10-323-017PLUMBING DEMOLITION FLOOR PLAN
lrhw#�i�Nri�]\ Ilsl�4��4UETi
TABLE 604.4 EFFECTIVE JULY 1 2008 **
PLUMBING FIXTURE
GENERAL PLUMBING NOTES
OR FIXTURE FITTING
1.6 GPF CYCLE
LAVATORY ,PRIVATE
i
14.
INSULATE! ALL AIR CONDITIONING AND REFRIGERATION CONDENSATE DRAIN WITH 3/4" INCOAFLEX PIPE INSULATION OR EQUAL,
FINISHED, WHERE EXPOSED, WITH 2 COATS OF WHITE LATEX PAINT AS PER MANUFACTURER'S INSTRUCTION.
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,AND ALL APPLICABLE LOCAL ORDINANCES. C. SANITARY PIPE FITTINGS:
2.
ALL WORK SHALL B E PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE
C.1 JOINTS FOR HUBLESS PIPE AND FITTING SHALL CONFORM EITH THE F.P.C. AND THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS AND LOCAL CODE REQUIREMENTS. HUBLESS COUPLINGS SHALL CONFORM TO CISPI 301. JOINTS FOR HUB AND
SINK FAUCET
PENETRATING FIRE
URINAL
COMPLETE SYSTEM SHALL BE FULLY OPERATIVE AFTER COMPLETION OF WORK.
SPIGOT PIPE SHALL BE INSTALLED WITH COMPRESSION GASKETS CONFORMING TO THE REQUIREMENTS OF ASTM STANDARD
15.
PIPING PENETRATION AT ROOFS, CEILINGS, FLOORS AND WALLS SHALL BE SEALED AIR AND WATER TIGHT. WHERE
SAFE TO PROVIDE PROTECTION MATCHING REQUIRED FIRE RESISTANCE RATING.
1.28 GALLONS PER FLUSHING CYCLE
PLUMBING CONTRACTOR SHALL FURNISH WRITTEN GUARANTEE THAT ALL PLUMBING WORK SHALL BE FREE OF DEFECTS OF
C -564 OR SHALL BE INSTALLED WITH LEAD AND OAKUM.
RATED CONSTRUCTION, FIRE
3.
MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE,
D. DOMESTIC WATER PIPING AND FITTINGS SHALL CONFORM WITH TABLES 605.4 through 605.8. OF THE F.P.C. AND SHALL BE ONE
16.
ALL HORIZONTAL VENT PIPING SHALL SLOPE TO DRAW TO STACKS. NO POCKETS OR LOW POINTS SHALL BE CREATED IN THE VENT
0.9 GALLONS PER RACK FOR ALL OTHERS
SHALL VISIT THE SITE AND THOROUGHLY FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS. FIELD VERIFY LOCATION
OF THE FOLLOWING TYPES:
UNDER THE COUNTER MACHINES
LINES WHICH MAY PREVENT VENTING IF FILLED WITH CONDENSATION.
4.
CONTRACTOR
OF EXISTING POINTS OF CONNECTIONS BEFORE SUBMITTING BID. OBTAIN ANY REQUIRED CLARIFICATION BEFORE COMMENCING WORK.
D.1 COPPER TYPE 'L' ABOVE GROUND AND COPPER TYPE 'K' BELOW GROUND CONFORMING WITH ASME B -88, AND ASTM B -16,
17.
CEILING ACCESS PANELS SHALL BE PROVIDED FOR VALVES INSTALLED ABOVE OTHERWISE NON- ACCESSIBLE CEILINGS.
WATER FACTOR OF 8 OR LOWER
COMPONENTS SHALL B E CAREFULLY REMOVED OR RELOCATED. EACH RESULTING
LEAD -FREE SOLDER. DOMESTIC WATER PIPING SHALL NO BE INSTALLED BELOW SLAB, UNLESS INDICATED OTHERWISE ON
EXCEPTIONS:
1- BLOWOUT DESIGN WATER CLOSETS (3.5 GALLONS PER FLUSHING CYCLE)
5.
WHERE INDICATED REQUIRED, EXISTING SYSTEM
CONSTRUCTION SHALL BE PROPERLY PATCHED AND FINISHED WITH THE SAME MATERIALS AS THOSE
THESE DRAWINGS
18.
NO EQUIPMENT OR MATERIALS SHALL BE PURCHASED OR INSTALLED PRIOR TO FINAL APPROVAL OF SHOP DRAWINGS.
L
OPENING IN THE BUILDING
ADJACENT TO THE OPENING.
D.2 PROVIDE WATER HAMMER ARRESTOR 18" HIGH, NEXT LARGE SIZE THAN PIPE SERVING FIXTURE.
19•
THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO SHOW AS -BUILT CONDITIONS AT THE COMPLETION OF
6.
COORDINATE NEW PLUMBING WORK WITH LIGHTING, ELECTRIC AL DUCTWORK,STRUCTURAL FRAMING AND CEILING SYSTEMS.
D.3 INSULATE ALL HOT WATER PIPING WITH 1" RIGID FIBERGLASS OR 1 2" THICK FLEXIBLE FOAM INSULATION
/
(ARMAFLEX). FLEXIBLE FOAM INSULATION SHALL NOT BE SPLIT, AND SHALL BE TAPED AT BUTT JOINTS.
CONSTRUCTION.
20.
FURNISH AND INSTALL DIELECTRIC COUPLINGS AT ALL CONNECTIONS BETWEEN DISSIMILAR METALS.
7.
CONTRACTOR SHALL BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND NOTIFY ARCHITECT /ENGINEER OF ANY DEVIATION DUE
21.
THE EXISTING PLUMBING LINES INDICATED OR NOTED ON THESE DRAWINGS, ARE SHOWN AS OBTAINED FROM EXISTING INFORMATION
TO FIELD CONDITIONS BEFORE COMMENCING WORK.
E. WALL CLEANOUTS.
OR SITE OBSERVATIONS, AND ARE ONLY APPROXIMATE IN LOCATION. THE CONTRACTOR SHALL VERIFY THESE LOCATIONS, CONNECTION
8.
CONTRACTOR SHALL COORDINATE LOCATION AND SIZE OF ALL PENETRATIONS THROUGH WALLS, CEILINGS, FLOORS AND ROOFS WITH
EA JOSAM SERIES 58750 WITH ACCESS COVER OR EQUAL
E.2 PROVIDE CHROME PLATED BRASS ESCUTCHEONS WITH LOCKING SCREWS WHERE PIPE PASS THROUGH FINISHED WALLS.
POINTS AND SIZES BEFORE PROCEEDING WITH WORK.
AND CARPETING WITHIN THIS
OTHER TRADES AND REPORT ANY DISCREPANCIES TO ARCHITECT /ENGINEER.NO STRUCTURAL MEMBER SHALL BE CUT OR MODIFIED
E.3 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH SOIL AND WASTE STACK.
22.
PRECAUTIONS SHALL BE TAKEN TO PREVENT CONTAMINATION OF OWNER EQUIPMENT, FURNITURE
EQUIPMENT, FURNITURE AND CARPETING AS NECESSARY. DUST AND DEBRIS SHALL BE STRICTLY
WITHOUT WRITTEN AUTHORIZATION.
F. VALVES.
BUILDING. COVER AND WRAP
CONTROLLED. CLOSE COORDINATION WITH OWNER WILL BE REQUIRED.
9.
DRAWING ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR EXACT LOCATION OF FIXTURES AND PIPING.
F.1 QUATER TURN BALL VALVES, RATED FOR 125 PSI. MANUFACTURED BY NIBCO, SCOTT, STOCKHAM OR EQUAL.
23.
WHERE REQUIRED, EXISTING CEILINGS SHALL BE REMOVED TO MODIFY THE EXISTING PLUMBING SYSTEMS. THESE CEILINGS SHALL BE
CONTRACTORS SHALL BE RESPONSIBLE FOR ALL PERMITS, TAXES, INSPECTIONS AND TEST FEES.
F.2 PROVIDES STOPS AT ALL PLUMBING FIXTURES. EXPOSED STOPS SHALL BE CHROME PLATED.
REPLACED TO MATCH ADJACENT SURFACES.
10.
DOCUMENTS SHALL MEET ALL THE REQUIREMENTS OF THE F.P.C. AND ALL OTHER
24.
ALL DISCONNECTED PLUMBING LINES SHALL BE EITHER RECONNECTED OR CAPPED.NO ONES SHALL REMAIN OPEN TO THE
11.
ALL MATERIALS TO BE PROVIDED UNDER THIS
LOCAL STANDARDS AND REGULATIONS. MATERIALS SHALL BE NEW. FREE OF DEFECTS AND OF AMERICAN MANUFACTURER,
G. PLUMBING FIXTURES.
ATMOSPHERE.
INDELIBLY MARKED WITH MANUFACTURER NAME, WEIGHT AND /OR CLASS. MANUFACTURER NAMES SHALL BE INTERPRETED AS
G.1 SEE PLUMBING FIXTURE SCHEDULE FOR FIXTURE SPECIFICATIONS.
25•
IF SPACES ARE USED AS "RETURN AIR CEILING PLENUMS", ALL MATERIALS INSIDE THE R/A PLENUM SHALL HAVE A
ESTABLISHMENT OF REQUIRED TYPE, CLASS AND QUALITY. MATERIAL SHALL BE PROVIDED AS FOLLOWS.
G.2 PLUMBING FIXTURES SHALL COMPLY WITH WATER CONSERVATION REGULATION FS.553.14.
MAXXIMUM IMUM FLAME SPREAD INDEX OF 25 AND A MAX SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A.
PIPING BELOW GRADE SHALL BE ONE OF THE FOLLOWING TYPES (AS PER TABLE- 702.2, F.P.C.)
G.3 EXPOSED HOT WATER PIPING SERVING PLUMBING FIXTURES SHALL BE PROPERLY INSULATED.
"NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM."
A. ALL WASTE, VENT, AND STORM
SERVICE WEIGHT CAST IRON, SOIL PIPE. PIPING AND FITTINGS SHALL CONFORM TO THE REQUIREMENTS OF CISPI STANDARD
12. PERFORM THE FOLLOWING TEST:
A.1
301, ASTM A -888 OR ASTM A- 74,LATEST ISSUE.
A. NEW DOMESTIC WATER PIPING SHALL BE HYDROSTATICALLY TESTED AT 100 PSIG FOR A PERIOD OF NO LESS THAN ONE HOUR.
BELL AND SPIGOT SERVICE WEIGHT CAST IRON, WITH LEAD AND OAKUM, OR GASKETED JOINTS. PIPING AND FITTINGS SHALL
B. WASTE AND VENT PIPING SHALL BE FILLED WITH WATER TO A 10 FOOT HEAD AND ALLOWED TO STAND UNTIL THE WATER
A.2
CONFORM TO THE REQUIREMENTS OF CISPI STANDARD 301, ASTM A -888 OR ASTM A -74, LATEST ISSUE.
LEVEL REMAINS CONSTANT.
SCHEDULE 40 ABS OR (DWV) PCV PIPING. FOR BUILDINGS EXCEEDING 3- STORIES IN HEIGHT, UNDERGROUND DRAINAGE
C. CORRECT ALL DEFECTS DISCLOSED BY ABOVE TESTING.
A.3
PIPING SHALL BE SERVICE WEIGHT CAST IRON AS PER SECTION A.1.
D. NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE PURGED OF DELETERIOUS MATTER AND, WHERE REQUIRED BY THE
TABLE- 702.1, F.P.C.)
ADMINISTRATIVE AUTHORITY, DISINFECTED PRIOR TO UTILIZATION.THE METHOD TO BE FOLLOWED SHALL BE THAT PRESCRIBED
VENT AND STORM PIPING ABOVE GRADE SHALL BE ONE OF THE FOLLOWING TYPES (AS PER
BE THE HEALTH AUTHORITY OR WATER PURVEYOR HAVING JURISDICTION OR, IN THE ABSENCE OF A PRESCRIBED
B. ALL WASTE
AND FITTINGS SHALL CONFORM WITH THE REQUIREMENTS OF CITI STANDARD
METHOD , THE PROCEDURE DESCRIBED IN EITHER AWWA C651 OR AWWA 652, OR AS DESCRIBED IN SECTION 610 FPC 2004.
B.1 SERVICE WEIGHT CAST IRON SOIL PIPE. PIPING
301, ASTM A -888 OR ASTM A -74.
13. WASTE PIPING 2 1/2" AND SMALLER SHALL BE SLOPED AT 1/4" PER FOOT MINIMUM.PIPES LARGER THAN 2 1/2" SHALL BE SLOPED
B.2 BELL AND SPIGOT. 'NO HUB' SERVICE WEIGHT CAST IRON, OR WROUGHT IRON, WITH SEALING SLEEVES AND STAINLESS STEEL
WITH THE REQUIREMENTS OF CISPI STANDARD
AT 1/8" PER FOOT MINIMUM FALL.
COUPLING JOINTS, CLAMPS AND BOLTS-PIPING AND FITTINGS SHALL CONFORM
301, ASTM A -888 OR ASTM A -74, LATEST ISSUE.
B.3 SCHEDULE 40 ABS OR (DWV) PCV PIPING. NO COMBUSTIBLE PIPING SHALL BE LOCATED IN RETURN AIR PLENM.
PLUMBING DEMOLITION FLOOR PLAN
lrhw#�i�Nri�]\ Ilsl�4��4UETi
TABLE 604.4 EFFECTIVE JULY 1 2008 **
PLUMBING FIXTURE
MAXIMUM FLOW RATE
OR FIXTURE FITTING
1.6 GPF CYCLE
LAVATORY ,PRIVATE
1.0 GPM AT 60 PSI
LAVATORY PUBLIC (METERING)
0.25 GALLONS PER METERING CYCLE
LAVATORY PUBLIC (OTHER THAN METERING)
0.5 GPM AT 60 PSI
SHOWER HEAD
1.5 GPM AT 80 PSI
SINK FAUCET
1.0 GPM AT 60 PSI
URINAL
WATERLESS OR
0.5 GALLONS PER FLUSHING CYCLE
WATER CLOSET
1.28 GALLONS PER FLUSHING CYCLE
DISHWASHER (RESIDENTIAL)
6.5 GALLONS PER CYCLE OR LESS
(ENERGY STAR/WATER SENSE CERTIFIED)
DISHWASHER (COMMERCIAL)
LESS THAN 1.2 GALLONS PER RACK FOR
FILL AND DUMP MACHINES AND LESS THAN
0.9 GALLONS PER RACK FOR ALL OTHERS
TYPES OF MACHINES.
UNDER THE COUNTER MACHINES
1.0 GALLON OR LESS PER RACK FOR HIGH -
TEMPERATURE MACHINES AND 1.7 GALLONS
PER RACK FOR LOW -TEMP. MACHINES.
WASHING MACHINE
WATER FACTOR OF 8 OR LOWER
(ENERGY STAR/WATER SENSE CERTIFIED)
EXCEPTIONS:
1- BLOWOUT DESIGN WATER CLOSETS (3.5 GALLONS PER FLUSHING CYCLE)
2- VEGETABLE SPRAYS.
3- CLINICAL SINKS (4.5 GALLONS PER FLUSHING CYCLE).
4- SERVICE SINKS.
5- EMERGENCY SHOWERS.
**MIAMI DADE COUNTY - FOR NEW CONSTRUCTION OR FOR REMODELING PERMIT OF AN
AMOUNT GREATER THAN 50% OR MORE OF A STRUCTURE'S MARKET VALUE.
TABLE 604.4 , EFFECTIVE MARCH 1, 2009
FIXTURE
MAXIMUM FLOW
RATES
WATER CLOSET
1.6 GPF CYCLE
LAVATORY ,PRIVATE
2.2 GPM AT 60 PSI
LAVATORY PUBLIC (METERING)
0.25 GP METERING CYCLE
SHOWER HEAD
2.5 GPM AT 80 PSI
LAVATORY PUBLIC
(OTHEN THAN METERING)
.5 GPM AT 60 PSI
SINK FAUCET
2.2 GPM AT 60 PSI
URINAL
1.0 GPF CYCLE
- FLORIDA BUILDING CODE -
1O EXISTING SINK TO BE REMOVED.
ALL DISCONNECTED PLUMBING LINES FOR EXISTING
FIXTURES SHALL BE CAPPED.NO LINES SHALL REMAIN
OPEN TO THE ATMOSPHERE.
(REFER TO A1.0 FOR DEMOLITION PLAN)
VVI 1 {- . .. ..
0
411 = 1' -0"
Apn ^^
ITECTU DESIGN RATIVE
� % /�i�//// , •, y / /jam/ /M YH / / / / / / /lj / /��j^ i�' UO����� / ///
- -�1�51 SEVILLAAVENUE, SUITE 200
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
STATE OF FLORIDA AR- 0010536
RAYMUNDO FEITO, R.A. AA- CO01315
Architect • Seal/Signature
Construction Documents for:
S= Pin
at:
ONE 7000 PLACE
SUITE: PHN
7th FLOOR
7000 SW 62nd AVENUE
SOUTH MIAMI, FL 33143
Issue Date & Issue Description Drawn By Checked By
01 12/04/09 AC AR
PERMIT ISSUE
02 01 Ll3�10 AC AR
PRICING SUBMITTAL
ZE
a
W
V
4
a
i
z
0
N
W
iY
_O
W
W Date & Delta Description Drawn By Checked By
I--
z
s
z_
Z
z
5
a
iY
U
W
H
2
Q
Client Information
HEALTHCARE REALTY
2601 SW 37th AVENUE
SUITE 805
MIAMI, FL 33133
OFFICE: (305) 446 -3666
Project Number
09148
CAD File Name
ONE 7000 PLACE - SUITE PHN
Description
FLT PLAN
Scale
AS NOTED