14-184R-006
FAI BATTERY CALCULATION - FACP - NOTIFIRE NFW2 -100 Device Type city. Standby / Device (Amp) Alarm / Device (Amp) Total Standby Current (Amp) Total Alarm Current (Amp) Main Board 1 0.14500 0.27500 0.145000 0.275000 ANN -80 Remote Annunciator 1 0.03700 0.04000 0.037000 0.040000 FDU -80 Remote Annunciator 0 0.02500 0.06400 0.000000 0.000000 NP -100 Smoke Detector 11 0.00030 20.4 0.003300 AC / Output #2 NOT-15G 12LX Pull Station 6 0.00023 16 - 33 0.001380 AC / Output #3 NH -100 - Heat Detector 4 0.00030 17.42 0.001200 AC / Output #4 DNR -100 Duct Detector 1 0.00030 0.065000 0.000300 20.4 NMM- I OOP Monitor Module 30 0.00038 0.065000 0.011400 WP Ell NC- I OOR Control Relay 9 0.00027 1.560000 0.002430 P2R ALL Addressable devices 1 Time (24 Hours) 0.40000 1.8768 0.40000 NAC # 1 1 A/H required Alarm 1.1700 0.263088 1.170000 NAG # 2 1 Time (5 Mmutes) 1.7350 4.0 A/H 1.735000 NAC # 3 1 1.8800 1.8231 1.880000 NAC # 4 1 0.0120 0.012000 Totals 0.202010 5.512000 AM Required Standby Time (24 Hours) 4,848240 A/H Required Alarm Time (5 Minutes) 4.0 A/H 0.463008 Sub Total Standby/ Alarm (Amp / Hrs) 5.311248 Multiply by the iterating Factor (1.2) 6.37 USE BATTERY SIZE 7.0 A/H FAI "A n BATTERY CALCULATION - NOTIMER FCP5 -2458 - POWER SUPPLY #I Device Type Qt,. Standby / Device Alarm / Device Total Standby Total Alarm Current Main Board 1 (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5upern5ion Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 0.00307 0.572 20.4 0.572000 AC / Output #2 1 2.5 0.921 16 - 33 0.921000 AC / Output #3 1 20.4 0.573 17.42 0.573000 AC / Output #4 1 16 - 33 0.921 0.065000 0.921000 20.4 2.51644U 1 1738 Totals 0.065000 3.132000 WP Ell HORMSTROBE (weatherproof -wall; P2RK AIH required Standby 1.560000 0.316764 P2R SYSTEM SENSOR WP ® Time (24 Hours) Sub Total 5tandby / Alarm (Amp/ Hm) 1.8768 ® STROBE LIGHT (wall / telling) SR/ SRC A/H required Alarm Multiply by the Deratmg factor (1.2) 0.263088 6.0 2.9B7 1 Time (5 Mmutes) USE BATTERY SIZE 4.0 A/H Sub Total Standby / 1.8231 Alarm (Amp/ Hrs) Multiply by the 2,19 Derating factor (1 .2) USE BATTERY SIZE 4.0 A/H BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY #2 Device Type Qt,. Standby / Device (Amp) Alarm / Device (Amp) Total Standby Current (Amp) Total Alarm Current (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power Supervision Relay 0 0.025 0.025 0.0000 0.000000 AC / Output # 1 1 18.17 1.341 2.5 1.341000 AC / Output #2 1 0.00307 1.039 20.4 1.039000 AC / Output #3 1 2.5 1.246 16 - 33 1.246000 AC / Output #4 1 20.4 0.000 17.42 0.000000 2.5 1 0.012 16 - 33 Totals 0.065000 3.771000 20.4 2.51644U 1 1738 AIH required Standby Time (24 Hours) 1.560000 NOTIFICATION DEVICES WP Ell HORMSTROBE (weatherproof -wall; P2RK AM required Alarm Time (5 Minutes) 0.316764 P2R SYSTEM SENSOR WP ® STROBE LIGHT (weatherproof -wall) Sub Total 5tandby / Alarm (Amp/ Hm) 1.8768 ® STROBE LIGHT (wall / telling) SR/ SRC SYSTEM SENSOR Multiply by the Deratmg factor (1.2) 2 25 6.0 2.9B7 1 USE BATTERY SIZE 4.0 A/H F.A.C.P. - VOLTAGE DROP CALCULATION - NFW2 -100 Vd= 2 x D(Ft) x DC Rc5i5t(Ohm/ft) x I(Amp) Circuit Descr ption Maxl(AunmpLoad Current Load Volt(Volt�nge WIAwG)e DC(ROhs�t� ce DI(tFt)ce Volt ge Voltage Drop Endinej NAC I 2.5 1.170 16 - 33 14 0.00307 310 20.4 2.226 18.17 NAC 2 2.5 1.735 16 - 33 14 0.00307 250 20.4 2.663225 17.74 NAC 3 2.5 1.722 16 - 33 14 NOTIFIER 280 20.4 2.960462 17.42 NAC 4 2.5 1 0.012 16 - 33 1 14 1 0.00307 150 20.4 2.51644U 1 1738 DNR NOTINER NOTIFICATION DEVICES WP Ell HORMSTROBE (weatherproof -wall; P2RK SYSTEM SENSOR HORN/5TROBE (wall) P2R SYSTEM SENSOR WP ® STROBE LIGHT (weatherproof -wall) 5 R SYSTEM SENSOR ® STROBE LIGHT (wall / telling) SR/ SRC SYSTEM SENSOR TOTAS5 6.0 2.9B7 1 P5 -1 - VOLTAGE DROP CALCULATION - FCP5 -2458 Vd= 2 x D(Ft) x DC ReSlst(Ohm/ft) x I(Amp) Circuit De5cr ption Maximum Load Current Ampjoad Volt(Volt5) (AWG)e DC(Ohm/Ft) ce DI(tFt)ce Volt ge Voltage Drop Votage NAC I 3.0 0.572 16 - 33 14 0.00307 295 20.4 _-TUN064 19.36 NAC 2 3.0 0.921 16 - 33 14 0.00307 435 20.4 2.459899 17.94 NAC 3 3.0 0.573 16 - 33 14 NOTIFIER 305 20.4 2.983672 17.42 NAC 4 3.0 0.921 1 16 - 33 1 14 0.00307 445 20.4 2.51644U 1 1738 DNR NOTINER NOTIFICATION DEVICES WP Ell HORMSTROBE (weatherproof -wall; P2RK SYSTEM SENSOR HORN/5TROBE (wall) P2R SYSTEM SENSOR WP ® STROBE LIGHT (weatherproof -wall) 5 R SYSTEM SENSOR ® STROBE LIGHT (wall / telling) SR/ SRC SYSTEM SENSOR TOTALS 8.0 2.9B7 1 P5 -2 - VOLTAGE DROP CALCULATION - FCP5 -2458 Vd= 2 x D(Ft) x DC Reslst(Ohm/ft) x I(Amp) Circuit Descr ption Maximum (Amp)oad Current Amp)ad Volt(Volt5) (AWG) DC(ROhS�F) ce DI(Ft)ce Voltage Voltage Drop Endirlej age NAC I 3.0 1.341 16 - 33 14 0.00307 395 20.4 3.252327 17.15 NAC 2 3.0 1.039 16 - 33 14 0.00307 300 20.4 1.913838 18.49 NAC 3 3.0 1.246 16 - 33 14 NOTIFIER 390 20.4 2.983672 17.42 NAC 4 3.0 0.000 16 - 33 14 0.00307 1 0 NOTIFIER F_ DUCT DETECTOR DNR NOTINER NOTIFICATION DEVICES WP Ell HORMSTROBE (weatherproof -wall; P2RK SYSTEM SENSOR HORN/5TROBE (wall) P2R SYSTEM SENSOR WP ® STROBE LIGHT (weatherproof -wall) 5 R SYSTEM SENSOR ® STROBE LIGHT (wall / telling) SR/ SRC SYSTEM SENSOR TOTALS 8,0 AMSECO / POTTER CABLE USES AND PERMITTED SUBSTITUTIONS FOR POWER- LIMITED FIRE ALARM CABLES CABLE TYPE USE REFERENCES PERMITTED SUBSTITUTIONS FPLP POWER -LIMITED FIRE ALARM PLENUM CABLE 760.61 (A) CMP FPLR POWER -LIMITED FIRE ALARM RISER CABLE 760.61 (B) CMP, FPLP, CMR FPL POWER -UMITED FIRE ALARM CABLE 760.61 (C) CMP, FPLP, CMR, FPLR, CMG, CM "A 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE # 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL HARING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER LIMITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCTORS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE If 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE WITH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - 0 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER (#16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALUC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L. LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL.• 41% OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48- (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN 3' -0' FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80* A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L USTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER UM170 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY WITH: Al FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION 'FIRE CODE -. D NFPA 101, 2009 EDITION, -UFE SAFE CODE'. E NFPA 72, 2007 EDITION - NATIONAL FIRE ALARM CODE -. F) NFPA 70, 2008 EDITION - NATIONAL ELECTRICAL CODE -. 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL. AND SHALL BE IDENTIFIED 'AS FIRE ALARM CIRCUIT' THE LOCATION CF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL 111 CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0' ABOVE THE FINISHED FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY do ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEIUNG HEIGHT: EXCEPT PARKING AREA IS LESS THAN 12 * -0 *. B. THIS SYSTEM WILL BE 'CERTIFIED OR PLACARDED' AS A 'CENTRAL STATION SERVICE' FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION WILL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. ,Q.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E ALL NACs SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. U FIRE ALARM LEGEN D 5 mbol Description IE Model -I Manufacturer CONTROL PANEL 64 FIRE ALARM CONTROL PANEL NFW2 -100 NOTIFIER ® FIRE CONTROL POWER SUPPLY FCP5 -2458 NOTIMER ® REMOTE ANNUNCIATOR N- ANN -80 NOTIFIER 114 1/26(13 -152) 1_3/8 35 1! () g13g 3 INITIATION DEVICES WP © PULL STATION (weatherproof) NBG- 1 21_05 NOTIFIER © PULL STATION NOT-5G 12LX NOTIMER O2 5MOKE DETECTOR NP -100 NOTIFIER 1 HEAT DETECTOR NH -100 NOTIFIER Q MONITOR MODULE NMM- I OOP NOTIFIER O HEAT DETECTOR (weatherproof) 302 ET -135 FIRE LITE ® CONTROL RELAY NC- I COP, NOTIFIER F_ DUCT DETECTOR DNR NOTINER NOTIFICATION DEVICES WP Ell HORMSTROBE (weatherproof -wall; P2RK SYSTEM SENSOR HORN/5TROBE (wall) P2R SYSTEM SENSOR WP ® STROBE LIGHT (weatherproof -wall) 5 R SYSTEM SENSOR ® STROBE LIGHT (wall / telling) SR/ SRC SYSTEM SENSOR SPRINKLER BELL MBA -6 -24 AMSECO / POTTER M System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 1C A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Steel Studs - *C -H' or 'C -T* shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) galv steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diem of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diem (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark Ti No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM /sq ft W- Rating - Class 1 (See Item 4) 1. Floor or wall Assembly Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. (114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow core Precast Concrete Units *. when floor i constucted of hollow core recast oncrete inits packing material (Item 3) and caulk fill material (item 4) to be installed mmetncaI on bJh sides of floor, flush with flor surface. Wall assembly may also be constucted of any UY Class'ifie, Concrete Blocks *. Max diam of opening in solid lightweight or normal weight concrete floor is 32 in (813mm�Max diam of opening in floor constructed of See Concrete Blocks (CA� and Precast Concrete Units (C categories in the Fire Resistance Directory for names of manufacturers. 11A.Steel Sleeve- (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or grouted intQ floor or wall assembly. Sleeve may extend a max of 2 in (51mm) above top of floor or beyond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71 mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccnt4cally within the fire stop system.Max annular space be between pipe, conduit or tubing and edge of through opening or sleeve is d ent on the rometers shown in item 4.Min annular between pipe or conduit and of through i is 0 i 'nt contact). Max annular spoke to be as shown in the ttoW in item 4.Pile, conduit or tubing be rigidlyg s on both sides of floor or wall assembly. The following types and sizes of metalric pipes, conduits or tubing may be used: A. Steel Pipe -Nom 30in.(762mm) diam (or amaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in.(762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in.(152mm) diam (or smaller ) rigid steel conduit.. D. Conduit -Nom 4 in.(102mm) diam (or smaller steel electrical metallic tube. E. Copper Tubing -Nom 6in.(152mm) diam (or smaller) Type L or heavier copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular or heavier copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or gloss rise fr ih into openi permankxit form.p rg material to ke recessed from top rface of fkx>r or frw both surfaces of wall as requires �O accommodate the required thickness of caulk &I material llitem 4 3A.Fonnin q Material * -As an altemate to the packing material in Item 3, nom 4 in.(102mm ) wide strips of min 1/2 in 13mm) thick compressible mat to be stacked to a thi greater than the width od a annuk spa an fitted edge -fret, to fal the annular spoor to a min 4 in.) As an optan, the strips of min 1l2 in 1E�3mm� nit to th' g er n the w anrxular a���rl� -le e��rstfo ir�ie�iln'�� � a min 1 is (�1 nm Tap of firmri� materiel fto� recessed nom top su ace of floor or ftrom both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. Fill, Void or C�erial- Caulk, Sealant- Appried to fill annular space flush with the top surface of floor. In wall assembly required caulk to be installed symmetricak on both sides of wit flush with wall surface. At pool contact location between penetrant and sleeve or betwween penetrant and concretes a min 1%4 in.(6mm) diam bead of caulk shall be applied ast toQ surface of floor and at both surfaces of wit The hmrhr F ratings and the min rer*1 kw�k thicknesses are dependent upon a number o parameters as shown in the following table: Min Floor or Wall Nom Pipe Tube or Thkns In (mm) Conduit D1am In (mm) Max Annular Space In. (mm) ,M in out Thkna In r mm) F Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 2 3) 2 2 -1 /2 643 1Z2-12 13 -3053 3 -1 /4 83 2 2 4_1/2 114 1/26(13 -152) 1_3/8 35 1! () g13g 3 4-1 /2 114 172-1 2 13-30 1 1 4 32 1 P.E. 4_1/2 114 1/2 -20 13_508 2 51 5 - 25 3 4-1 /2 114 172-20 13-508 2 1 1 2 Q 4 -1 /2 114 1 2 -1 13 -305 �2- 3 -1 4 83) (1 1 5 3 4 -1/2 5 -1 /2 114 2 -30 58 -76 140 1 6(13 -152) 2 1 -3�8 35) 1 1 �2 �( ) 3 4 ((a Min 2 in.(51mm) thickness of mineral wool batt insulation of forming material (Item3A) required in annular space (b�kin 1 in.(25mm) thickness of mineral wool batt insulation required in annular space of both sides of floor or wall assembly (c)Min 1 in.(25mm) thickness of caulkl to be installed flush with each surface of floor or wall assembly 3M COMPANY- CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fre Resistance Directory REVISED PLANS aR 0 •mil L P M{AM4.40A DE CCE1r, TY :RE 1)EPARTME 8LDG(/ PEPU%V.T/ .._ Ft: n: A i1J.RM , FIRE SUPPAESSI; N. = A) +-i2/}.fAtN• EXT._-,_ FTRE ALARM SYSTEM TO BE (N z! fALLLD IN ACCORDANCE WrM NFPA 72; 70; 101 r iRE ALARM SHALL 13E A CENTRAL ,TATION SRRVICE. A CERTIFICATE )R PLACARD SHALL- BE P06TED AT FINAL INSPECTION, AS PER NFPA 72 "Nw4k viass��l/ ,r . <ti 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL : 305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 01INICTIFIEW W by Honeywell FM AIR11al m 8 10 1 S.W. 104th STREET MIAMI. FLORIDA 33156 PHONE: (786) 390 -8213 W Z U 'r1'' R9 W ENGINEERING m W LU Carlos Rodriguez, P.E. LIC. #65687 8 10 1 S.W. 104th STREET MIAMI. FLORIDA 33156 PHONE: (786) 390 -8213 Revnion5: Qi 01.27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown f RE ALARM SYSTEM fA-G sheet 6 of 7 W Z U W m W LU ~ NO - J LL- 0 Z (n Q Z m2 L Lr) p -� Q O In 11 tJ_ ca M Z W U Z O W L � U Revnion5: Qi 01.27.2014 Plan review comments 0 08. 18.2014 A5 Built Revision drawn by: L.C. date: 07.24..2013 project #: 13 -0724 scale: a5 shown f RE ALARM SYSTEM fA-G sheet 6 of 7