Loading...
14-184-006BATTERY CALCULATION - FACP - NOT[ fIRE NFW2 -100 Device Type City. Standby / Device (Amp) Alarm / Device (Amp) Total Standby Current (Amp) Total Alarm Current (Amp) Main Board 1 0,14500 0.27500 0.145000 0.275000 ANN -80 Remote Annunciator 1 0.03700 0.04000 0.037000 0.040000 FDU -80 Remote Annunciator 0 0,02500 0.06400 0.000000 01000000 NP -100 Smoke Detector 11 1 0.00030 2.663225 0.003300 NAG / Output #3 NOT-13G 12LX Pull 5tation 12 1 0.00023 14 0,002760 NAG / Output #4 NH -100 --Heat Detector 6 0100030 NAG 4 0.001800 NAG if Output #4 DNR -100 Duct Detector 1 0.00030 0.065000 0.000300 1 NMM- I COP Monitor Module 24 0.00038 1,560000 0.009120 NC- I OOR Control Relay B 0.00027 1.560000 0.002160 ALL Addressable devices 1 Time (24 Hours) 0.40000 1.8231 0.40000 NAG # 1 1 A/H required Alarm 1.1700 2,19 1.170000 NAG # 2 1 Time (5 Minutes) 1.7350 4.0 A/H 1.735000 NAG # 3 1 1.7220 1.722000 NAG # 4 1 0.0120 1.8768 2 25 0.012000 Totals 0.201440 5.354000 Derating factor (1.2) A/H Required 5tandb1 Time (24 Hours) 4.834560 USE BATTERY SIZE 4.0 A/H A/H Required Alarm Time (5 Minutes) 0.449736 5ub Total Standby/ Alarm (Amp /hm) 5.284296 Multiply by the derating Factor ( I .2) 6.34 USE BATTERY 512E 7.0 A/H BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER SUPPLY # I Device Type Qt,, Standby/ Device (Amp) Alarm / Device (Amp) Total Standby Current (Amp) Total Alarm Current (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5upervision Relay 0 0.025 0.025 0.0000 0.000000 NAG / Output # I 1 0.025 0.572 0.0000 0.572000 NAG / Output #2 1 1 0.921 2.663225 0.921000 NAG / Output #3 1 1 0,573 14 0,573000 NAG / Output #4 1 2,960462 0.921 NAG 4 0.921000 NAG if Output #4 1 14 Totals 0.065000 3.132000 1 20.39 0 A/H required 5tandby Time (24 Hours) 1,560000 3.771000 Q LL_ A/H required Alarm Time (5 Minutes) 1.560000 0.263088 Time (24 Hours) Sub Total 5tandby/ Alarm (Amp/ Hr5) 1.8231 U z A/H required Alarm Multiply by the Deratmg factor (1.2) 2,19 4.639 Time (5 Minutes) USE BATTERY SIZE 4.0 A/H BATTERY CALCULATION - NOTIFIER FCP5 -2458 - POWER 5UPPLY #2 Device Type Qt,. Standby / Device Alarm / Device Total Standby Total Alarm Current DI (Ft)Ce Voltage (Amp) (Amp) Current (Amp) (Amp) Main Board 1 0.065 0.145 0.065000 0.145000 Power 5upervi5ion Relay 0 0.025 0.025 0.0000 01000000 NAG / Output # I 1 250 1.183 2.663225 1.183000 NAG / Output #2 1 1,722 1.039 14 1.039000 NAG / Output #3 1 2,960462 1.404 NAG 4 1.404000 NAG if Output #4 1 14 0.000 150 0.000000 1 20.39 0 Totals 0.065000 3.771000 Q LL_ A/H required 5tandby 1.560000 Time (24 Hours) W U z A/H required Alarm TOTALS 0.316764 4.639 Time (5 Minutes) U Sub Total Standby / Alarm (Amp /Hrs) Multiply by the 1.8768 2 25 Derating factor (1.2) USE BATTERY SIZE 4.0 A/H P.A.C.P. - VOLTAGE DROP CALCULATION - NFW2 -100 Vd= 2 x D(Ft) x DC Re515t(Ohrn/ft) x I(Amp) Circuit Description Maximum p� avid Cur(eAmp)Load Volt (Volts) (AWG)) DC(ROhs�Ftj ce DI (Ft)Ce Voltage Voltage Drop ndincj NAG I 2.5 1.170 16 - 33 14 0.00307 310 20.4 2.226978 28 NAC 2 2.5 1.735 16 - 33 14 0,00307 250 20.4 2.663225 17.74 NAC 3 2,5 1,722 - 14 .00 0 280 20.4 2,960462 17.44 NAG 4 2.5 0.012 16 - 33 14 0.00307 150 20.4 1 20.39 0 � 0 Q LL_ M Z W U z TOTALS 6,0 4.639 L ! L U P5- I - VOLTAGE DROP CALCULATION - FCP5 -2458 Vd= 2 x D(Ft) x DC RC515t(0hM/ft) x I(Amp) Circuit Description Maximum Load (Amp) Current Load (Amp) Voltage Range (Volts) Wire Size (AWG) DC Re515tance (Ohm/Ft) D15tance (Ft) Starting Voltage Voltage Drop Ending Voltage NAC I 3.0 0.572 16 - 33 14 0.00307 295 20.4 1.036064 28 NAG 2 3.0 0.921 16 - 14 0,00307 435 20.4 2.459899 17.94 NAG 3 3.0 0.573 16 14 .00 0 305 20.4 1.0723 17.04 NAG 4 3,0 0.921 - 14 0,00307 445 20.4 2.516448 20.40 0 � 0 Q LL_ M Z W U z TOTALS 1 8,0 8 L ! L U P5 -2 - VOLTAGE DROP CALCULATION - FCP5 -2458 Vd= 2 x D(Ft) x DC RC515t(0hm/fQ x I(Amp) Circuit Description Maximum Load (Amp) Current Load (Amp) Voltage Range (Volts) Wire 51ze (AWG) DC Re515tance (Ohrr✓Ft) Distance (Ft) Starting Voltage Voltage Drop Ending Voltage NAC I 3.0 1.183 16 - 33 14 0.00307 375 e Control Relay 28 NAG 2 3.0 1.039 16 - 33 14 0,00307 300 20.T- 1.913838 4 -1 /2 114 NAC 3 3.0 1.404 - 14 1 2 -1 13 -305 390 20.4 3.362018 17.04 NAC 4 3.0 1 �2 �1() 16 - 33 z 0.00307 p 20.T__ 0.000000 20.40 0 � 0 Q LL_ M Z W U z TOTALS 8.0 W L ! L U CABLE USES AND PERMITTED SUBSTITUTIONS FOR POWER - LIMITED FIRE ALARM CABLES CABLE TYPE USE REFERENCES PERMITTED SUBSTITUTIONS FPLP POWER - LIMITED FIRE ALARM PLENUM CABLE 760.61 (A) CMP FPLR POWER- UMITED FIRE ALARM RISER CABLE 760.61 (B) CMP, FPLP, CMR FPL POWER- UMITED FIRE ALARM CABLE 760.61 (C) CMP, FPLP, CMR, FPLR, CMG, CM SCOPE OF WORK INSTALLATION OF NEW FIRE ALARM SYSTEM No. Devices Description F Rating Hr Fire Alarm Control Panel 2 Fire Control Power Supply 1 Remote Annunciator 1 I Smoke Detector 6 beat Detector 12 Pull Station 24 Monitor Module e Control Relay 28 Horn/Strobe 44 Strobe Light I Sprinkler Bell I Duct Detector 1. THESE UNITS OR DEVICES SHALL BE INSTALLED USING APPOVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE N.E.C. # 70 AND THE NATIONAL FIRE PROTECTION ASOCIATION ARTICLE if 760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL WIRING ORDENANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE # 760 POWER LIMITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCTORS SHALL HAVE A MINIMUM RATING OF 300 VOLTS AND SHALL BE OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. 3. ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER N.E.C. ARTICLE # 760 -61. 4. FPLP OR FPLR SIGNAL CABLE FOR USE IN ACCORDANCE NTH N.E.C. ARTICLE 760 AND N.E.C. ARTICLE 725 CLASS 2 OR 3 CIRCUIT. 5. MINIMUN CABLE SIZE: A - # 18 AWG COPPER ( #18 FPL OR FPLP) FOR INITIATING CIRCUITS. B - # 16 AWG COPPER ( #16 FPL OR FPLP) FOR SIGNAL CIRCUITS. 6. CONDUCTORS USED IN DUCTS OR PLENUM CEILINGS FOR ENVIRONMENTAL AIR SHALL EMPLOY THE USE OF ELECTRICAL METALLIC TUBING OR PLENUM TYPE CABLE WHICH MEETS THE REQUIREMENTS OF THE NATIONAL PROTECTION ASSOCIATION AND ARE U.L LISTED OR COMPATIBLE FOR THIS USE. 7. CONDUIT FILL 41X OR LESS. 8. PENETRATIONS: AS NOTED ON DETAIL 9. THE LOCATION OF AUDIBLE DEVICES SHALL BE DESIGNED TO BE EFFECTIVELY HEARD 15 DB. ABOVE AMBIENT NOISE LEVEL OBTAINED UNDER NORMAL CONDITION OF OCCUPANCY AS PER ARTICLE 7.4.2 OF THE NFPA 72 2007 EDITION. 10. PULL STATIONS SHALL BE INSTALLED AT 48" (CENTER) A.F.F. AS PER ARTICLE 4.2.5 OF THE FLORIDA ACCESIBIUTY CODE FOR BUILDING CONSTRUCTION 2007 EDITION. 11. ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN 3' -0" FROM A/C DIFUSERS. 12. VISUAL DEVICES SHALL BE INSTALLED 80" A.F.F. PER ARTICULE 11.4.28.3 OF FLORIDA BUILDING CODE 2007. 13. ALL EQUIPMENT TO BE INSTALLED SHALL BE COMPATIBLE, NEW AND U.L USTED FOR USE IN FIRE ALARM SYSTEMS. 14. THIS SYSTEM SHALL BE POWER LIMITED AND ALL EQUIPMENT SHALL BE RATED POWER LIMITED 15. THE INSTALLATION OF THIS FIRE ALARM SYSTEM SHALL COMPLY WITH: A FLORIDA FIRE PREVENTION CODE (FFPC) 2010 EDITION. B FLORIDA BUILDING CODE (FBC) 2010 EDITION. C NFPA 1, 2009 EDITION "FIRE CODE ". D NFPA 101, 2009 EDITION, "LIFE SAFE CODE". E NFPA 72, 2007 EDITION "NATIONAL FIRE ALARM CODE ". F) NFPA 70, 2008 EDITION "NATIONAL ELECTRICAL CODE". 16. THIS FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 17. CONNECTIONS (120 VOLTS) TO FIRE ALARM CONTROL PANEL AND POWER SUPPLIES SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING. SHALL BE ACCESIBLE ONLY TO AUTHORIZED PERSONAL, AND SHALL BE IDENTIFIED "AS FIRE ALARM CIRCUIT" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM PANEL I& CONTROL PANEL AND ANY NECESARY POWER SUPPLY SHALL BE LOCATED IN A MECHANICALLY VENTILED ROOM. 19. THE MAXIMUM HEIGHT TO THE TOP OF THE CONTROL PANEL AND ANY INSTALLED POWER SUPPLY SHALL NOT EXCEED 6' -0" ABOVE THE FINISij--3 FLOOR. 20. RECORD OF COMPLETION WILL BE PREPARED BY WORLD SECURITY & ELECTRIC, INC., AND A COPY WILL BE PROVIDED TO THE OWNER AND TO THE CITY FIRE RESCUE DEPARTMENT. 21. THE FOLLOWING DOCUMENTATION WILL BE ON SITE UPON THE FINAL ACCEPTANCE TEST OF THE SYSTEM: - OWNER'S MANUAL AND INSTALLATION INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT. - RECORD DRAWINGS. NOTES: A. CEILING HEIGHT. EXCEPT PARKING AREA IS LESS THAN 12' -0 ". B. THIS SYSTEM WILL BE "CERTIFIED OR PLACARDED" AS A "CENTRAL STATION SERVICE" FIRE ALARM SYSTEM AND WILL BE PROVIDED WITH 24 HOURS OF POWER SUPPLY. THE METHOD OF COMMUNICATION MALL BE VIA TELEPHONE LINES C. BUILDING IS FULLY SPRINKLERED. ,Q.,�HIS IS A 4 STORY NEW BUILDING WITH APROX. 63,000 SQ.FT. E. ALL NACe SHALL BE CLASS B - STYLE Y. F. SLC SHALL BE CLASS B - STYLE 4. N M System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 X. 1C 16 A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) galy steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark Ti No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM /sq ft W- Rating - Class 1 (See Item 4) 1. Floor or wall Assembly - Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. (114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow core Precast Concrete Units *. when floor is, constucted of hollow core precast concrete inits, packin material (Item 3) and caulk fill material (Rem 4) to be installed symmetrically on both sides of floor, flush with flor surface. Wall assembly may also be constucted of any UL Classified oncrete Blocks *. Max diam of opening in solid lightweight or normal weight concrete floor is 32 in (813mm ).Max diam of opening in floor constructed of See Concrete Blocks (CA� and Precast Concrete Units (C categories in the ire Resistance Directory for names of manufacturers. 1A.Steel Sleeve - (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mm above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop system.Max annular space be between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in item 4.Min annular space between ppipe or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4. pe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in. (762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in. 1 2mm diam or smaller rigid steel conduit.. D. Conduit -Nom 4 in. 102mm3 diam kor smaller) steel electrical metallic tube. E. Copper Tubing -Nom Sin. 152 diam or smaller) Type L or heavier copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass i r insulation firmly packed into open' s permanent f .Pa kung material to be recessed from top surface of floc or fro both surfaces of wall as requlre� �0 accommoTaatne he required thickness of caulk fill material item 41 RForminq Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min 1/2 in 113mm) thick compressible mat to be stacked to a th' greater than the width od the annuls and compression -fined edge -W, to fill the annular space to a min 4 in.102mm) dept As an option, the strips of min 11 in 13mm) th' k corn re�siT�l folde in half, II gihwise, gnd stgckV. to g thirkn grater tf�an the wi �f tt e� annular space am roman- fitted, efrst, to I the annu space a min In. (tram) h. op of ormigg a to recessed Tram top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. F11, Void or Cavity Material - Caulk, Sealant - Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thickness to be installed symmetrical on both sides of wa ,flush with wall surface. At nt contact location between penetrant and sleeve or betwween penetrant ana concretes a min 1%4 in.(6mm) diam bead orccoulk shall be applied ast top surface of floor and at both surfaces of wall. The hoary F ralJV and the min regnured caulk thidmesses are dependent upon a number of parameters as shown in the following table: Min Floor or Wall Thkns In (mm) Nom Pipe Tube or Conduit Diam In (mm) Max Annular Space In. (mm) Thkns lnu{kmm l ) F Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /2( 3) 2 ■ 1 /2 -1(213 -30)53 3 -1 /4 83 1 2ti 2 4 114 1/2 1 -1 35 1! () 2 -1/2 -11 3-305 4 32 12 1 1 E 1 %2 -20 13 -508 51 213 3 4 -1 /2 114 1 /2 -20 13 -508 2� 1 - 1�1 3 IN 1 2 -1 13 -305 i4 1 5 M System No. W -L -1413 February 07, 2007 F- Rating - 1 and 2 Hr (See Item 1) T- Rating - 0 Hr A 1 3 3 2 2 X. 1C 16 A Section A -A 1.Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Steel Studs - "C -H" or "C -T" shaped studs, min 2 -1/2 in (64 mm) wide by 1 -1/2 in (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) galy steel, spaced max 24 in (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max. diam of circular cutout in gypsum liner panel is 10 in.(254mm) C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Pertition Design. Max diam of circular cutout in gypsum board is 10 in.(254mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which is installed. 2.Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be minimum 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 8 in (203 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 8 in. (203 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in diam (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. D. Copper Tubing - Nom 6 in. (152 mm)diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe 3. Fill, Void or Cavity Material* Caulk as sealant - Min 1 in. (25 mm) thickness of fill material applied within the gypsum board liner panel flush with the faces of the liner panel. Min 5/8 in. (16 mm) thickness of fill material applied within the gypsum board annulus, flush with the finished side of the wall. Min 1/2 in. (13 mm) diam beadof caulk applied to penetrant /gypsum board interface at the point contact location on the finished side of the wall 3M COMPANY - CP25WB+ Caulk or FB -3000 WT Sealant *Bearing the UL Classification Mark Ti No. C -AJ- March 15, 2007. F- Rating -2,3 and 4 Hr (See Items 2A and 4) T- Rating - 0 Hr L- Rating at Ambient - Less than 2 CFM /sq ft L- Rating at 400 F - Less than 1 CFM /sq ft W- Rating - Class 1 (See Item 4) 1. Floor or wall Assembly - Lightweight or normal weight(100 -150 pef or 1600 -2400 Kg /m3) concrete. Except as noted in table under item 4, min thickness of solid concrete floor or wall assembly is 4 -1/2 in. (114mm). Floor may also be constructed of any min 6 in.(152mm) thick UL Classified hollow core Precast Concrete Units *. when floor is, constucted of hollow core precast concrete inits, packin material (Item 3) and caulk fill material (Rem 4) to be installed symmetrically on both sides of floor, flush with flor surface. Wall assembly may also be constucted of any UL Classified oncrete Blocks *. Max diam of opening in solid lightweight or normal weight concrete floor is 32 in (813mm ).Max diam of opening in floor constructed of See Concrete Blocks (CA� and Precast Concrete Units (C categories in the ire Resistance Directory for names of manufacturers. 1A.Steel Sleeve - (Optional, Not Shown) -Nom 16 in (406mm) diam (or smaller) Schedule 10 (or heavier) steel sleev cast or groute Int floor or wall assembly. Sleeve may extend a max of 2 in 151mm above top of floor or bevond either surface of wallAs an alternate, nom 16 in (406mm) diam (or smaller) min 0.028(0.71mm) thick galvanized sheet sleeve cast or grouted into floor or wall assembly flush with floor or wall surfaces. 2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccntrically within the fire stop system.Max annular space be between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in item 4.Min annular space between ppipe or conduit and edge of through opening is 0 In (point contact). Max annular space to be as shown in the table in item 4. pe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe -Nom 30in.(762mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -Nom 30in. (762mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -Nom 6 in. 1 2mm diam or smaller rigid steel conduit.. D. Conduit -Nom 4 in. 102mm3 diam kor smaller) steel electrical metallic tube. E. Copper Tubing -Nom Sin. 152 diam or smaller) Type L or heavier copper tube. F. Copper Pipe -Nom 6 in.(152mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Packing Material- Polyethlene backer rod or nom 1 in.(25mm) thickness of thighly- packed mineral wool batt or glass i r insulation firmly packed into open' s permanent f .Pa kung material to be recessed from top surface of floc or fro both surfaces of wall as requlre� �0 accommoTaatne he required thickness of caulk fill material item 41 RForminq Material * -As an alternate to the packing material in Item 3, nom 4 in.(102mm) wide strips of min 1/2 in 113mm) thick compressible mat to be stacked to a th' greater than the width od the annuls and compression -fined edge -W, to fill the annular space to a min 4 in.102mm) dept As an option, the strips of min 11 in 13mm) th' k corn re�siT�l folde in half, II gihwise, gnd stgckV. to g thirkn grater tf�an the wi �f tt e� annular space am roman- fitted, efrst, to I the annu space a min In. (tram) h. op of ormigg a to recessed Tram top su ace of floor or from both surfaces of wall as necessary to acommodate the required thickness of caulk fill material. 3M COMPANY -Fire Barrier Packing Material 4. F11, Void or Cavity Material - Caulk, Sealant - Applied to fill annular space flush with the top surface of floor. In wall assembly required caulk thickness to be installed symmetrical on both sides of wa ,flush with wall surface. At nt contact location between penetrant and sleeve or betwween penetrant ana concretes a min 1%4 in.(6mm) diam bead orccoulk shall be applied ast top surface of floor and at both surfaces of wall. The hoary F ralJV and the min regnured caulk thidmesses are dependent upon a number of parameters as shown in the following table: Min Floor or Wall Thkns In (mm) Nom Pipe Tube or Conduit Diam In (mm) Max Annular Space In. (mm) Thkns lnu{kmm l ) F Rating Hr 2 -1 /2 64 1 /2 -12 13 -305 1 -3/8 35 1 /2( 3) 2 2 -1 /2 64 1 /2 -1(213 -30)53 3 -1 /4 83 1 2ti 2 4 114 1/2 1 -1 35 1! () 2 -1/2 -11 3-305 4 32 12 1 1 4 -1 %2 114 1 %2 -20 13 -508 51 213 3 4 -1 /2 114 1 /2 -20 13 -508 2� 1 1 25 3 4 -1/2 114 1 2 -1 13 -305 3-11Y4 83) 1 5 3 5 -1 72 140 12 23 016-152) 1? 38 35) 1 �2 �1() 4 a Min 2 in.(51mm) thickness of mineral wool butt insulation of forming material (Item3A) required in annular space b n 1 in.(25mm) thidmess of mineral wool bott insulation required in annular space of both sides of floor or wall assembly c)Min 1 in.(25mm) thickness of caulk) to be installed flush with each surface of floor or wall assembly 3M COMPANY - CP25WB+ or FB -3000 WT (Note: W Rating applies only when FB -30OWT is used) *Bearing the UL Classification Marking This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory ou - ill`- .C3•�. COLiCYaTY' F`s�'�= AR i MB� ML. .t r ....• _ FIRE 3UP RES�IOh +4-- FIRE ALARri4 SHA1_i.. SE A CENTRAL sTATICii REF "t11C A C�:R Tif=1C:-<_ OR PLACARD SHALL Kz POSTED faf FINAL INSPi✓CTION, AS PER Nl P_ A 72 M gySTF'M TO Bt FIRE ALAR - : dCLw 1, A72,70; 101 085 & SECURITY SYSTEMS 7963 N.W. 14th STREET DORAL, FLORIDA 33126 TEL : 305.477.9640 FAX: 305.477.1083 www.WSEFS.com LICENSE #: EC- 0001652 (�� NOTIFIEFe by Honeywell APPROVEID FM r• W �` uJ c til t• . il/ _ y• ENGINEERING: Carlos Rodriguez, P.E. LIC. #65687 8 10 1 5.W. 1 04th STREET MIAMI, FLORIDA 33156 PHONE: (78G) 390 -8213 Revi5ion5: Di 01 .27.2014 Plan review comments drawn by: L.C. date. 07.24..2013 project #: 13 -0724 scale: as shown FIRE ALARM SYSTEM FA -6 sheet 6 of 7 W z U W L m W �m � > Q Q N F 0 2 z �Q z m2 L 0 � 0 Q LL_ M Z W U z O W L ! L U Revi5ion5: Di 01 .27.2014 Plan review comments drawn by: L.C. date. 07.24..2013 project #: 13 -0724 scale: as shown FIRE ALARM SYSTEM FA -6 sheet 6 of 7