14-184R-006
D BATTERY CALCULATION - RELEASING PANEL - NOTIFIRE RP -2001 Device Type Qty. Standby / Device (Amp) Alarm / Device (Amp) Total Standby Current (Amp) Total Alarm Current (Amp) Main Circuit Board 1 0.09500 0.22100 0.095000 0.221000 0 0.00000 0.00000 0.000000 0.00000 2 - Wire Smoke Detector 2 0.00005 0.13000 0.000100 0.2600 0.0000 0.000000 OUT # I 1 0.0000 0.000000 OUT # 2 / Releasing Solenoid 1 0.3640 0.364000 OUT # 3 1 0.0000 0.000000 OUT # 4 1 0.0000 0.000000 . Totals 0.095100 0.845000 A/H Required 5tandby Time (24 Hours) 2,282400 A/H Required Alarm Time (5 Minutes) 0.0709810 5ub Total 5tandby / Alarm (Amp / Hr5) 2,353380 Multiply by the derating Factor (1.2) 2.82 USE BATTERY 51ZE 4.0 A/H BATTERY CALCULATION - FACP - NOTIFIRE NFW2 -100 Device Type Qt,. Standby / Device Alarm / Device Total Standby Total Alarm Current (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.14500 0.27500 0.145000 0.275000 ANN -80 Remote Annunciator 1 0.03700 0.04000 0.037000 0.040000 FDU -80 Remote Annunciator 0 0.02500 0.06400 0.000000 0.000000 NP -100 Smoke Detector 11 0.00030 0.003300 NOT -BG 12LX Pull Station 6 0.00023 0.001380 NH- 100 - Heat Detector 4 0.00030 0.001200 DNR- I DO Duct Detector 1 0.00030 0.000300 NMM- I OOP Monitor Module 30 0.00038 0.011400 NC- I OOR Control Relay 12 0.00027 0.003240 ALL Addre55able devices 1 0.40000 0.40000 NAC # 1 1 1.1700 1.170000 NAC # 2 1 1.7350 1.735000 NAC # 3 1 1.8800 1.880000 NAC # 4 1 0.0120 0.012000 Totals 0.202820 5.512000 A/H Required 5tandby 4,867680 Time (24 Hours) A/H Required Alarm 0.463008 Time (5 Minutes) Sub Total Standby / 5.330688 Alarm (Amp / Hrs) Multiply by the 6.40 derating Factor (1.2) USE BATTERY SIZE 7.0 A/H FAI BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY # I Device Type Qt,. Standby / Device Alarm / Device Total Standby Total Alarm Current (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5upervi5ion Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 0.572 0.572000 14AC / Output #2 1 0.921 0.921000 AC / Output #3 1 0.573 0.573000 AC / Output #4 1 0.745 0.745000 Totals 0.065000 2.956000 A/H required Standby 1.560000 Time (24 Hours) AA1 required Alarm 0.248304 Time (5 Minutes) 5ub Total Standby / 1.8083 Alarm (Amp/ Hrs) Multiply by the 217 Derating factor (1.2) U5E BATTERY SIZE 4.0 A/H D BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY #2 Device Type Qty. Standby / Device Alarm / Device Total Standby Total Alarm Current (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5uperw5ion Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 1.341 1.341000 AC / Output #2 1 1.039 1.039000 AC / Output #3 1 1.246 1.246000 AC / Output #4 1 0.000 0.000000 Totals 0.065000 3.771000 A/H required Standby 1.560000 Time (24 Hours) AJH required Alarm 0.316764 Time (5 Minutes) Sub Total Standby / 1.8768 Alarm (Amp/ Hm) Multiply by the 2.25 berating factor (1.2) USE BATTERY SIZE 4.0 A/H F.A.C.P. - VOLTAGE DROP CALCULATION - NFW2 -100 Vd= 2 x D(Ft) x DC Res15t(Ohm/ft) x I(Amp) Circuit Descr ption Maximum Load Cur(Antpj ad Voltage Volt�nge WirAe�Gj e DC(O sm/Ft)ce DI(tFatjce Voltage Voltage Drop Voltage NAC I 1.170 - 310 20.4 0926TTIT 1B.17 2,5 1.735 - 4 250 •4 2.5 1.722 - 280 2,5 0.012 - 150 6.0 oLENAC2 FAI BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY # I Device Type Qt,. Standby / Device Alarm / Device Total Standby Total Alarm Current (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5upervi5ion Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 0.572 0.572000 14AC / Output #2 1 0.921 0.921000 AC / Output #3 1 0.573 0.573000 AC / Output #4 1 0.745 0.745000 Totals 0.065000 2.956000 A/H required Standby 1.560000 Time (24 Hours) AA1 required Alarm 0.248304 Time (5 Minutes) 5ub Total Standby / 1.8083 Alarm (Amp/ Hrs) Multiply by the 217 Derating factor (1.2) U5E BATTERY SIZE 4.0 A/H D BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY #2 Device Type Qty. Standby / Device Alarm / Device Total Standby Total Alarm Current (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5uperw5ion Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 1.341 1.341000 AC / Output #2 1 1.039 1.039000 AC / Output #3 1 1.246 1.246000 AC / Output #4 1 0.000 0.000000 Totals 0.065000 3.771000 A/H required Standby 1.560000 Time (24 Hours) AJH required Alarm 0.316764 Time (5 Minutes) Sub Total Standby / 1.8768 Alarm (Amp/ Hm) Multiply by the 2.25 berating factor (1.2) USE BATTERY SIZE 4.0 A/H F.A.C.P. - VOLTAGE DROP CALCULATION - NFW2 -100 Vd= 2 x D(Ft) x DC Res15t(Ohm/ft) x I(Amp) Circuit Descr ption Maximum Load Cur(Antpj ad Voltage Volt�nge WirAe�Gj e DC(O sm/Ft)ce DI(tFatjce Voltage Voltage Drop Voltage NAC I 1.170 - 310 20.4 0926TTIT 1B.17 2,5 1.735 - 4 250 •4 2.5 1.722 - 280 2,5 0.012 - 150 6.0 oLENAC2 D BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY #2 Device Type Qty. Standby / Device Alarm / Device Total Standby Total Alarm Current (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5uperw5ion Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 1.341 1.341000 AC / Output #2 1 1.039 1.039000 AC / Output #3 1 1.246 1.246000 AC / Output #4 1 0.000 0.000000 Totals 0.065000 3.771000 A/H required Standby 1.560000 Time (24 Hours) AJH required Alarm 0.316764 Time (5 Minutes) Sub Total Standby / 1.8768 Alarm (Amp/ Hm) Multiply by the 2.25 berating factor (1.2) USE BATTERY SIZE 4.0 A/H F.A.C.P. - VOLTAGE DROP CALCULATION - NFW2 -100 Vd= 2 x D(Ft) x DC Res15t(Ohm/ft) x I(Amp) Circuit Descr ption Maximum Load Cur(Antpj ad Voltage Volt�nge WirAe�Gj e DC(O sm/Ft)ce DI(tFatjce Voltage Voltage Drop Voltage NAC I 1.170 - 310 20.4 0926TTIT 1B.17 2,5 1.735 - 4 250 •4 2.5 1.722 - 280 2,5 0.012 - 150 6.0 oLENAC2 F.A.C.P. - VOLTAGE DROP CALCULATION - NFW2 -100 Vd= 2 x D(Ft) x DC Res15t(Ohm/ft) x I(Amp) Circuit Descr ption Maximum Load Cur(Antpj ad Voltage Volt�nge WirAe�Gj e DC(O sm/Ft)ce DI(tFatjce Voltage Voltage Drop Voltage NAC I 1.170 - 310 20.4 0926TTIT 1B.17 2,5 1.735 - 4 250 •4 2.5 1.722 - 280 2,5 0.012 - 150 6.0 oLENAC2 A P5-1 - VOLTAGE DROP CALCULATION - FCP5 -2458 Vd= 2 x D(Ft) x DC Re5mt(Ohm/ft) x I(Amp) Maximum Load Cur(e) ad Volt( Size DCRht)ce DI(;ce IVoltage Drop De5cr pt on (p Amp VOlt5) (AWG) (Orrrvf ft Voltage Voltage NAG I 0.572 435 NAG 2 3.0 0.921 - 33 0.00307 NAC 3 3.0 0.573 16 - 305 NAC 4 3.0 0.745 16 - 395 20.4 1.806848 18.59 TOTAL5 8.0 P5-2 - VOLTAGE DROP CALCULATION - FC175 -2458 Vd= 2 x D(Ft) x DC Re515t(Ohm/ft) x I(Amp) Circuit Maximum Load Current Load Voltage Range Wire Size DC Resistance D15tance Starting Voltage Drop Ending Description (Amp) (Amp) (Volts) (AWG) (Ohm/Pt) (Ft) Voltage Voltage NAC 1 1.341 - 395 20.4 3.252327 1715 NAG 2 3.0 1.039 - 33 14 0.00307 300 20.4 1,913838 18.49 NAC 3 3.0 1.246 16 - 33 14 0.00307 300 .4 NAC 4 3.0 0.000 - U.UUUUUU 20.40 TOTALS 8.0 CABLE USES AND PERMITTED SUBSTITUTIONS FOR POWER- LIMITED FIRE ALARM CABLES 7771 CABLE TYPE USE REFERENCES PERMITTED SUBSTITUTIONS FPLP POWER- LIMITED FIRE ALARM PLENUM CABLE 760.61 (A) CMP FPLR POWER- LIMITED FIRE ALARM RISER CABLE 760.61 (B) CMP, FPLP, CMR FPL POWER- LIMITED FIRE ALARM CABLE 760.61 (C) CMP, FPLP, CMR, FPLR, CMG, CM 2 3 SCOPE OF WORK IN5TALLATION OF NEW FIRE ALARM 5Y5TEM No. Devices Description I Fire Alarm Control Panel 2 Fire Control Power Supply I Remote Annunciator I I Smoke Detector 6 Heat Detector 12 Pull Station 30 Monitor Module 12 Control Relay 27 Horn/Strobe 44 Strobe Light I Sprinkler Bell 1 Duct Detector I Pre - Action System connection 'k 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER U'AITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCT(RS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS. PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL' 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN S -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L LISTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY MATH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE'. D NFPA 101, 2009 EDITION, 'UFE SAFE CODE'. E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE ". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT'" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 18. CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A 'CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. jQ.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. FIRE ALARM LEGEND 5 mbol De5crlptnon Model Manufacturer CONTROL PANEL FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER FCP5- FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIFIER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER PACE PRE- ACTION CONTROL PANEL RP2001 NOTIFIER SO SOLENOID VALVE 753 -E VICTAULIC INITIATION DEVICE5 WP © PULL STATION (weatherproof) NBG- 12LO13 NOTIFIER © ADDRESSABLE PULL STATION NOT-13G 12LX NOTIMER O2 ADDRESSABLE SMOKE DETECTOR NP -100 NOTIFIER l ADDRESSABLE HEAT DETECTOR AH -100 NOTIFIER 0 ADDRESSABLE MONITOR MODULE NMM- I OOP NOTIFIER WP O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® ADDRESSABLE CONTROL RELAY NC- I OOR NOTIFIER D ADDRESSABLE DUCT DETECTOR D N R. NOTIFIER CONVENTIONAL SMOKE DETECTOR 2W -13 SYSTEM SENSOR PS PRESSURE SWITCH BY OTHERS BY OTHERS @- TAMPER SWITCH BY OTHERS BY OTHERS O� FLOW SWITCH BY OTHERS BY OTHERS MAG MAGNETIC DOOR HOLDER BY OTHERS BY OTHERS NOTIFICATION DEVICES, WP HORN/STROBE (weatherproof -wall) P2RK SYSTEM SENSOR ®Q HORN/STROBE (wall) P2R SYSTEM SENSOR WF ® STROBE LIGHT (weatherproof -wall) 5(K SYSTEM SENSOR ® STROBE LIGHT (wall / ceiling) 5R / 5RC SYSTEM SENSOR OR SPRINKLER BELL MBA -G -24 AMSECO / POTTER r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 oLENAC2 A P5-1 - VOLTAGE DROP CALCULATION - FCP5 -2458 Vd= 2 x D(Ft) x DC Re5mt(Ohm/ft) x I(Amp) Maximum Load Cur(e) ad Volt( Size DCRht)ce DI(;ce IVoltage Drop De5cr pt on (p Amp VOlt5) (AWG) (Orrrvf ft Voltage Voltage NAG I 0.572 435 NAG 2 3.0 0.921 - 33 0.00307 NAC 3 3.0 0.573 16 - 305 NAC 4 3.0 0.745 16 - 395 20.4 1.806848 18.59 TOTAL5 8.0 P5-2 - VOLTAGE DROP CALCULATION - FC175 -2458 Vd= 2 x D(Ft) x DC Re515t(Ohm/ft) x I(Amp) Circuit Maximum Load Current Load Voltage Range Wire Size DC Resistance D15tance Starting Voltage Drop Ending Description (Amp) (Amp) (Volts) (AWG) (Ohm/Pt) (Ft) Voltage Voltage NAC 1 1.341 - 395 20.4 3.252327 1715 NAG 2 3.0 1.039 - 33 14 0.00307 300 20.4 1,913838 18.49 NAC 3 3.0 1.246 16 - 33 14 0.00307 300 .4 NAC 4 3.0 0.000 - U.UUUUUU 20.40 TOTALS 8.0 CABLE USES AND PERMITTED SUBSTITUTIONS FOR POWER- LIMITED FIRE ALARM CABLES 7771 CABLE TYPE USE REFERENCES PERMITTED SUBSTITUTIONS FPLP POWER- LIMITED FIRE ALARM PLENUM CABLE 760.61 (A) CMP FPLR POWER- LIMITED FIRE ALARM RISER CABLE 760.61 (B) CMP, FPLP, CMR FPL POWER- LIMITED FIRE ALARM CABLE 760.61 (C) CMP, FPLP, CMR, FPLR, CMG, CM 2 3 SCOPE OF WORK IN5TALLATION OF NEW FIRE ALARM 5Y5TEM No. Devices Description I Fire Alarm Control Panel 2 Fire Control Power Supply I Remote Annunciator I I Smoke Detector 6 Heat Detector 12 Pull Station 30 Monitor Module 12 Control Relay 27 Horn/Strobe 44 Strobe Light I Sprinkler Bell 1 Duct Detector I Pre - Action System connection 'k 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER U'AITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCT(RS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS. PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL' 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN S -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L LISTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY MATH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE'. D NFPA 101, 2009 EDITION, 'UFE SAFE CODE'. E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE ". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT'" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 18. CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A 'CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. jQ.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. FIRE ALARM LEGEND 5 mbol De5crlptnon Model Manufacturer CONTROL PANEL FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER FCP5- FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIFIER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER PACE PRE- ACTION CONTROL PANEL RP2001 NOTIFIER SO SOLENOID VALVE 753 -E VICTAULIC INITIATION DEVICE5 WP © PULL STATION (weatherproof) NBG- 12LO13 NOTIFIER © ADDRESSABLE PULL STATION NOT-13G 12LX NOTIMER O2 ADDRESSABLE SMOKE DETECTOR NP -100 NOTIFIER l ADDRESSABLE HEAT DETECTOR AH -100 NOTIFIER 0 ADDRESSABLE MONITOR MODULE NMM- I OOP NOTIFIER WP O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® ADDRESSABLE CONTROL RELAY NC- I OOR NOTIFIER D ADDRESSABLE DUCT DETECTOR D N R. NOTIFIER CONVENTIONAL SMOKE DETECTOR 2W -13 SYSTEM SENSOR PS PRESSURE SWITCH BY OTHERS BY OTHERS @- TAMPER SWITCH BY OTHERS BY OTHERS O� FLOW SWITCH BY OTHERS BY OTHERS MAG MAGNETIC DOOR HOLDER BY OTHERS BY OTHERS NOTIFICATION DEVICES, WP HORN/STROBE (weatherproof -wall) P2RK SYSTEM SENSOR ®Q HORN/STROBE (wall) P2R SYSTEM SENSOR WF ® STROBE LIGHT (weatherproof -wall) 5(K SYSTEM SENSOR ® STROBE LIGHT (wall / ceiling) 5R / 5RC SYSTEM SENSOR OR SPRINKLER BELL MBA -G -24 AMSECO / POTTER r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 P5-2 - VOLTAGE DROP CALCULATION - FC175 -2458 Vd= 2 x D(Ft) x DC Re515t(Ohm/ft) x I(Amp) Circuit Maximum Load Current Load Voltage Range Wire Size DC Resistance D15tance Starting Voltage Drop Ending Description (Amp) (Amp) (Volts) (AWG) (Ohm/Pt) (Ft) Voltage Voltage NAC 1 1.341 - 395 20.4 3.252327 1715 NAG 2 3.0 1.039 - 33 14 0.00307 300 20.4 1,913838 18.49 NAC 3 3.0 1.246 16 - 33 14 0.00307 300 .4 NAC 4 3.0 0.000 - U.UUUUUU 20.40 TOTALS 8.0 CABLE USES AND PERMITTED SUBSTITUTIONS FOR POWER- LIMITED FIRE ALARM CABLES 7771 CABLE TYPE USE REFERENCES PERMITTED SUBSTITUTIONS FPLP POWER- LIMITED FIRE ALARM PLENUM CABLE 760.61 (A) CMP FPLR POWER- LIMITED FIRE ALARM RISER CABLE 760.61 (B) CMP, FPLP, CMR FPL POWER- LIMITED FIRE ALARM CABLE 760.61 (C) CMP, FPLP, CMR, FPLR, CMG, CM 2 3 SCOPE OF WORK IN5TALLATION OF NEW FIRE ALARM 5Y5TEM No. Devices Description I Fire Alarm Control Panel 2 Fire Control Power Supply I Remote Annunciator I I Smoke Detector 6 Heat Detector 12 Pull Station 30 Monitor Module 12 Control Relay 27 Horn/Strobe 44 Strobe Light I Sprinkler Bell 1 Duct Detector I Pre - Action System connection 'k 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER U'AITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCT(RS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS. PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL' 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN S -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L LISTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY MATH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE'. D NFPA 101, 2009 EDITION, 'UFE SAFE CODE'. E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE ". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT'" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 18. CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A 'CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. jQ.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. FIRE ALARM LEGEND 5 mbol De5crlptnon Model Manufacturer CONTROL PANEL FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER FCP5- FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIFIER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER PACE PRE- ACTION CONTROL PANEL RP2001 NOTIFIER SO SOLENOID VALVE 753 -E VICTAULIC INITIATION DEVICE5 WP © PULL STATION (weatherproof) NBG- 12LO13 NOTIFIER © ADDRESSABLE PULL STATION NOT-13G 12LX NOTIMER O2 ADDRESSABLE SMOKE DETECTOR NP -100 NOTIFIER l ADDRESSABLE HEAT DETECTOR AH -100 NOTIFIER 0 ADDRESSABLE MONITOR MODULE NMM- I OOP NOTIFIER WP O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® ADDRESSABLE CONTROL RELAY NC- I OOR NOTIFIER D ADDRESSABLE DUCT DETECTOR D N R. NOTIFIER CONVENTIONAL SMOKE DETECTOR 2W -13 SYSTEM SENSOR PS PRESSURE SWITCH BY OTHERS BY OTHERS @- TAMPER SWITCH BY OTHERS BY OTHERS O� FLOW SWITCH BY OTHERS BY OTHERS MAG MAGNETIC DOOR HOLDER BY OTHERS BY OTHERS NOTIFICATION DEVICES, WP HORN/STROBE (weatherproof -wall) P2RK SYSTEM SENSOR ®Q HORN/STROBE (wall) P2R SYSTEM SENSOR WF ® STROBE LIGHT (weatherproof -wall) 5(K SYSTEM SENSOR ® STROBE LIGHT (wall / ceiling) 5R / 5RC SYSTEM SENSOR OR SPRINKLER BELL MBA -G -24 AMSECO / POTTER r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 CABLE USES AND PERMITTED SUBSTITUTIONS FOR POWER- LIMITED FIRE ALARM CABLES 7771 CABLE TYPE USE REFERENCES PERMITTED SUBSTITUTIONS FPLP POWER- LIMITED FIRE ALARM PLENUM CABLE 760.61 (A) CMP FPLR POWER- LIMITED FIRE ALARM RISER CABLE 760.61 (B) CMP, FPLP, CMR FPL POWER- LIMITED FIRE ALARM CABLE 760.61 (C) CMP, FPLP, CMR, FPLR, CMG, CM 2 3 SCOPE OF WORK IN5TALLATION OF NEW FIRE ALARM 5Y5TEM No. Devices Description I Fire Alarm Control Panel 2 Fire Control Power Supply I Remote Annunciator I I Smoke Detector 6 Heat Detector 12 Pull Station 30 Monitor Module 12 Control Relay 27 Horn/Strobe 44 Strobe Light I Sprinkler Bell 1 Duct Detector I Pre - Action System connection 'k 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER U'AITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCT(RS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS. PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL' 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN S -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L LISTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY MATH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE'. D NFPA 101, 2009 EDITION, 'UFE SAFE CODE'. E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE ". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT'" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 18. CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A 'CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. jQ.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. FIRE ALARM LEGEND 5 mbol De5crlptnon Model Manufacturer CONTROL PANEL FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER FCP5- FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIFIER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER PACE PRE- ACTION CONTROL PANEL RP2001 NOTIFIER SO SOLENOID VALVE 753 -E VICTAULIC INITIATION DEVICE5 WP © PULL STATION (weatherproof) NBG- 12LO13 NOTIFIER © ADDRESSABLE PULL STATION NOT-13G 12LX NOTIMER O2 ADDRESSABLE SMOKE DETECTOR NP -100 NOTIFIER l ADDRESSABLE HEAT DETECTOR AH -100 NOTIFIER 0 ADDRESSABLE MONITOR MODULE NMM- I OOP NOTIFIER WP O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® ADDRESSABLE CONTROL RELAY NC- I OOR NOTIFIER D ADDRESSABLE DUCT DETECTOR D N R. NOTIFIER CONVENTIONAL SMOKE DETECTOR 2W -13 SYSTEM SENSOR PS PRESSURE SWITCH BY OTHERS BY OTHERS @- TAMPER SWITCH BY OTHERS BY OTHERS O� FLOW SWITCH BY OTHERS BY OTHERS MAG MAGNETIC DOOR HOLDER BY OTHERS BY OTHERS NOTIFICATION DEVICES, WP HORN/STROBE (weatherproof -wall) P2RK SYSTEM SENSOR ®Q HORN/STROBE (wall) P2R SYSTEM SENSOR WF ® STROBE LIGHT (weatherproof -wall) 5(K SYSTEM SENSOR ® STROBE LIGHT (wall / ceiling) 5R / 5RC SYSTEM SENSOR OR SPRINKLER BELL MBA -G -24 AMSECO / POTTER r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 2 3 SCOPE OF WORK IN5TALLATION OF NEW FIRE ALARM 5Y5TEM No. Devices Description I Fire Alarm Control Panel 2 Fire Control Power Supply I Remote Annunciator I I Smoke Detector 6 Heat Detector 12 Pull Station 30 Monitor Module 12 Control Relay 27 Horn/Strobe 44 Strobe Light I Sprinkler Bell 1 Duct Detector I Pre - Action System connection 'k 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER U'AITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCT(RS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS. PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL' 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN S -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L LISTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY MATH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE'. D NFPA 101, 2009 EDITION, 'UFE SAFE CODE'. E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE ". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT'" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 18. CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A 'CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. jQ.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. FIRE ALARM LEGEND 5 mbol De5crlptnon Model Manufacturer CONTROL PANEL FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER FCP5- FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIFIER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER PACE PRE- ACTION CONTROL PANEL RP2001 NOTIFIER SO SOLENOID VALVE 753 -E VICTAULIC INITIATION DEVICE5 WP © PULL STATION (weatherproof) NBG- 12LO13 NOTIFIER © ADDRESSABLE PULL STATION NOT-13G 12LX NOTIMER O2 ADDRESSABLE SMOKE DETECTOR NP -100 NOTIFIER l ADDRESSABLE HEAT DETECTOR AH -100 NOTIFIER 0 ADDRESSABLE MONITOR MODULE NMM- I OOP NOTIFIER WP O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® ADDRESSABLE CONTROL RELAY NC- I OOR NOTIFIER D ADDRESSABLE DUCT DETECTOR D N R. NOTIFIER CONVENTIONAL SMOKE DETECTOR 2W -13 SYSTEM SENSOR PS PRESSURE SWITCH BY OTHERS BY OTHERS @- TAMPER SWITCH BY OTHERS BY OTHERS O� FLOW SWITCH BY OTHERS BY OTHERS MAG MAGNETIC DOOR HOLDER BY OTHERS BY OTHERS NOTIFICATION DEVICES, WP HORN/STROBE (weatherproof -wall) P2RK SYSTEM SENSOR ®Q HORN/STROBE (wall) P2R SYSTEM SENSOR WF ® STROBE LIGHT (weatherproof -wall) 5(K SYSTEM SENSOR ® STROBE LIGHT (wall / ceiling) 5R / 5RC SYSTEM SENSOR OR SPRINKLER BELL MBA -G -24 AMSECO / POTTER r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 'k 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER U'AITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCT(RS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS. PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL' 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN S -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L LISTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY MATH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE'. D NFPA 101, 2009 EDITION, 'UFE SAFE CODE'. E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE ". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT'" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 18. CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A 'CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. jQ.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. FIRE ALARM LEGEND 5 mbol De5crlptnon Model Manufacturer CONTROL PANEL FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER FCP5- FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIFIER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER PACE PRE- ACTION CONTROL PANEL RP2001 NOTIFIER SO SOLENOID VALVE 753 -E VICTAULIC INITIATION DEVICE5 WP © PULL STATION (weatherproof) NBG- 12LO13 NOTIFIER © ADDRESSABLE PULL STATION NOT-13G 12LX NOTIMER O2 ADDRESSABLE SMOKE DETECTOR NP -100 NOTIFIER l ADDRESSABLE HEAT DETECTOR AH -100 NOTIFIER 0 ADDRESSABLE MONITOR MODULE NMM- I OOP NOTIFIER WP O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® ADDRESSABLE CONTROL RELAY NC- I OOR NOTIFIER D ADDRESSABLE DUCT DETECTOR D N R. NOTIFIER CONVENTIONAL SMOKE DETECTOR 2W -13 SYSTEM SENSOR PS PRESSURE SWITCH BY OTHERS BY OTHERS @- TAMPER SWITCH BY OTHERS BY OTHERS O� FLOW SWITCH BY OTHERS BY OTHERS MAG MAGNETIC DOOR HOLDER BY OTHERS BY OTHERS NOTIFICATION DEVICES, WP HORN/STROBE (weatherproof -wall) P2RK SYSTEM SENSOR ®Q HORN/STROBE (wall) P2R SYSTEM SENSOR WF ® STROBE LIGHT (weatherproof -wall) 5(K SYSTEM SENSOR ® STROBE LIGHT (wall / ceiling) 5R / 5RC SYSTEM SENSOR OR SPRINKLER BELL MBA -G -24 AMSECO / POTTER r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 r� System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C 1B �r A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) gale steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark n No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM sq ft W- Rating - Class 1 (See Item 4) Section A -A 1. Floor or wall Assembly- Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. C114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow con: Precas� oncrete Units *. when lour i constucted of hollow core recast concrete lilts packing m.�{erial (Item ,1 and caulk fill material item 4� to be installed mebical�r on both sides of f %or, flush with flor surface. Wall assembly may also be constucted of any U�Classlfie�a i=rate Blocks *. Max dram of opening in solid lightweight or normal weight concrete floor is 32 in (813mmMax diam of opening in floor constructed of See Concrete Blocks (CA and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 1A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mmnl above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop soem.Max annular space be between pipe, conduit or tubing and a of through opening or sleeve is dependent on the parameters shown in Item 4.Min annular space between Ape or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4 conduit cordut or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and saes of metallic pipes, conduits or tubing may W used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam or smaller) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm3 diam (or smaller) steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier) copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier ) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass ft insulation firl mto oPer ing permanent foml.Padang material to b)e recessed from top dace of a fro both surfaces of wall as required �o accommodate the required thickness of caulk fill' materiaitem 4 3A.Formin Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min j,2 in13mm) thick compressble mat to be stacked to a thi greater than the width ad the annuls spa an �g{an�optio{n�, the strips of min 11 f 2 in rl3' Z kconia� fitted, eairst;� inepm�n space �O a rtan kmth(�1 rt�xnhg Top of fig r�to be ire ud ran top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or Material - Caulk, Sealant-Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thin to be installed Wmetriwk on both sides of wd flush with wall surface. At point contact location between 4enetront and sleeve or betwween penetrant and concxe% c min 1%4 in.(6mm) diam bead of caulk shall be applied ast surface of fba and at bath surfaces of wal. The howdy F mfiV and the min regwed caul= thkkre es are dependent upon a number parameters as shown in the following table: Min Floor or Wall Nom Pi Tube or Max Annular 1y�in u F Thkns In (mm) Conduit Diam In (mm) Space In. (mm) Thk►is In mm) Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /213) 2 2-1Z2 643 1 /2 -12� 13 -3053 3-1Z4 83 �1�2 2 4 -1/2 114 1/2- 613 -152 1 -3/8 35 1S )Q) 2 4 -1/2 114 1/2 -1 13 -30 1 -1/ 4 32 L1 J 3 4 -1 /2 114 1 /2 -20 13 -508 2 (51 2 3 4 -1 /2 114 1 /2 -20 13 -508 2((((((51 1 25 3 4-1Z2 114 1 2 -1 13 -305 3-1/4 83) K2� 3 4 -1/2 114 2 -30 58 -76 2 1 1 3 5 -1 /2 140 1 2- 6113 -152) 1 -3�8 35) 1 4 ((a Min 2 in.(51mm) thickness of mineral wool baU insulation of forming material (Item3A) required in annular space (b�Min 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory 0 , � 1• J f r� it 1,.A' Ems+ Gi- e'll il�E Crl :J V-_0 pf �1��SP�- • Y�1�y'i1p fit; WI`s' Il`E IN ACC VD FAM & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL :305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 NOTIFIEW ; by Honeywell amp FM AR'ROMm U`" V_ ENGINEERING: Carlos Rodriguez, P.E. LIC. #G5G87 8101 S.W. 104th 5TREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 W Z U 0 W m L LLJ ILJ m m > � Q _ 0 O G Z nQ Z m� L i� .Onn Q 1, U. N E W Z U Z o W L U Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7 Revisions: Qi 01 .27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision Q3 09.17.20 14 Fire Dpto. Comments drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown FIRE ALARM SYSTEM fA-G sheet G of 7