13-330-001GENERAL ELECTRICAL NOTES ABBREVIATIONS /DEFINITIONS (USE THOSE THAT APPLY): BF: Ballast factor. CCT: Correlated color temperature. CFL: Compact fluorescent. CRI: Color- rendering index Emi: Electromagnetic interference EMT: Electrical metallic tubing. ENT: Electrical nonmetallic tubing FBC: Florida building code. FMC: Flexible metal conduit GFCI: Ground -fault circuit interrupter. GFEP: Ground fault equipment protection GFP: Ground fault protection. HID: High - intensity discharge HPS: High pressure sodium IMC: Intermediate metal conduit LFMC: Liquidtight flexible metal conduit LFNC: Liquidtight flexible nonmetallic conduit Luminoire: Complete lighting fixture, including ballast housing if provided. MCCB: Molded case circuit breakers NC: Normally closed NEC: NFPA 70, the national electrical code. NEMA: National electromechanical manufacturers association NETA: International electrical testing association NFPA: National fire protection association NICET: National institute for certification in engineering technologies NO: Normally open NRTL: Nationally recognized testing laboratories OAR: Owners authorized representative OCPD: Overcurrent protective device PIGTAIL: Short lead used to connect a device to a branch - circuit conductor. RFI: Radio - frequency interference. RMC: Rigid metal conduit RNC: Rigid nonmetallic conduit SF: Square feet SPOT. Single pole, double throw TVSS: Transient voltage surge suppressor. UL: underwriters laboratories UTP: unshielded twisted pair. 260500 GENERAL A. DRAWINGS 1. THE DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE STRUCTURAL, ARCHITECTURAL, AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK. WHERE HEADROOM OR SPACE CONDITIONS APPEAR INADEQUATE, CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED FOR PROPER EXECUTION OF THE WORK. SITE CONDITIONS SHALL GOVERN THE EXACT LOCATION OF ALL ELECTRICAL EQUIPMENT, DEVICES, WIRING, CONDUIT, ETC. WITH PRIOR APPROVAL BY DESIGN TEAM. 2. ONE COMPLETE SET OF DRAWINGS AND SPECIFICATIONS SHALL BE KEPT ON FILE AT THE SITE FOR THE SOLE USE OF MARKING AS -BUILT DATA. ALL CHANGES SHALL BE MARKED IN RED ON THESE PRINTS AS WORK PROGRESSES. 3. PRIOR TO EACH REQUISITION FOR PAYMENT, AS -BUILT PRINTS SHALL BE BROUGHT UP TO DATE FOR ACCEPTANCE BY OWNER'S AUTHORIZED REPRESENTATIVE (OAR). 4. THE COMPLETED SET OF AS -BUILT PRINTS SHALL BE DELIVERED TO THE OWNER PRIOR TO FINAL PAYMENT FOR INCORPORATION ONTO ORIGINALS. 5. RISERS ARE DIAGRAMMATIC AND DON'T INTEND TO SHOW EVERY BEND REQUIRED FOR THE INSTALLATION. B. CODES 1. INSTALLATION SHALL COMPLY WITH THE MOST STRINGENT REQUIREMENTS OF THE FOLLOWING CODES WHERE APPLICABLE TO THE WORK SHOWN ON THE DOCUMENTS OF THIS PROJECT: a. 2008 NFPA 70 NATIONAL ELECTRICAL CODE. b. 2010 FLORIDA BUILDING CODE c. 2009 NFPA 70E STANDARD FOR SAFETY IN THE WORKPLACE. 2. CONTRACTOR SHALL PROVIDE RECORD DRAWINGS TO OWNER WITHIN 30 DAYS OF DATE OF SYSTEM ACCEPTANCE PER 2004 FBC CH 13, 13- 413.ABC.2.1 3. CONTRACTOR SHALL PROVIDE OWNER WITH OPERATION AND MAINTENANCE MANUALS PER FBC CH 13, 13- 413.ABC.2.2 C. COORDINATION 1. CONTRACTOR WILL BE REQUIRED TO FURNISH, INSTALL, AND /OR CONNECT WITH APPROPRIATE SERVICES ALL ELECTRICAL ITEMS. 2. COORDINATE INSTALLATION: a. TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS SPECIFIC MOUNTING HEIGHTS THAT REDUCE HEADROOM ARE INDICATED. b. TO PROVIDE FOR EASE OF DISCONNECTING THE EQUIPMENT WITH MINIMUM INTERFERENCE TO OTHER INSTALLATIONS. c. TO ALLOW RIGHT OF WAY FOR PIPING AND CONDUIT INSTALLED AT REQUIRED SLOPE. SO CONNECTING RACEWAYS, CABLES, WIREWAYS, CABLE TRAYS, AND BUSWAYS WILL BE CLEAR OF OBSTRUCTIONS AND OF THE WORKING AND ACCESS SPACE OF OTHER EQUIPMENT. d. COORDINATE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET SLEEVES IN CAST -IN -PLACE CONCRETE, MASONRY WALLS, AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED. INSTALL TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT OF COMPONENTS OF BOTH ELECTRICAL EQUIPMENT AND OTHER NEARBY INSTALLATIONS. e. CONNECT IN SUCH A WAY AS TO FACILITATE FUTURE DISCONNECTING WITH MINIMUM INTERFERENCE WITH OTHER ITEMS IN THE VICINITY. 3. DO NOT INTERRUPT ELECTRICAL SERVICE TO FACILITIES OCCUPIED BY OWNER WITHOUT OWNER'S WRITTEN PERMISSION. 260526 GROUNDING AND BONDING 1. SIGNAL AND COMMUNICATION EQUIPMENT: FOR TELEPHONE, ALARM, VOICE AND DATA, AND OTHER COMMUNICATION EQUIPMENT, PROVIDE NO. 12 AWG MINIMUM INSULATED GROUNDING CONDUCTOR IN RACEWAY AND BOND ANTENNA METAL SUPPORT TO EXISTING GROUND BAR IN MDF ROOM. 260529 HANGERS AND SUPPORTS 1. DEVICES, INCLUDING ANCHORS, FASTENERS, HANGERS AND SUPPORTS, SHALL BE OF A TYPE DESIGNED OR FABRICATED FOR THE PURPOSE, AND SHALL ADEQUATELY AND SAFELY SECURE THE MATERIAL AND EQUIPMENT AND PRESENT A NEAT APPEARANCE. USE DEVICES WITH CORROSION RESISTANT CHARACTERISTICS FOR THE ATMOSPHERIC CONDITIONS IN WHICH THEY ARE INSTALLED. OUTDOOR EQUIPMENT SHALL BE SUPPORTED BY HOT -DIP GALVANIZED UNISTRUT WITH STAINLESS STEEL HARDWARE. 2. DO NOT USE POWDER - ACTUATED ANCHORS ON LIGHTWEIGHT- AGGREGATE CONCRETE, PRECAST STRUCTURAL MEMBERS, OR FOR SLABS LESS THAN 4 INCHES THICK 260529 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS A. GENERAL 1. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, AND MARKED FOR INTENDED USE. ROUTING OF RACEWAYS, INTERCONNECTING OUTLETS AND HOME -RUNS IS UP TO THE ELECTRICAL CONTRACTOR UNLESS SPECIFIC INSTRUCTION IS PROVIDED ON THE DRAWINGS. AFTER COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL SUBMIT TO THE OWNER AS -BUILT DRAWINGS OF THE WORK FOR FUTURE RECORD. ALL CONDUCTORS SHALL BE IN CONDUIT. COMPLETE RACEWAY INSTALLATION BEFORE STARTING CONDUCTOR INSTALLATION. B. RACEWAYS AND CABLE SUPPORTS 1. INSTALL NO MORE THAN THE EQUIVALENT OF THREE 90- DEGREE BENDS IN ANY CONDUIT RUN EXCEPT FOR COMMUNICATIONS CONDUITS, FOR WHICH TWO BENDS ARE ALLOWED. 2. CONDUIT INSTALLATION IN FINISHED AREAS SHALL BE CONCEALED UNLESS OTHERWISE INDICATED. CONCEAL ALL CONDUITS IN WALLS, ABOVE CEILINGS, IN OR UNDER SLABS OR IN FURRING, EXCEPT IN ELECTRICAL ROOMS. 3. INSTALL EXPOSED CONDUIT PARALLEL WITH OR AT RIGHT ANGLES TO THE BUILDING LINES. CONDUIT IN CONCRETE MEMBERS AND SLABS SHALL BE LOCATED SO AS NOT TO AFFECT THEIR STRUCTURAL STRENGTH. 4. USE EMT FOR INTERIOR CONCEALED WIRING AND ELSEWHERE AS PERMITTED BY THE NEC. 5. SECTIONS OF METALLIC CONDUIT SYSTEM SHALL BE GROUNDED AND ELECTRICALLY CONTINUOUS. 6. ROUTE RACEWAYS TO AVOID CONFLICTS WITH THE WORK OF OTHER TRADES. KEEP RACEWAYS AT LEAST 6" AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT -WATER PIPES. 7. ALUMINUM CONDUIT WILL NOT BE PERMITTED. C. EXPANSION FITTINGS 1. PROVIDE EXPANSION FITTINGS AS FOLLOWS: a. IN CONDUIT RUNS CROSSING EXPANSION JOINTS IN THE STRUCTURE. 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS ON EACH UNIT OF EQUIPMENT, INSTALL UNIQUE DESIGNATION LABEL THAT IS CONSISTENT WITH WIRING DIAGRAMS, SCHEDULES, AND THE OPERATION AND MAINTENANCE MANUAL. IDENTIFICATION SHALL BE SELF- ADHESIVE ENGRAVED, LAMINATED ACRYLIC OR MELAMINE LABEL. UNLESS OTHERWISE INDICATED, PROVIDE A SINGLE LINE OF TEXT WITH 1/2 -INCH- HIGH LETTERS ON 1 -1/2- INCH -HIGH LABEL; WHERE TWO LINES OF TEXT ARE REQUIRED, USE LABELS 2 INCHES HIGH. WHERE EQUIPMENT IS ADDED IN EXISTING INSTALLATIONS, NEW LABEL SHALL MATCH EXISTING TYPE. --- ----- Iamhenoa Nstas C! Step3 Attach Inc tower braclel and clamp using the same n,ethud as the upper bracket and clamp See Step I for inoro information The lower breclet doe, not require a swing arm Figure 7 Atbcbing Mounting Brackets to Pole c Mounting the Antenna to Pole Brackets The antenna has studs onto which you attach th; antenna brackets. The top antenna bracket attaches to tine adjustable pole bracket (with the swmr urmI at the top of the pole Follow these steps to attach the antenna to the antenna brackets and to the assembled pole brackets (See Figure ^_): Step 1 Position the antenna so that the arunv on the onentation label is pointed up The snow points to (he top of we antenna se that it can he installed correctly. IkA-- - NOtt The orlenWUUn label 16 looted oil lbe bail panel of the antenna. Step 2 Attach th, antenna JiMketS to the lop auJ bonoln set of studs located on the ant,rtriz Atach thr breads using . 114 In flat washer, o 114 in lock washer. and a 114 in - 20 hex nut Use a 7116 in picket of Nlel i'll to ughtcn the nuts Po not ocemghten (torque 5 4 to 5 9 nm ) Cisco Aironat 17 -dai Sau" Antanne (AIR- ANT5117S -Nr )a- 15101 �edaW pecihutians - T Technical Specifications Antenna I pe 90- degrr: sector -I /�yyam� 00 rn T M r-- C r M N U- _�.�.. 49(X1 - 5E50 A71117 II j I c Mounting the Antenna to Pole Brackets The antenna has studs onto which you attach th; antenna brackets. The top antenna bracket attaches to tine adjustable pole bracket (with the swmr urmI at the top of the pole Follow these steps to attach the antenna to the antenna brackets and to the assembled pole brackets (See Figure ^_): Step 1 Position the antenna so that the arunv on the onentation label is pointed up The snow points to (he top of we antenna se that it can he installed correctly. IkA-- - NOtt The orlenWUUn label 16 looted oil lbe bail panel of the antenna. Step 2 Attach th, antenna JiMketS to the lop auJ bonoln set of studs located on the ant,rtriz Atach thr breads using . 114 In flat washer, o 114 in lock washer. and a 114 in - 20 hex nut Use a 7116 in picket of Nlel i'll to ughtcn the nuts Po not ocemghten (torque 5 4 to 5 9 nm ) Cisco Aironat 17 -dai Sau" Antanne (AIR- ANT5117S -Nr )a- 15101 �edaW pecihutians - T Technical Specifications Antenna I pe 90- degrr: sector -I /�yyam� 00 rn T M r-- C r M N Operating frequency range 49(X1 - 5E50 A71117 ^c off ° -o Nomnal Input impedance 1.io 0 0 0 Z OT�L `o -oi 2I VS%4kbandwidth 49C)G- 5850 1,11-1Z ' ; _ Gain(d3i) u -- '�' r �7 LE Polarisation Vernul � - Aumu:h plane 3 -0 ,90 degrees U t nea•nwrJtt, j � ! czf ---- t G1eva:ron plane 3 -dB 5.5 degrees ( ' d- bcau,width W N L.cngt9 °3 7 to (62.73 cnt) _o CE I : 4A M Y U 3 Q7 0 L3o-'C x.75 to 0 cn" I O M V Dtrtb Weight 12 Pis (0.9 kg) j IStaudatd ! Corn« uu type N.fcli, Operating temperature ' 111. 185 F ' ( -40 85 C) - niph \'r•tnt' rattnl- ,125 ('01 klnh) A2lmuth Riedlatlon Pattern jFlasauon Rodlaliun Pattern tic •: '� � r I rfa Ciscs Aarao117.dat S.cim Antsana MR- ANTSIITS -N1 _ It t�• �11 °� &19a53i1 1 Slop 3 Attach the IoP autemta hreckct to the id ' lustable pole bracket la:altJ at the top of li -e pelt H rh an appropriate sucker or wrench, attach Me antenna bread using a 1,4 Jr. 20 3 3 u,. hex 1 caJ bolt a 114 to flat washer a 114'n IoLk wasnet, and a 114 to - 20 hex nut on c:uh side ni the rrac arc a Use a 7116 in socket of wrench 1„ Capture 111, bra head hnit while you tighur, me nu . b Du not completely ughtcn Ill. nun lturquc the bolts to 7 k w 8 1 rm) See Figure 2 for a wsuat dtsplzy of 111'5 pnrceu Figure Z Mounting Antenna Brackets to Polo Brackets oil la. I_ II I I I ;II I I 1 J 'T `6 , 1 I Antenna bracket 6 Antenna -- _- 2 11!4-20 nut, fl at and lock wush.r Iturq,ie 5 3 to 5 9 urn)- 7 Ill »•2G bolt. flat washer, anJ lock ausPc'r - 3- ,l rUrackn - -- !a IU-cri,racket - -- - - -- - 4 Clamp _- - -. - - - 1 -'-n't -- -- - - - -- 5 ISwing ant, -- _ --- _. - ---- Coco !ironer 17 -dBt Senor Alumna JAI "- ANT51175 -NI _ - -_ -- 781ea54a1 u /, 1 ,11 I'I�' ^``•fit ', � "7 ,0, _ M 00- 1: 1X7 N /�yyam� 00 rn T M r-- C r M N � 0 � Tv. f-- ^c off ° -o v C3 c .` Q 0 0 0 Z OT�L `o -oi -4- °° ' L oM � V)w _ 0°' r �7 LE acre r - L2-6 o U m C o L U czf ---- E La) C8,- ,_ .4 o U d u ai in Cr N W _o CE 4A M Y U 3 Q7 0 L3o-'C tn3 O M V N . k ' r��im Nt ,.. M: F. Garcia, ,fi E. •-, 5ta e�of_ Flofidd" 24221 z 0 la_t Q 0 J Q f-- CL Q 02/15/13 O w -4- = Z Checked M.F.G. Q :�e Cie Q 5 a 8� r1 3� g "pX �a �g o� K b , LL 0 E a z Date 02/15/13 Scale As Shown Designed M.F.G. Drawn D. R. Checked M.F.G. Sheet E1.0