rS z GENERAL H.V.A.C. NOTES 1. GENERAL 1.1 ALL WORK TO BE PERFORMED UNDER THESE DOCUMENTS SHALL CONFORM WITH THE FLORIDA BUILDING CODE, AS WELL AS ALL OTHER APPLICABLE STATE AND LOCAL REGULATIONS AND ORDINANCES. 1.2 ALL WORK SHALL BE PERFORMED BY A LICENSED AND INSURED MECHANICAL CONTRACTOR, IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE AFTER COMPLETION OF WORK. 1.3 MECHANICAL CONTRACTOR SHALL FURNISH TO THE OWNER WRITTEN WARRANTEE THAT THE INSTALLED SYSTEM SHALL BE FREE OF MATERIALS AND WORKMANSHIP DEFECTS FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE. 1.4 MECHANICAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING HIS OWN PERMIT AND PAYING ALL PERMIT AND INSPECTION FEES. 1.5 SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. 1.6 THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO SHOW AS -BUILT CONDITIONS AT THE COMPLETION OF CONSTRUCTION. 1.7 INTERRUPTION OF EXISTING FACILITIES AND / OR SERVICES SHALL BE KEPT TO A MINIMUM. THE CONTRACTOR SHALL FURNISH ALL MATERIALS REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICES. COORDINATE ALL INTERRUPTIONS WITH OWNER. 1.8 PRECAUTIONS SHALL BE TAKEN TO PREVENT CONTAMINATION OF OWNER EQUIPMENT, FURNITURE AND CARPETING WITHIN THIS BUILDING. COVER AND WRAP EQUIPMENT, FURNITURE AND CARPETING AS NECESSARY. DUST AND DEBRIS SHALL BE STRICTLY CONTROLLED. CLOSE COORDINATION WITH OWNER WILL BE REQUIRED. DURING CONSTRUCTION CONTRACTOR SHALL FOLLOW THE "SMACNA" LATEST EDITION "INDOOR AIR QUALITY GUIDELINES FOR OCCUPIED BUILDINGS UNDER CONSTRUCTION ". 1.9 ALL BUILDING CONSTRUCTION AFFECTED BY THE REMOVAL, RELOCATION OR INSTALLATION OF ANY PIECE OF EQUIPMENT SHALL BE REPAIRED AND FINISHED AS REQUIRED TO MATCH EXISTING CONDITIONS, OR AS DIRECTED BY THE ARCHITECTURAL DRAWINGS AND/ OR SPECIFICATIONS. 1.10 IF ANY CONFLICT IS ENCOUNTERED WITHIN THE DESIGN DOCUMENTS, REGARDLESS OF TRADE OR RESPONSIBILITY, THE GREATER SCOPE OF WORK SHALL PREVAIL. 2. FIELD VERIFICATION 2.1 ALL WORK SHALL BE FIELD VERIFIED AND COORDINATED BEFORE INSTALLATION WITH ALL OTHER TRADES. 2.2 WHERE INTERFERENCES OCCUR AND DEPARTURES FROM INDICATED DESIGN WILL BE REQUIRED TO DETERMINE CHANGES ON LOCATIONS, SIZES AND ELEVATIONS OF PIPING, DUCTWORK, ETC. THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR THE CHANGE ACCOMPANIED BY A DETAILED DRAWING FOR APPROVAL FROM ARCHITECT/ ENGINEER PRIOR TO PROCEEDING WITH ANY CHANGE OR DEPARTURES FROM EXISTING CONTRACT. 2.3 COORDINATE LOCATION OF DUCTWORK WITH OTHER TRADES, PARTICULARLY WHERE DUCTS RUN THROUGH STRUCTURAL ELEMENTS. PROVIDE ALL NECESSARY SLEEVES BEFORE CONCRETE IS POURED. 2.4 CONTRACTOR SHALL VERIFY EXISTING DUCTWORK SIZES, IF APPLICABLE, WHICH CONNECT TO NEW DUCTWORK BEFORE FABRICATION AND INSTALLATION. 2.5 CONTRACTOR SHALL VERIFY EXISTING PIPING SIZES, IF APPLICABLE, WHICH CONNECT TO NEW PIPING BEFORE FABRICATION AND INSTALLATION. 2.6 BEFORE CUTTING OR MAKING OPENINGS IN ANY BUILDING COMPONENT, CONTRACTOR SHALL VERIFY USING ANY REQUIRED MEANS THAT ITS LOAD BEARING CAPABILITY IS NOT COMPROMISED IN ANY MATTER. 2.7 THE CONTRACTOR, BY VIRTUE OF SIGNING THE CONTRACT, ACKNOWLEDGES THAT HE AND ALL HIS SUBCONTRACTORS HAVE SATISFIED THEMSELVES . AS TO THE NATURE AND LOCATION OF THE WORK. THE GENERAL AND LOCAL CONDITIONS INCLUDE, BUT ARE NOT RESTRICTED TO THOSE BEARING UPON; ACCESS POINTS AND POINTS OF CONNECTION TO THE SITE; THE CONFORMATION AND CONDITIONS OF THE WORK AREA; AND THE CHARACTER OF EQUIPMENT AND DEVICES NEEDED PRELIMINARY TO AND DURING THE PERFORMANCE OF THE WORK. FAILURE ON THE PART OF THE CONTRACTOR TO COMPLETELY OR PROPERLY EVALUATE ANY FACTORS OF COSTS PRIOR TO BIDDING SHALL NOT FORM A BASIS FOR ADDITIONAL COMPENSATION IF HE IS AWARDED THE CONTRACT. 3. EXISTING SYSTEMS 3.1 NOT USED. 3.2 CONTRACTOR SHALL VERIFY THE COOLING AND HEATING CAPACITIES AND AIR SUPPLY VOLUMES OF ALL EXISTING HVAC SYSTEMS TO REMAIN. THE CONTRACTOR SHALL ADVISE THE ARCHITECT AND ENGINEER OF ANY DEVIATION FROM WHAT IS INDICATED ON PLANS, BEFORE PROCEEDING WITH WORK. 3.3 ALL EXISTING MECHANICAL EQUIPMENT LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND HURRICANE FORCE WINDS FROM ANY DIRECTION AS PER F.B.C. 3.4 CONTRACTOR SHALL INSPECT ALL EXISTING DUCTWORK TO BE REUSED AND MAKE ANY NECESSARY REPAIRS TO ENSURE AN AIRTIGHT SYSTEM. AIR LEAKAGE RATES SHALL BE IN CONFORMANCE WITH THE SMACNA'S STANDARDS. DUCTWORK INSULATION SHALL BE INSPECTED AND REPLACED IN AREAS WHERE THE INSULATION IS DETERIORATED, DAMAGED, OR NOT CONTINUOUS. ALL WORK AND MATERIALS SHALL BE IN CONFORMANCE WITH THE CONTRACT DOCUMENTS. INSPECT AND REPAIR IF REQUIRED DUCT SUPPORTS TO ENSURE SECURE MOUNTING OF THE DUCT SYSTEM. 3.5 CONTRACTOR SHALL ADVISE THE OWNER OF THE GENERAL CONDITIONS OF THE EXISTING SYSTEMS TO REMAIN. 3.6 ALL EQUIPMENT IN WORKING CONDITIONS REMOVED UNDER THIS CONTRACT SHALL BE PROTECTED AND STORED AT THE JOB SITE FOR THE CONTRACTOR TO DELIVER TO A LOCATION DESIGNATED BY THE OWNER. ITEMS TO BE DEMOLISHED, INCLUDING DUCTWORK SYSTEM AND ACCESSORIES, SHALL BE PHYSICALLY REMOVED AND DISPOSED OF BY THE CONTRACTOR. CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR FINAL ARRANGEMENTS. 3.7 ANY EQUIPMENT OR DEVICES TO REMAIN THAT MIGHT HAVE TO BE DISCONNECTED BECAUSE OF THE REMOVAL OF ANY OTHER DEVICE MUST BE RECONNECTED AND TIED BACK TO THE EXISTING BUILDING SYSTEMS AND TESTED FOR CORRECT OPERATION. 4. NOT USED 5. DUCTWORK 5.1 PROVIDE ALL NECESSARY ACCESS PANELS TO CONTROL VALVES, DAMPERS, SENSORS, AND ANY OTHER DEVICES NON- ACCESSIBLE OTHERWISE. 5.2 ALL SIZES SHOWN FOR LINED AND UNLINED DUCTS ARE CLEAR INSIDE DUCT DIMENSIONS. 5.3 CONDITIONED AIR DUCTWORK SHALL BE CLASS "ONE" FIBER GLASS DUCT BOARD IN ACCORDANCE WITH SMACNA'S FIBROUS DUCTS STANDARDS, Unless specified otherwise on the Mechanical Floor Plans. INSULATION SHALL HAVE THE REQUIRED DENSITY AND THICKNESS TO PROVIDE A MINIMUM INSULATION VALUE OF R -6 FRO SUPPLY DUCTWORK RUNNING THROUGH UNCONDITIONED SPACE AND R -4.2 FOR DUCTWORK RUNNING THROUGH CONDITIONED SPACE. 5.4 PROVIDE VOLUME DAMPERS, TURNING VANES, ETC., IN DUCTWORK FOR PROPER AIR FLOW AND BALANCE. PROVIDE MULTIPLE VANE EXTRACTORS OR SPUTTERS WITH CONTROL RODS AT ALL OUTLETS CONNECTED CLOSER THAN TWO DUCT DIAMETERS TO MAIN SUPPLY DUCT AND WHERE SHOWN. 5.5 VENTILATION AND EXHAUST AIR DUCTWORK SHALL BE OF SHEET METAL CONSTRUCTION PER SMACNA'S STANDARDS. 5.6 EXHAUST VENTS SHALL BE LOCATED 10' MINIMUM DISTANCE FROM ANY OUTSIDE AIR INTAKE. 5.7 SEE SCHEDULES ON PLANS FOR AIR DISTRIBUTION DEVICES SPECIFICATIONS. 6. TEST AND BALANCING 6.1 NOT USED. 6.2 PERFORM A COMPLETE OPERATING AND BALANCING TEST OF THE FINISHED SYSTEM. PROVIDE WRITTEN REPORT OF THE RESULT OF THIS TEST STATING THE ACCEPTABILITY OF THE SYSTEM AND COMPLIANCE WITH THE DESIGN DOCUMENTS. TEST AND BALANCE AGENCY SHALL BE AN INDEPENDENT, AABC OR NEBB CERTIFIED AGENCY, AND SHALL BE RETAINED BY THE OWNER. CONTRACTOR SHALL COORDINATE WITH OWNER AND TESTING AND COMMISSIONING AGENCY ALL WORK FOR FINAL CERTIFICATION OF THE HVAC SYSTEM. 51111611111111 HVAC LEGEND SYMBOL DESCRIPTION A.H.U. AIR HANDLER UNIT ER EXISTING TO BE RELOCATED N NEW BDD BACK DRAFT DAMPER O/A OUTSIDE AIR CFM CUBIC FEET PER MINUTE E.F. EXHAUST FAN E.R. EXISTING TO REMAIN R/A RETURN AIR RG RETURN GRILLE S/A SUPPLY AIR SR SIDEWALL REGISTER TG TRANSFER GRILLE MVD MANUAL VOLUME DAMPER COND. CONDENSATE �T THERMOSTAT, PROGRAMMABLE (k) OA AIR DISTRIBUTION SEE PLAN SP* SPRINKLER HEAD (DOWNWARD) ® SUPPLY DUCT SECTION m EXHAUST, RETURN, OR OUTSIDE AIR ffe MANUAL VOLUME DAMPER uvo MVD AT TAKE OFF F FIRE DAMPER DRIVE TYPE BELT /DIRECT SUPPLY AIR DUCT RECTANGULAR WALL OPENING SIZE IN DUAL DUCT ACCESSORIES SHALL HAVE TURNING VANES ALTHOUGH NOT MAXIMUM SONE RATING. SHOWN [�] FLEXIBLE ROUND DUCT 1 FLEXIBLE ROUND DUCT DOWN TO GRILLE ROOF CURBS MODEL No. DUCT MOUNTED SMOKE DETECTOR TO GRILLE ACCESSORIES /REMARKS REMOTE TEST STATION/ AUDIBLE ALARM CEILING SUPPLY DIFFUSER ® LINEAR SUPPLY DIFFUSER CEILING RETURN DIFFUSER ', STANDARD BRANCH SUPPLY OR NOTES: 1. ALL FANS, VENTS, AND CAPS LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE RETURN, NO SPUTTER (45- TAP) 2. ALL FANS SHALL HAVE UL APPROVED LOCAL DISCONNECT MEANS, SUPPLIED BY WITH MVD AT TAKE OFF 3. NOT USED POINT OF CHANGE IN DUCT 5. ALL DIRECT DRIVE FANS SHALL BE PROVIDED WITH A SOLID STATE SPEED CONTROLLER CONSTRUCTION STATIC PRESSURE 6. FANS SHALL BE OF WELDED CONSTRUCTION UTILIZING CORROSION RESISTANT FASTENERS. CLASS. RETURN TREATMENT TO PREVENT CORROSION. AIR (R /A) GRILLE. ++ I 8. FAN DRIVER SHALL HAVE REGREASABLE BEARINGS WITH CAST IRON HOUSING AND EXTENDED E= SIDEWALL, CEILING GRILLE /REGISTER. _I.._ ONE INCH (1 ") DOOR UNDERCUT. EXHAUST FAN (CEILING MOUNTED). OUTSIDE AIR INTAKE WALL CAP. ,x L11� J� WALL MOUNTED EXHAUST FAN (PROPELLER / CENTRIFUGAL). LT WALL MOUNTED LOUVER. CONNECT TO EXISTING NOTE NOT ALL SYMBOLS MAY BE USED HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR LOCATION FIRE DAMPERS) SMOKE DAMPERS) BATHROOMS /JANITOR FIRE RATED ENCLOSURE MANUFACTURER COOK CEILING ASSEMBLY FLOOR •�c de FIRE STOPPING SMOKE CONTROL EXHAUST * * LXIS I ING SCOPE OF WORK THE SCOPE OF WORK ENTAILS THE RELOCATION OF EXISTING DIFFUSERS AS INDICATED IN THE FLOOR PLANS AS WELL AS THE INSTALLATION ON NEW OPEN - PLENUM RETURN AIR DIFFUSERS AND EXHAUST FAN AS SPECIFIED. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS BEFORE PROCEEDING WITH WORK. IF ANY DISCREPANCIES, ERRORS OR OMISSIONS ARE ENCOUNTERED ON PLANS, CONTRACTOR SHALL NOTIFY ARCHITECT /ENGINEER BEFORE ANY PART OF THE WORK IS STARTED SO THA PROPER CORRECTIONS BE MAKE. IF ARCHITECTS /ENGINEER IS NOT NOTIFIED PRIOR TO COMMENCING OF THE WORK , THE CONTRACTOR SHALL BEAR FULL RESPONSIBILITY FOR ANY DISCREPANCIES , ERROR OR OMISSIONS. THESE PLANS ARE FOR BUILDING DEPARTMENT REVIEW ONLY. THEY ARE NOT TO BE CONSTRUED AS CONSTRUCTION DOCUMENTS UNTIL ALL BUILDING DEPARTMENT APPROVALS ARE OBTAINED. VENTILATION EQUIPMENT SCHEDULE MARK EF -1 LOCATION CEILING AREA SERVED BATHROOMS /JANITOR MANUFACTURER COOK MODEL NUMBER GC -122 SYSTEM TYPE EXHAUST DESIGN AIR FLOW CFM 55 E.S.P. (IWC) 0.15 FAN TYPE CENTRIFUGAL FAN SPEED RPM 1,200 FAN Hp /Watts -° - -_ ELECTRICAL SERVICE V/-/Hz 120/1/60 DRIVE TYPE BELT /DIRECT DIRECT WALL OPENING SIZE IN - -- MAXIMUM SONE RATING. 1.2 BACK DRAFT DAMPER MODEL No. - -- ROOF CURBS MODEL No. - -- ACCESSORIES /REMARKS - -- WEIGHT LBS 13 NOTES: 1. ALL FANS, VENTS, AND CAPS LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE INSTALLED TO WITHSTAND HVHZ WIND VELOCITIES AS PER F.B.C. 2. ALL FANS SHALL HAVE UL APPROVED LOCAL DISCONNECT MEANS, SUPPLIED BY ELECTRICAL CONTRACTOR. 3. NOT USED 4. ALL ROOF FANS AND VENTS SHALL HAVE BACK -DRAFT DAMPERS AND ALUMINUM BIRD SCREENS. 5. ALL DIRECT DRIVE FANS SHALL BE PROVIDED WITH A SOLID STATE SPEED CONTROLLER INSTALLED AT THE FAN FOR AIR BALANCING PURPOSES. 6. FANS SHALL BE OF WELDED CONSTRUCTION UTILIZING CORROSION RESISTANT FASTENERS. ALL STEEL FAN COMPONENTS SHALL HAVE A SUPERFICIAL ELECTROSTATIC COATING TREATMENT TO PREVENT CORROSION. 7. ALL MOTORS SHALL BE HEAVY TYPE WITH PERMANENTLY LUBRICATED SEALED BALL BEARINGS AND FURNISHED TO THE SPECIFIED VOLTAGE PHASE AND ENCLOSURE. 8. FAN DRIVER SHALL HAVE REGREASABLE BEARINGS WITH CAST IRON HOUSING AND EXTENDED LOBE LINES IF APPLICABLE. 9. ALL FANS SHALL BE OF AN AMERICAN MANUFACTURER AND MANUFACTURED AT A CERTIFIED FACILITY. ALL FANS SHALL BEAR AMCA CERTIFIED RATING AND UL LISTED. DRAWING NOTES O NOT USED. OB EXITING TO REMAIN S/A DIFFUSER. © EXITING S/A DIFFUSER TO BE RELOCATED AS DESIGNATED. PROVIDE NEW FLEXIBLE/RIGID DUCT (if necessary) AND SET DAMPER TO MAINTAIN EXISTING CFM BEING DELIVERED. UD EXITING OPEN - PLENUM R/A DIFFUSER TO BE RELOCATED AS DESIGNATED. �E 4 "0 EXHAUST FAN DUCT UP TO ROOF. PROVIDE BDD & BIRD SCREEN AT ROOF CAP. DRAWING LEGEND E F - - - --� EXITING TO REMAIN SUPPLY AIR DIFFUSER. ER EXITING SUPPLY AIR DIFFUSERTO BE R RELOCATED. REFER TO NOTE (P). . F- --� RELOCATED SUPPLY AIR DIFFUSER. ER Fr\-- - EXITING RETURN AIR DIFFUSER TO BE L �A RELOCATED. ilRELOCATED RETURN AIR DIFFUSER. NEW RETURN AIR DIFFUSER. T1 EXITING TO REMAIN THERMOSTATS. GENERAL DIFFUSERS NOTES • THE CONTRACTOR MUST, AS PART OF THE SCOPE OF SERVICES, CLEAN ALL EXISTING DIFFUSERS TO REMAIN AND TO BE RELOCATED. IF ANY EXISTING TO REMAINIRELOCATED DIFFUSER IS FOUND UNSERVICEABLE, THE CONTRACTOR SHALL, PRIOR PROCEEDING, CONTACT OWNER. ANY REPLACEMENT SHALL MATCH EXISTING TYPE, EXISTING NECK SHALL BE MAINTAINED. • SQUARE OR ROUND DAMPERS MUST BE ORDERED SEPARATELY AND FIELD INSTALLED. • RETURN AIR DIFFUSERS SHALL NOT BE INSTALLED WITH FILTERS. • PROVIDE SIA DIFFUSER'S VOLUME DAMPER FOR BALANCING IF AFTER FIELD INSPECTION IT IS MISSING. • ALL NEW DIFFUSER(S) SHALL MATCH EXISTING. OUTSIDE AIR GENERAL NOTES EXISTING OUTSIDE AIR DEMAND REMAIN AS IS. THE RENOVATIONS DO NOT AFFECT THE OUTSIDE AIR REQUIREMENTS, OFFICE USAGE REMAINS AS IS. MECHANICAL FLOOR PLAN Scale: 4" = 1'4" 151 SEVILLA AVENUE, SUITE 200 CORAL GABLES, FL 33134 OFFICE: (305) 442 -1188 FAX: (305) 445 -1509 WWW. ADCINTERNATIONAL.NET STATE OF FLORIDA AR- 0010536 RAYMUNDO FEITO, R.A. AA- CO01315 Architect • Seal/Signature Construction Documents for: S1 Pfw at: ONE 7000 PLACE SUITE: PHN 7th FLOOR 7000 SW 62nd AVENUE SOUTH MIAMI, FL 33143 Issue Date & Issue Description Drawn By Checked By 01 12/04/09 AC AR PERMIT ISSUE Li Z Z Z a W CL Q 0 Z N W IW- Date '& Delta Description Drawn By Checked By Z i 0 Z Z Z 5 IL • W I- W h 2 Q Client Information HEALTHCARE REALTY 2601 SW 37th AVENUE SUITE 805 MIAMI, FL 33133 OFFICE: (305) 446 -3666 Project Number 09148 CAD File Name ONE 7000 PLACE - SUITE PHN Description MECHANICAL FLOOR PLAN, SCHEDULE, & NOTES Scale AS NOTED Consultant • Seal/Signature z r: • �� t 6 21 SW 102 Ct.1VIfa ` .' 174 Office: (786) 863 -7 91 z Fax: (305) 220 -51 6 Qpgengineerdesign@bellsouth.net 1 U M=l so W STATE OF FLORIDA ERGUIN CAPOTE P.E. No. 62487 LUIS O. PEREZ, PE P.E. No. 62586