643
16016 "N. Firestop Collar
*Bearing the UL Classification Mark
S ►F/
ELM Reproduced by HILTI, Inc. Courtesy of V
Underwriters Laboratories, Inc.
Hilt! Firestop Systems November 18,2006 m
System No. W -L -2284
F Rating -1 Hr
T Rating -1 Hr
a
N
3
SECTION A -A
1. Wall Assembly -- The 1 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specked in the individual 0300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features:
A Studs -- Wall framing shall consist of wood studs or steel channel studs. Wood studs to consist of 2 by 4 in. lumber
spaced 16 in. OC. Steel studs to be min 3 -1/2 in. wide and spaced max 24 in. OC.
B. Gypsum Board* -- Min 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness,
number of layers and orientation shall be as specified in the individual U300 or U400 Wall and Partition Design. Max
diam of opening is 4 in.
-- nonmetallic i to be centered within the firestop em. An annular space of 3 16 to 1 4 in.
2. Through Penetrants One nonmet Pipe p syst Pa / /
is required within the firestop system. Pipe to be rigidly supported on both sides of wall assembly. The following types and
sizes of nonmetallic pipes may be used:
A Polyvinyl Chloride (PVC) Pipe - Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in
closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 3 in. diam (or smaller) SDR 13.5 CPVC pipe for use in closed
(process or supply) piping systems.
3. Fill, Void or Cavity Material* -- Wrap Strip - Layers of intumescent wrap strip are continuously wrapped around the pipe with
ends held in place with tape. Wrap strip installed such that ends protrude nom. 1/8 in. beyond both surfaces of wall. Size
of wrap strip and number of layers are shown in table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP648 -E W25/1' or CP648 -E W45/1 -3/4' Frestop Wrap Strip
ProdudDesignation
Pipe
Number of
Nom. Wrap Strip
SYMBOL
Diameter (in.)
Layers
Width (n.)
CP648- E- W2511'
1 -112 and 2
1
1
CP648- E -W45/1 -314°
1 -112, 2 and 3
1
1 -3/4
A. Fill, Void or Cavity Material* - Wrap Strip -- (As an aftemate to the wrap strip in Item 3) - One layer of intumescent
wrap strip is tightly wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip
installed such that ends protrude nom. 1/8 in. beyond both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- CP648- S -1.5' US, CP648 -S -2' US, CP648 -S -3' US
*Bearing the UL Classification Mark
L= ;J Reproduced
Laboratories, Inc.
of
FIRESTOP SYSTEMS Apnl22•2005 C US
System No. F -A -2089 0
F Rating - 3 Hr a
T Rating - 0 Hr
W Rating - Class 1(See Item 3B)
2 1
313
44.
t
A A
3A
SECTION A -A
1. Floor Assembly - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100.150 pd) concrete. Max diameter of opening is 5 in.
1A. Floor AssemblygOptional - Not Shown) - The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials
and in the manner specified in the individual D900 Series designs in the Fire Resistance Directory and as summarizes below:
A Concrete - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pd) concrete.
B. Steel Floor and Form Units* - Composite or non-composite max 3 in. deep gale steel fluted units as specified in the individual Floor- Ceiling
Design.
2. Through Penetrants - One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the
firestop system is dependent upon the diam and type of penetrant used as tabulated in Item 3A. Pipe to be rigidly supported on both sides of floor
or wall assembly. The following types and sizes of nonmetallic pipes may be used:
A Polyvinyl Chloride (PVC) Pipe - Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or supply) or
vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. diam (or smaller) SDR13.5 CPVC for use in dosed (process or supply) piping
systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process
or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 3 in. diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or supply) or
vented (drain, waste or vent) piping system.
3. Firestop System - The firestop system shall consist of the following:
A Fill, Void or Cavity Material` -Wrap Strip - Nom 3116 in. thick by 1-314 in. wide intumescent wrap strip. The layers of wrap strip are
continuously wrapped tightly around pipe with ends held in place with tape. Wrap strip installed recessed % in. from bottom surface of
concrete cover. The max diam of opening, max diam and type of penetrant, annular space within the firestop system and layers of wrap strip
required are tabulated below:
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP648 -E W4511 -314' Wrap Strip
B. Fill, Void or Cavity Materials•- Sealant - Min 1/4 in. thickness of fill material applied within the annulus directly on top of wrap strip, flush with
top surface of floor. W Rating applies only when CP 601 S Sealant is used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC- FS-ONE Sealant or CP 601S Sealant
*Bearing the UL Classification Mark
S IF/
Reproduced by HILTI, Inc. Courtesy of VI tom►
Underwriters Laboratories, Inc.
m
Hilti Firestop Systems October 06, 2005
1
PLUMBING FIRE PENETRATION DETAILS
Scale: NTS
PRINTED ON: 12-07-2009
System No. C -AJ -1226 N
F RATING = MR. :y
T RATING = MR !
L Rating At Ambient - Less than 1 CFM/Sq Ft
L Rating At 400 F -4 CFWSq Ft
3
4B F_ A 2 4B 1
i
3 A 4A
SECTION A -A
1. Floor or Wall Assembly -- Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150
pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of
opening is 32 in.
2. Metallic Sleeve -- (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve
cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3
in. above floor or beyond both surfaces of wall.
3. Through - Penetrant -- One metallic pipe, tube or conduit to be installed either concentrically or
eccentrically within the firestop system. The annular space between penetrant and periphery of opening
shall be min 0 in. (point contact) to max 1 -7/8 in. Penetrant may be installed with continuous point
contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types
and saes of metallic penetrants may be used:
A. Steel Pipe -- Nom 30 in. dam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 30 in. dam (or smaller) cast or ductile iron pipe.
C. Copper Pipe -- Nom 6 in. dam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E Conduit -- Nom 6 in. d conduit
am (or smaller) steel cond
F. Conduit - Nom 4 in. dam (or smaller) steel electrical metallic tubing
4. Firestop System -- The fmstop system shall consist of the following:
A. Packing Material -- Min 4 in. thickness of min 4 pcf mineral wool butt insulation firmly packed
into opening as a permanent form. Packing material to be recessed from top surface of floor or
sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of
fill material
B. Fill, Void or Cavity Material* -- Sealant -- Min 1/4 in. thickness of fill material applied within the
annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point
or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of
fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of
floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- FS -One Sealant *Bearing the UL Classification Mark
M�_M
LJ-- iJ�L���• hKodutmil
undowdti s� tiLat � d /�
FIRESn7P SYSTEMS October 30. 2003 C U$
Page: t of t
System No. C -AJ -2342 N
F Rating - 3 Hr a
T Rating - 0 Hr
W Rating - Class 1 (See Item 3B)
2
3B 1
A A
3A
SECTION A -A
1. Floor or Wall Assembly- Min 2 -1/2 in. (64 mm) thick reinforced lightweight or normal weight (100 -150 pd or 1600 -2400 kg/m3) concrete floor or
wall. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 6 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants - One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the
firestop system is dependent upon the max diam and type of penetrant used as tabulated in Item 3A Pipe to be rigidly supported on both sides of
floor or wall assembly. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or
supply) or vented (drain, waste or vent) piping systems. i
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC for use in dosed (process or supply) piping
ly) P P 9
systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in dosed
(process or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nam 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or
supply) or vented (drain, waste or vent) piping system.
3. Firestop System - The firestop system shall consist of the following:
A Fill, Void or Cavity Material* - Wrap Strip - Layers of intumescent wrap strip are continuously wrapped around the pipe with ends held in place
with tape. Wrap strip installed recessed max 1/4 in. (6 mm) from bottom surface of floor or from both surfaces of wall. Size of wrap strip and number
of layers for a given size penetrant are shown in table below:
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - CP648 -E W2511' or CP648 -E W4511 -3/4" Firestop Wrap Strip
Reproduced by HILTI, Inc. Courtesy of V
S 1 Fj�
Underwriters Laboratories, Inc.
Hilti Firestop Systems August2g,2007 e,
P Y Page- 1 of 2
A-7
A---J
System No. W -L -1290 N
F Rating -1 and 2 Hr (See Item 1) 3
T Rating - 0 Hr
L Rating at Ambient - Less than 1 CFM /Sq Ft
L Rating at 400° F - Less than 1 CFM /Sq Ft
1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in
the manner specified in the individual 0300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and
shall include the following construction features.
A Studs -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features.
B. Gypsum Board * - -- Nom 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number
of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the Fire
Resistance Directory. Max dam of opening is 5 in.
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system.
Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to
be rigidly supported on both sides of wall assembly. The annular space between the pipe or tube and periphery of the opening
shall be min 0 in (point contact) to max 1/2 in. The following types and sizes of metallic pipes, conduit or tube may be used:
A Steel Pipe -- Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Iron Pipe -- Nom 4 in. dam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in. dam (or smaller) steel electrical metallic tubing (EMT) or steel conduit
D. Copper Tube -- Nom 4 in. dam (or smaller) Type L (or heavier) copper tube.
E. Copper Pipe -- Nom 4 in. dam (or smaller) Regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material * - Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with both
surfaces of wall. At the point contact location between pipe and wall, a min % in dam bead of fill material shall be applied at
the pipe /wall interface.
HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP606 Flexible Firestop Sealant
*Bearing the UL Classification Mark
Reproduced by HILTI, Inc. Courtesy of Ic,v l FVFp
Unden!writers Laboratories, Inc.
FIRESTOP SYSTEMS .tune 03, 2005 C US
System No. C -AJ -2342
F Rating - 3 Hr 'a
T Rating - 0 Hr
W Rating - Class 1 (See Item 3B)
Product Designation
Pipe Size in.
(mm)
Max Opening
Diam (in.)
PLUMBING
SYMBOL
LEGEND
Nom Wrap Strip
Width in. (mm)
CP648 -E W2511'
11/2(38)
3(76)
3/16 (4.8)
15/16 (24)
GATE - VALVE
1(25)
CP648 -E W4511 -314"
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
1
13/4 (45)
�
VENT THRU ROOF (VTR)
31/2(89)
SANITARY PIPE
CW
COLD WATER PIPE
'Id
P -TRH
2 (51)
31/2(89)
3/16(4.8)
15116 (24)
1
1314 (45)
CP648 -E W4511 -314'
3 (76)
4 (102)
PIPING TURNING UP
15116 (24)
1
1314 (45)
CP648 -E W45/1 -314'
3 (76)
WATER HAMMER (SHOCK)
318 (10)
1 1/16(27)
----- - - - - --
VENT PIPE
HW
HOT WATER PIPE
6 (152)
ARRESTOR.
11/8(29)1
PIPING TURNING DOWN
-
COLD WATER PIPE
CONNECT TO EXISTING
CO
WALL CLEAN OUTS
--
HOT WATER PIPE
F.F.
FIRST FLOOR
FD
FLOOR DRAIN
UG
UNDERGROUND
S.F.
SECOND FLOOR
CD
CONDENSATE DRAIN PIPE
FU
FIXTURE UNITS
DCV
DOUBLE CHECK VALVE
FW
FILTERED WATER
BACKFLOWPREVENTER;
CA
COMPRESSOR SYSTEM PIPING
VA
VACUUM SYSTEM PIPING
®
FLOOR CLEAN -OUT
1
PLUMBING FIRE PENETRATION DETAILS
Scale: NTS
PRINTED ON: 12-07-2009
System No. C -AJ -1226 N
F RATING = MR. :y
T RATING = MR !
L Rating At Ambient - Less than 1 CFM/Sq Ft
L Rating At 400 F -4 CFWSq Ft
3
4B F_ A 2 4B 1
i
3 A 4A
SECTION A -A
1. Floor or Wall Assembly -- Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150
pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of
opening is 32 in.
2. Metallic Sleeve -- (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve
cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3
in. above floor or beyond both surfaces of wall.
3. Through - Penetrant -- One metallic pipe, tube or conduit to be installed either concentrically or
eccentrically within the firestop system. The annular space between penetrant and periphery of opening
shall be min 0 in. (point contact) to max 1 -7/8 in. Penetrant may be installed with continuous point
contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types
and saes of metallic penetrants may be used:
A. Steel Pipe -- Nom 30 in. dam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 30 in. dam (or smaller) cast or ductile iron pipe.
C. Copper Pipe -- Nom 6 in. dam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E Conduit -- Nom 6 in. d conduit
am (or smaller) steel cond
F. Conduit - Nom 4 in. dam (or smaller) steel electrical metallic tubing
4. Firestop System -- The fmstop system shall consist of the following:
A. Packing Material -- Min 4 in. thickness of min 4 pcf mineral wool butt insulation firmly packed
into opening as a permanent form. Packing material to be recessed from top surface of floor or
sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of
fill material
B. Fill, Void or Cavity Material* -- Sealant -- Min 1/4 in. thickness of fill material applied within the
annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point
or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of
fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of
floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- FS -One Sealant *Bearing the UL Classification Mark
M�_M
LJ-- iJ�L���• hKodutmil
undowdti s� tiLat � d /�
FIRESn7P SYSTEMS October 30. 2003 C U$
Page: t of t
System No. C -AJ -2342 N
F Rating - 3 Hr a
T Rating - 0 Hr
W Rating - Class 1 (See Item 3B)
2
3B 1
A A
3A
SECTION A -A
1. Floor or Wall Assembly- Min 2 -1/2 in. (64 mm) thick reinforced lightweight or normal weight (100 -150 pd or 1600 -2400 kg/m3) concrete floor or
wall. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 6 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants - One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the
firestop system is dependent upon the max diam and type of penetrant used as tabulated in Item 3A Pipe to be rigidly supported on both sides of
floor or wall assembly. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or
supply) or vented (drain, waste or vent) piping systems. i
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC for use in dosed (process or supply) piping
ly) P P 9
systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in dosed
(process or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nam 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or
supply) or vented (drain, waste or vent) piping system.
3. Firestop System - The firestop system shall consist of the following:
A Fill, Void or Cavity Material* - Wrap Strip - Layers of intumescent wrap strip are continuously wrapped around the pipe with ends held in place
with tape. Wrap strip installed recessed max 1/4 in. (6 mm) from bottom surface of floor or from both surfaces of wall. Size of wrap strip and number
of layers for a given size penetrant are shown in table below:
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - CP648 -E W2511' or CP648 -E W4511 -3/4" Firestop Wrap Strip
Reproduced by HILTI, Inc. Courtesy of V
S 1 Fj�
Underwriters Laboratories, Inc.
Hilti Firestop Systems August2g,2007 e,
P Y Page- 1 of 2
A-7
A---J
System No. W -L -1290 N
F Rating -1 and 2 Hr (See Item 1) 3
T Rating - 0 Hr
L Rating at Ambient - Less than 1 CFM /Sq Ft
L Rating at 400° F - Less than 1 CFM /Sq Ft
1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in
the manner specified in the individual 0300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and
shall include the following construction features.
A Studs -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features.
B. Gypsum Board * - -- Nom 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number
of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the Fire
Resistance Directory. Max dam of opening is 5 in.
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system.
Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to
be rigidly supported on both sides of wall assembly. The annular space between the pipe or tube and periphery of the opening
shall be min 0 in (point contact) to max 1/2 in. The following types and sizes of metallic pipes, conduit or tube may be used:
A Steel Pipe -- Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Iron Pipe -- Nom 4 in. dam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in. dam (or smaller) steel electrical metallic tubing (EMT) or steel conduit
D. Copper Tube -- Nom 4 in. dam (or smaller) Type L (or heavier) copper tube.
E. Copper Pipe -- Nom 4 in. dam (or smaller) Regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material * - Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with both
surfaces of wall. At the point contact location between pipe and wall, a min % in dam bead of fill material shall be applied at
the pipe /wall interface.
HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP606 Flexible Firestop Sealant
*Bearing the UL Classification Mark
Reproduced by HILTI, Inc. Courtesy of Ic,v l FVFp
Unden!writers Laboratories, Inc.
FIRESTOP SYSTEMS .tune 03, 2005 C US
System No. C -AJ -2342
F Rating - 3 Hr 'a
T Rating - 0 Hr
W Rating - Class 1 (See Item 3B)
Product Designation
Pipe Size in.
(mm)
Max Opening
Diam (in.)
Annular Space
Min in.(mm)
Annular Space
Max in. (mm)
Number of
Layers
Nom Wrap Strip
Width in. (mm)
CP648 -E W2511'
11/2(38)
3(76)
3/16 (4.8)
15/16 (24)
1
1(25)
CP648 -E W4511 -314"
11/2(38)
3 (76)
3/16(4.8)
1516 (24)
1
13/4 (45)
CP648 -E W2511"
2 (51)
31/2(89)
3/16(4.8)
15116 (24)
1
1(25)
CP648 -E W45/1 -314"
2 (51)
31/2(89)
3/16(4.8)
15116 (24)
1
1314 (45)
CP648 -E W4511 -314'
3 (76)
4 (102)
3/16(4.8)
15116 (24)
1
1314 (45)
CP648 -E W45/1 -314'
3 (76)
5 (127)
318 (10)
1 1/16(27)
2
1314 (45)
CP648 -E W4511 -314'
4 (102)
6 (152)
318 (10)
11/8(29)1
77TF
1314 (45)
Al. Fill, Void or Cavity Material' - Wrap Strip - (As an alternate to the wrap strip in Item 3A) - One layer of intumescent wrap strip is continuously
wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip installed recessed max 1/4 in. (6 mm) from top surface
of floor or from both surfaces of wall. Size of wrap strip for a given size penetrant are shown in the table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - CP646- S-1.5" US, CP648 -S-2' US, CP648 -S-3" US or CP648 -SA" US Wrap Strip
Product Designation
Pipe Size
Max Opening
Annular Space
Annular Space
Nom Wrap Strip
Nom Wrap
Strip Thick in.
Nom Wrap
Strip Width in.
in. mm
( )
Diam in.
( )
Min in. mm
( )
Max in. mm
( )
Len in. (mm)
Length
(mm)
(mm)
CP648- S-1.5° US
1 1/2 (38)
3 (76)
3/16(4.8)
15/16(24).
6.5(165)
0.18 (4.6)
1 (25)
CP648 -S-2" US
2 (51)
3112 (89)
3116 (4.8)
15116 (24)
8 (203)
0.18 (4.6)
1 (25)
CP648 -S-3" US
3(76)
4 (102)
3/16(4.8)
5/16 (8)
11.5 (292)
0.18 (4.6)
13/4(45)
CP648 -S-4° US
4(102)-
6 (152}
318 (10)
11/8(29)
15.1 (384)
0.36(9)
1 3/4 (45)
Al. Fill, Void or Cavity Material* - Wrap Strip - (As an alternate to the wrap strip in Item 3A) - One layer of intumescent wrap strip is continuously
wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip installed recessed max 1/4 in. (6 mm) from top surface
of floor or from both surfaces of wall. Size of wrap strip for a given size penetrant are shown in the table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - CP648-S-1.5° US, CP648 -S -2' US, CP648 -S-3" US or CP648-SA" US Wrap Strip
B. Fill, Void or Cavity Material" - Sealant - Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor of
both surfaces of wall. W Rating applies only when CP 601S or CP 604 sealant is used.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC FS-ONE Sealant, CP 601S Sealant or CP 604 Sealant
C. Packing Material (not shown) - Min 1/2 in. (13 mm) thickness of 4 pd (64 kg/m3) mineral wool batt insulation firmly packed into annular space
and recessed from the top surface of floor to accommodate the required thickness of fill material. Required only when CP 604 Sealant is used.
*Bearing the UL Classification Mark
S►Fi
Reproduced by HILTI, Inc. Courtesy of V
Underwriters Laboratories, Inc.
Systems August 2s,2oo7
Hilti Firestop Y m Page: 2 of 2
151 SEVILLA AVENUE, SUITE 200
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
STATE OF FLORIDA AR- 0010536
RAYMUNDO FEITO, R.A. AA- CO01315
Architect • Seal/Signature
Construction Documents for:
- SR PFW
at:
ONE 7000 PLACE
SUITE: PHN
7th FLOOR
7000 SW 62nd AVENUE
SOUTH MIAMI, FL 33143
9
Issue Date & Issue Description Drawn By Checked By
01 12/04/09 AC AR
PERMIT ISSUE
Z_
Z
J
CL
W
U
CL
i
Z
0
N
W
IO
n:
O
I-- Date & Delta Description Drawn By Checked By
Z
•
t9
Z
Z
QZ
IL
•
W
H
V
W
F-
V
Q
Client Information
HEALTHCARE REALTY
2601 SW 37th AVENUE
SUITE 805
MIAMI, FL 33133
OFFICE: (305) 446 -3666
Project Number
09148
CAD File Name
ONE 7000 PLACE - SUITE PHN
DesPn , oNrG FIRE DETAILS
Scale
AS NOTED
Consultant • Seal/Signature
1 1 �•
I, I)