14-184-007ELEVATOR RECALL — Sequence of Operation
A. Smoke Detectors in elevator lobbies, and or elevator machine room shall:
1. Initiate an alarm condition at the panel.
2. Initiate the recall of the elevator cars as follows in accordance with NFPA 72
(2007 edition), Chapter 6.16.3.
B. Phase I recall: Any elevator lobby smoke detector located on floors 2 and above
and /or any smoke detector in the elevator machine or elevator hoistway shall initiate
phase I recall which will bring the elevator car to the 1st floor and lock the doors
in the open position.
C. Phase II recall: Any elevator lobby smoke detector located on the 1st floor shall
initiate recall which will bring the elevator car to the 2nd floor and lock the doors
in the open position.
D. Elevator Warning Signal: Actuation of any elevator machine room smoke detector
or elevator hoistway detector shall also initiate the elevator warning signal to alert
emergency personnel that the elevators are not safe for use as required in NFPA 72
(2007 edition) Chapter 6.16.3.12.3
E. Shunt —Trip Heat Detectors: Heat Detectors dedicated for Elevator Shunt shall be
connected where required and activate a control shunt to disconnect the elevator
power upon activation. The shunt power source shall be monitored by the Fire Ak
Control Panel as required in NFPA 72.
ELEVATOR RECALL WIRING DIAGRAM
(INTELLIGENT SYSTEM
Elevator Machine Room, & Lobby Heat Detectors, Smoke
Detectors, connected to activate Fire Fighter's Service Recall
Al
SEQUENCE OF OPERATION:
SMOKE DETECTOR
Activation of Smoke Detector shall initiate the following functions:
— Generate an audible signal at the Fire Alarm Control Panel
— Generate an audible signal simultaneously on all areas of
the building by means of Horns devices. Generate a visual
alarm signal simultaneously on all areas of the building by
the use of Strobe devices or combination Horn /Strobe
notification device.
— Indicate the location of the Smoke Detector by displaying
the alarmed device and its location on the FACP.
— Transmits a Fire Alarm Signal to the designated U.L.
Certified Central Station.
HEAT DETECTOR
Activation of Heat Detector shall initiate the following functions:
— Generate an audible signal at the Fire Alarm Control Panel
— Generate an audible signal simultaneously on all areas of
the building by means of Horns devices. Generate a visual
alarm signal simultaneously on all areas of the building by
the use of Strobe devices or combination Horn /Strobe
notification device.
— Indicate the location of the Heat Detector by displaying
the alarmed device and its location on the FACP.
— Transmits a Fire Alarm Signal to the designated U.L.
Certified Central Station.
MANUAL FIRE ALARM PULL STATION
Activation of Pull Station shall initiate the following functions:
— Generate an audible signal at the Fire Alarm Control Panel
— Generate an audible signal simultaneously on all areas of
the building by means of Horns devices. Generate a visual
alarm signal simultaneously on all areas of the building by
the use of Strobe devices or combination Horn /Strobe
notification device.
— Indicate the location of the Pull Station by displaying
the alarmed device and its location on the FACP.
— Transmits a Fire Alarm Signal to the designated U.L.
Certified Central Station.
WATERFLOW DETECTOR
Activation of Waterflow shall initiate the following functions:
— Generate an audible signal at the Fire Alarm Control Panel
— Generate an audible signal simultaneously on all areas of
the building by means of Horns devices. Generate a visual
alarm signal simultaneously on all areas of the building by
the use of Strobe devices or combination Horn /Strobe
notification device.
— Indicate the location of the Waterflow Detector by displaying the
alarmed device and its location on the FACP.
— Activate the outdoor Sprinkler Bell.
— Transmits a Fire Alarm Signal to the designated U.L.
Certified Central Station.
TAMPER SWITCHES
Activation of Tamper Switches shall initiate the following
functions:
— Generate an audible supervisory signal at the FACP.
— Indicate the location of the Tamper Switch by displaying.
the activated device and its location on the FACP.
— Transmits a Supervisory Signal to the designated U.L.
Certified Central Station.
DUCT DETECTOR
Activation of Duct Detector shall initiate the following
functions:
— Generate an audible supervisory signal at the FACP.
— Indicate the location of the Duct Detector by displaying
the activated device and its location on the FACP.
— Shut down the AHU.
— Transmits a Supervisory Signal to the designated U.L.
Certified Central Station.
TROUBLE
— Indicate the location of trouble signal at the FACP.
— Generate an audible signal at the FACP.
— Transmits a Trouble Signal to the designated U.L. Certified
Central Station.
DIGITAL ALARM COMMUNICATION TRANSMITTER (DACT)
— The DACT shall be provided with (2) telephone lines. The
telephone lines shall first be connected to the DACT and
then to the rest of extensions.
— Upon a signal received by the DACT from the FACP, the
DACT shall immediately seize the telephone line, abort any
current telephone session and terminates any incoming
call. Within 90 seconds, the DACT shall call first programmed
number of the designated U.L. Listed Central Station on the
primary telephone line and report the event.
— If the primary telephone line 1 fails to provide a dial tone
or, for any reason, is unseccessful in completing the
transmission, the DACT shall excercise telephone line 2 as
per NFPA -72. Telephone line 2 is the backup line.
FLOW BELL NOTES:
- FLOW BELL SHALL SOUND UPON ACTIVATION OF FLOW SWITCH ONLY
- FLOW BELL SHALL SOUND AS LONG AS WATER IS FLOWING
- FLOW BELL SHALL NOT BE CAPABLE OF BEING SILENCED FROM FACP
nA ODI
Z
61
Z
U
BLOC
f °IRE 8V �Fr�A[ /::. Zlwe
Al
FIRE ALARM SHALL BE A CENTRAL
S "f�7iC.1 -:` RMCt . i CERT ;F iCN r
C,� PLACARD SHALL EIE P:;LTED AT
FINAL 1t,SFEC T iON, AS PER NFPA 72
FIR,. At�APM SYSTEM TO BE
j.N TALLE U 7ia Lv,-- old D,�jgcL wiTli
Ni,t A 72; 70; 101
���gmw\-
7963 N.W. 14th STREET
DORAL, FLORIDA 33126
TEL : 305.477.9640
FAX: 305.477.1083
www.WSEFS.com
LICENSE #: EC- 0001652
@NOTIFIEFe
by Honeywell
APPROVIM
FM
ENGINEERING:
Carlos Rodriguez, P.E.
LIC. #G5G87
8101 S.W. 104th STREET
MIAMI, FLORIDA 33156
PHONE: (786) 390 -8213
W
Z
U
C)
W
:2
cn
c_
ENGINEERING:
Carlos Rodriguez, P.E.
LIC. #G5G87
8101 S.W. 104th STREET
MIAMI, FLORIDA 33156
PHONE: (786) 390 -8213
Rev151on5:
VA
\1
�m
Im
N (V/
_ 0
� lL
cn Q
Ln
n _
G) �.
LIB
,O
( J
Q 01 .27.2014
Plan review comments
drawn by: L.C.
date: 07.24..2013
project #: 13 -0724
scale: a5 shown
FIRE ALARM
SYSTEM
7
Y
�i
-ll
S:
ev
eK�
Oct
6
W
Z
U
W
:2
W
Q
J
O
z
z
N
N
N
L
Q
O
u-
n/
z
W
U
z
O
W
UIL.
Rev151on5:
VA
\1
�m
Im
N (V/
_ 0
� lL
cn Q
Ln
n _
G) �.
LIB
,O
( J
Q 01 .27.2014
Plan review comments
drawn by: L.C.
date: 07.24..2013
project #: 13 -0724
scale: a5 shown
FIRE ALARM
SYSTEM
7
Y
�i
-ll
S:
ev
eK�
Oct
6